INSTALLATION
INSTRUCTIONS
FA162C
2-PARTITIONED SECURITY SYSTEM
Principal changes between the FA162C and the
former FA160C are indicated by margin lines.
N7526-1V3 8/97
Page 1: ...INSTALLATION INSTRUCTIONS FA162C 2 PARTITIONED SECURITY SYSTEM Principal changes between the FA162C and the former FA160C are indicated by margin lines N7526 1V3 8 97...
Page 2: ...n alarm in the hallway outside may not wake up the sleeper if the door is closed Install a smoke detector inside bedrooms where electrical appliances such as portable heaters air conditioners or humid...
Page 3: ...ing Off Fire Alarm Sounding 18 Wiring 4 Wire Smoke Combustion Detectors on Zones 2 7 18 Wiring 2 Wire Latching Type Glass Break Detectors on Zone 8 19 Check Out Procedure for Hard Wired Zones 20 Secti...
Page 4: ...ield 43 Reviewing a Data Field Erasing an Entry in a Data Field 44 Interactive Mode Programming 56 80 82 and 83 44 Loading Factory Defaults 44 Programming System Setup Fields 44 Exiting the Programmin...
Page 5: ...11 Figure 4 Telephone Line Connections 12 Figure 5 Connection of 4300 Transformer to the Control Board 13 Figure 6 Keypad Connections to the Control Board 15 Figure 7 Using a Supplementary Power Supp...
Page 6: ...perational difficulties This symbol indicates a critical note that could seriously affect the operation of the system or could cause damage to the system Please read each warning carefully This symbol...
Page 7: ...5881 5882 in Canada type RF Receiver as indicated below Receiver Model No of Zones 5881L 5882L Up to 8 5881M 5882M Up to 16 5881H 5882H Up to 30 Requires the use of 5800 series wireless transmitters T...
Page 8: ...sarmed in time an alarm will sound and an Exit Error report sent to the central station An Exit Alarm condition will also occur if an Entry Exit or Interior zone re opens within 2 minutes after the en...
Page 9: ...ection Auxiliary Power Output Provides 12VDC 600 mA maximum Uses current limiting circuitry for protection This output interrupts for smoke detector reset if 4 wire smoke detectors are used Programmin...
Page 10: ...Do not locate the cabinet in an area of high RF interference revealed by frequent or prolonged lighting of the LED in the receiver after it is operational random flicker is OK Installing the Lock if...
Page 11: ...of the cabinet as shown in Detail A in Figure 3 Make sure that the board rests on the correct row of tabs as shown 3 Swing the base of the board into the mounting clips and secure it to the cabinet wi...
Page 12: ...E LINE MONITOR HAS BEEN PROGRAMMED IN FIELD 92 Figure 4 Telephone Line Connections Wiring The AC Transformer 1321 Wire the 1321 transformer to terminals 1 and 2 on the control board See wiring table b...
Page 13: ...nstructed to do so later in the manual 1 Place the 12 volt back up battery in the control cabinet 2 Attach Red and Black wires on the battery connector cable as follows a Red to the positive battery t...
Page 14: ...used for each wire size Current draw for all devices can be found in the SPECIFICATIONS AND ACCESSORIES section Note Refer to Auxiliary Device Current Draw Worksheet in the FINAL POWER UP section for...
Page 15: ...it for specific information Using a Supplementary Power Supply to Power Additional Keypads The control provides 600mA for powering keypads up to a maximum of 4 per partition and other devices from the...
Page 16: ...ugging the AC transformer previously wired to the control into a 120VAC outlet 3 Busy Standby Alpha keypads or dI Fixed word keypads will be displayed After approximately 1 minute the green READY LED...
Page 17: ...em may not respond to an open circuit on the zone High Resistance Supervision on Hard Wired Zones 2 8 Special supervision in the control senses high resistance on hard wired zone loops 2 8 causing a w...
