5.9.4 VCS voltage control
All Panda generators from Panda 8000 upwards are fitted with the electronic voltage control "VCS" as standard.
The VCS controls the generator voltage and motor speed. A actuator on the injection pump can increase the engine
speed by up to 8%.
If the generator is run without load, the voltage should be 231V with a frequency of approx 48.5 to 49Hz. The fre-
quency (equates to the speed) can be increased by up to 8%. This ensures that the engine speed is increased when
there is an extra load. The maximum speed is achieved when 80% load is reached.
The speed gauge is governed by an adjusting screw, above and below. Adjustment of this screw may not occur wit-
hout the expressive approval of the manufacturer.
All signals pass through the circuit board in the AC-Control box. The signal impulse for the actuator is passed to the
electric motor by means of the 5 core wire.
The generator maintains its full capability if the VCS has a defect.
In this case the base current must be raised to at least 240 V by adjusting the minimum setting on the speed gauge,
in order to ensure that the generator output voltage at 70% nominal load does not drop below 215 V.
Fig. 5.9.4-1: VCS Control
1
6
5
4
2
3
7
1. Connection measuring voltage
2. Adjusting booster voltage (do not adjust!)
3. Adjustment VCS-voltage
4. Connection VCS inlet
5. Electrical fuse (1.6 A, slow to blow)
6. Potentiometer for booster time