Generator Failure
10.6.16
Kapitel/Chapter 8: Generator Failure - Seite/Page 119
Fig. 8.5.1-1: Capacitor
1) Switch off generator
2) Disconnect starter battery
3) Open AC-Control box
The capacitors are discharged, by short circuit the two contacts. In addition use the cone end of an isolated
screwdriver.
8.5.2 Checking the Capacitors
ATTENTION!
Before working (installation) on the System read the
section „Safety Instructions“ in this Manual.
Do not check the capacitors whilst the generator motor is running! Charged capacitors can be lethal. Do not contact
the capacitors with bare fingers or non-insulated metallic objects! In order to test the capacitors, the terminal lead
wires have to be disconnected using pliers or a screwdriver with insulated handle(s). Once the wires have been
removed, the capacitors must discharged by bridging the capacitor terminals together with a slot screwdriver with an
isolated handle.
Fig. 8.5.2-1: Capacitor
Discharge the capacitor
1. Screw driver blade
2. Capacitor connections
3. Capacitor
The capacitors can be checked using a normal multimeter with a continuity beeper. Check that the multimeter
„beeps“ when the selector is set to continuity and the end probes are contacted together.
1
2
3
Summary of Contents for 10000x
Page 10: ...Seite Page 10 Kapitel Chapter 2 10 6 16 Leere Seite Intentionally blank...
Page 96: ...Installation Instructions Seite Page 96 Kaptitel Chapter 5 Installation Instructions 10 6 16...
Page 148: ...Seite Page 148 Kapitel Chapter 9 Appendix 10 6 16 Leere Seite Intentionally blank Appendix...
Page 149: ...Panda_xControl_eng R01 5 10 6 16 Panda xControl Manual...
Page 189: ...Panda xControl 10 6 16 Kapitel Chapter 11 Panda xControl Seite Page 189...