Page 18: ...FOR FIRE Figure 8 2 Wire Smoke Detector Connected to Zone 1 Wiring 4 Wire Smoke Combustion Detectors on Zones 2 7 The system will support as many 4 wire detectors as can be powered from Auxiliary Pow...
Page 19: ...tector Remove 2000 ohm EOL resistor if connected across the selected zone terminals Compatible Glass Break Detectors Use detectors that meet the following ratings Standby Voltage 5VDC 13 8VDC Standby...
Page 20: ...act the Alpha keypad connected to the system should display DISARMED READY TO ARM If the following is displayed DISARMED Press to show faults press the key to display the faulted zone s Restore any fa...
Page 21: ...ct the 4219 or 4229 module to the control s keypad terminals see diagram below 1 2 3 4 5 OFF ON ON e e h h h h h h e e e e e e e e e e e e e e e e e e e e e e e e e e e e e e g g g g g g 2 Set the 421...
Page 22: ...isplayed DISARMED Press to show faults press the key to display the faulted zone s Restore any faulted zone s as necessary also make sure that you have connected a 1000 ohm EOL resistor across the ter...
Page 23: ...K and zone 09 will also be displayed a If communication between the panel and the receiver is interrupted or b If no valid RF signals from at least one supervised wireless transmitter are received wit...
Page 24: ...uctions provided with the receiver for further installation procedures regarding antenna mounting etc MOUNTING HOLES INTERFERENCE INDICATOR LED CIRCUIT BOARD DIP SWITCH PLUG SOCKET INSERT IN RIGHT HAN...
Page 25: ...s On the 5816 for example the wire connection terminal block is loop 1 the reed contact is loop 2 Each loop must be assigned a different zone number UL The 5816 and 5817 transmitters do not have EOL s...
Page 26: ...life in a given installation The wireless system can identify a true low battery situation thus allowing the dealer or user of the system time to arrange a change of battery and maintain protection fo...
Page 27: ...release the test switch or momentarily short the contacts again 3 beeps will occur if the control has accepted the input code and a summary display showing the enrolled input loop No will appear 5816...
Page 28: ...nduct this test with your hand wrapped around the transmitter as this will cause inaccurate results Note On button type transmitters whose buttons have been set to Arm Away Arm Stay or Disarm pressing...
Page 29: ...ransformer Therefore if using Powerline Carrier Devices a 4300 transformer must be used in place of the regular system transformer Once a device is programmed into the system the user sees no differen...
Page 30: ...SABLING TAMPER COVER TAMPER REED SWITCH TB1 4204 TB2 4 PIN CONSOLE PLUG 12 11 10 9 8 7 6 5 4 3 2 1 C NC NO C NC NO C NC NO RELAY 3 RELAY 2 RELAY 1 RELAY 4 TYPICAL SHOWN OFF EITHER OR BOTH CAN BE USED...
Page 31: ...4142TR Cable Wire 4 Sync RED Pin 5 of 9 pin connector 5 Data VIOLET Pin 1 of 9 pin connector 6 Com WHITE Pin 4 of 9 pin connector 1 2 3 4 5 6 7 8 9 9 PIN CONNECTOR ON CONTROL BOARD BLACK BLUE BROWN G...
Page 32: ...st have Touch tone capability though Touch tone service is not necessary if premises uses PULSE dialing switchable phones must be set for Touch tone temporarily before attempting phone access A Phone...
Page 33: ...ls 1 through 5 on the Phone Module as shown in the Wiring Table below and in the FA4285 wiring diagram that follows Use an RJ31X jack with a direct connect cord and make all connections exactly as sho...
Page 34: ...RTH GROUND COLD WATER PIPE ETC NOT INSTALLER ADJUSTABLE UNUSED KEYED HEADER 4285 VOICE MODULE 1 2 3 4 5 6 7 YELLOW TO DATA OUT term 7 NO CONNECTION RED TO AUX term 5 BLACK TO AUX GROUND term 4 GREEN T...
