5.8.11 Recording submenu
The control can record 10 data sets internally
on a rolling basis (Recording submenu,
parameter 1 set to „On“). Snapshots of the
unit status are carried out at intervals of 10 s,
which can be helpful for troubleshooting.
When all memory slots are filled, a new set of
data overrides the oldest entry. A recorded
set of data is conserved for a period of max.
7 days.
The complete record [93] can be saved to a
USB stick with NTFS formatting.
For saving, pls. proceed as follows:
»
Call up recording submenu.
»
Set parameter „Saving_start“ (2) to
„On“.
»
Insert USB stick in connector on
mainboard (s. drawing below). Sav-
ing starts automatically. Then,
parameter „Saving_start“ returns to
the „Off“-state.
By looking at parameter „Saving_status“ (4)
the status of the saving procedure can be
checked. „Activated“ means that writing to
the memory stick is underway.
Erasing of the complete memory is achieved
by setting the „Recording_delete“ parameter
(5) to „On“.
A data set consists of the following values:
USB connector on mainboard
No.
Value
only
1
Steam_actual_unit
2
Steam_actual_Cyl. 1
DZG
3
Steam_actual_Cyl. 2
DZG
4
Status_unit
5
Status_cyl. 1
6
Status_cyl. 2
DZG
7
Fault message_unit
8
Fault message_cyl. 1
9
Fault message_cyl. 2
DZG
10
Safety interlock_open
11
Demand
12
Steam_output_max.
13
Current_actual_Cyl. 1
ELDB
14
Current_actual_Cyl. 2
ELDB DZG
15
Water_level_cyl. 1
HKDB
16
Water_level_cyl. 2
HKDB DZG
17
Humidity_actual value
18
Humidity_set value
19
Humidity_actual_value_max
MB
20
Humidity_set_value_max
MB
Legend:
ELDB = Electrode Steam Humidifier
HKDB = Heater Element Steam Humidifier
DZG = Double Cylinder Unit
MB= Variable Max. Limitation