![fisair DFRIGO Series User Manual Download Page 44](http://html1.mh-extra.com/html/fisair/dfrigo-series/dfrigo-series_user-manual_2294097044.webp)
DFRIGO User Manual |
Document subject to change without prior notice.
44
8.10 Supervision menu
Menu displays the operation of the main components, the
temperature and humidity values and the unit's incidents or
alarms on the main screen.
Press
to access
This is the main pre-set screen.
It activates automatically after 60 seconds have elapsed.
The flashing arrows indicate the operation of the process
(dry air) fan motor, the rotor motor (rotor turning) and of the
reactivation fan motor (wet air).
The reactivation battery temperature measured by the ST1
probe appears in the top right corner of the screen.
In the event of an incident or alert in the unit, a warning
triangle will appear, followed by the name or number of the
alert. For the alarm origin and the recommended action, see
section "List of equipment alarms".
In the "M" measurement signal configuration, the value
measured by the relative humidity probe will also be shown
on the main screen.
If the value measured by the probe is higher than the sum
total of the set point and the alarm entered in the adjustments
menu, an alarm bell icon will flash on the screen (maximum
humidity alert).