Page 35: ...mpt HELLO ENTER PHONE CODE NOW The caller should enter the programmed 2 digit phone code If the premises phone system includes an answering machine the 2 digit phone code should be entered during a pa...
Page 36: ...ith use of an 8 ohm 30 watt speaker 745X3 Voice Siren Driver Voice siren driver with English Spanish and French voice messages Separate messages for Fire and Burglary Use with 8 ohm speaker UL Listed...
Page 37: ...he sounder output to trip 3 4 ALARM OUTPUT NO 702 SIREN CONTROL BOARD Figure 17 Typical Sounder Wiring Testing the Sounder After installation of the sounder is completed each partition of the Security...
Page 38: ...ine is supervised as well as certain functions in the radio If communication is lost or a trouble develops a message will be attempted to be sent via both radio and telephone to the central station Fo...
Page 39: ...phone number the control will trigger the AAV if at least one of the messages was an alarm report The control will send a listen in to follow message Contact ID event code 606 which signals the 685 to...
Page 40: ...RPOSE EAGLE SECURITY MODEL 1241 Figure 20 Connection Of AAV Unit When Not Using A FA4285 Phone Module 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 ON GND VDC RING TO TERM 22 TIP TO TERM 21 REFER TO AAV MODU...
Page 41: ...ED After approximately 1 minute the initial displays will revert to DISARMED READY TO ARM for Alpha keypads or READY for Fixed word keypads if there are no faulted zones This 1 minute delay allows PIR...
Page 42: ...ad a low battery message is displayed and if so programmed will be reported to the central station In addition the connection to the battery is checked every 3 minutes CSFM requirement If there is no...
Page 43: ...n the control 4 5 6 7 Also both partitions must be disarmed The Alpha keypad need not necessarily remain in the system after programming Programming can also be performed remotely from the installer s...
Page 44: ...pha Programming Zone alpha descriptors 83 Sequential Mode 5800 series transmitter serial numbers Loading Factory Defaults To load the factory defaults enter the programming mode press 97 then exit the...
Page 45: ...dock or basement door Type 03 Perimeter Burglary This zone type gives an instant alarm if the zone is faulted when the panel is armed in the Away Stay Instant or Maximum modes This zone type is usuall...
Page 46: ...grammed entry time if tripped when the panel is armed in the Away mode Entry delay begins whenever sensors in this zone are violated regardless of whether or not an entry exit delay zone was tripped f...
Page 47: ...stem 22 RF SYSTEM 0 0 no RF receiver being used 1 5881 5882 RF receiver being used 23 FORCED BYPASS FUNCTION Partition 1 0 Partition 2 0 0 no forced bypass 1 provide automatic bypass of all open fault...
Page 48: ...48 The data line is supervised as well as certain functions in the radio If communication is lost or a trouble develops a message will be attempted to be sent via both radio and telephone to the cent...
Page 49: ...t for a maximum of 20 seconds 37 AUDIBLE EXIT WARNING 1 1 0 no exit warning sound Part 1 Part 2 1 provide exit warning sound when armed AWAY Warning sound consists of slow continuous beeps until last...
Page 50: ...nter 0 as the first digit of a 4 digit account number for Nos 0000 0999 Exit field by pressing and press next field number if only 3 digits are used To clear entries from field press 43 44 45 or 46 Se...
Page 51: ...Options 6 9 send reports to the primary phone number and send reports to a pager which has its phone number entered as the secondary phone number in field 42 The pager report is a 10 digit code in the...
Page 52: ...rmat Enter a code in the first box 1 9 A B C D E or F Enter 10 for A this reports a 0 on some receivers 11 for B 12 for C 13 for D 14 for E 15 for F An entry of 0 in the first box will disable a repor...
Page 53: ...will be sent followed by the second digit of the programmed alarm code for that zone If 3 1 or 4 1 format is used only the digit entered in this field will be sent This message will go to the Primary...
Page 54: ...ous page Reports with Partition 1 Subscriber No 75 RF XMTR LOW BATTERY RESTORE CODE 0 0 See box This is sent when a transmitter that previously sent in a low battery message has sent a message indicat...
Page 55: ...Press first to enter 2 digit options UL installations must be 0 AAV disabled 92 PHONE LINE MONITOR ENABLE 0 0 Not used 1 Local keypad display only when phone line is faulted 2 Local keypad display pl...
Page 56: ...No No Enter 0 No Yes No Enter 0 No No Yes Enter 1 14 No Yes Yes Enter 15 See note at left OTHER PROGRAMMING COMMANDS 56 ZONE PROGRAMMING MODE Interactive menu mode used for programming zone attribute...
Page 57: ...hat you use as the program tool can also be used as a transmitter in the system If you plan to use an existing transmitter it must first be enrolled into the system as its associated zones You may the...
Page 58: ...nt Burglary Default values for zones 01 to 08 are Zone No Zn 01 02 03 04 05 06 07 08 Zone Type Default 09 01 03 03 03 03 03 03 Partition Default 1 1 1 1 1 1 1 1 Response Time Default 1 1 1 1 1 1 1 1 1...
Page 59: ...zone e g press a button open or close a door etc 10 INPUT S N L A002 4064 1 The system will enroll the serial number of the first transmitter heard add the loop number entered to this serial number d...
Page 60: ...he loop number you must go back through zone programming for that zone and manually enter the loop number over the existing one PROGRAM ALPHA 0 NO 1 YES 0 ENTER ZN NUM 00 QUIT 11 If you want to progra...
Page 61: ...e device These conditions apply only when a zone list is used The different choices for EVENT are listed below and in the Programming Output Relays Powerline Carrier devices section that follows ALARM...
Page 62: ...ic zone response type or system operation action can be selected to de activate the device If a specific ZONE TYPE is chosen any zone of that response type that restores from a previous alarm trouble...
Page 63: ...0 Enter the desired device action as listed below Press the key to continue 0 No response 2 Close and Stay Closed 1 Close for 2 seconds 3 Continuous Pulse on off 1 sec ON 1 sec OFF 02 Start Event Not...
Page 64: ...re faulted or when any 24 hour auxiliary zone is faulted We want to be able to turn off the lamp manually without affecting the arming status of the system To program this we would do the following In...
Page 65: ...the common zone is faulted but once armed the other partition cannot arm That partition must first bypass the common zone or correct the fault before arming Either partition can clear and restore the...
Page 66: ...196 words stored in memory see a following page In addition up to 10 installer defined words can be added to those already in memory Thus when an alarm or trouble occurs in a zone an appropriate descr...
Page 67: ...display for that zone will appear You must then press plus the same zone number again to gain access to the entry mode flashing cursor for that zone Flashing Cursor ZN 01 B ACK ZN 01 BACK Flashing Cur...
Page 68: ...s in memory Summary Display ZN 01 BACK DOOR The flashing cursor will disappear indicating that the word s are stored in memory for that zone as shown in the summary display at the left 11 To enter a d...
Page 69: ...enter 02 etc A cursor will now appear at the beginning of the second line 3 Refer to the CHARACTER LIST of letters numbers and symbols on a following page Press the key followed by the two digit entry...
Page 70: ...ER 148 PHONE 150 POINT 151 POLICE 152 POOL 153 POWER R 155 RADIO 156 REAR 157 RECREATION 159 REFRIGERATION 160 RF 161 RIGHT 162 ROOM 163 ROOF S 164 SAFE 165 SCREEN 166 SENSOR 167 SERVICE 168 SHED 169...
Page 71: ...ill not appear If either not using a tool or one has already been programmed skip to step 4 00 INPUT S N L Axxx xxxx 3 If 1 is entered the system will prompt for the unit s serial number Enter the pro...
Page 72: ...UIT 12 Zone Number Entered Enter the next zone number to be enrolled e g zone 12 The system will search for that zone and will display the prompt shown in the beginning of step 5 If you wish to exit t...
Page 73: ...S N prompt A single long beep will be heard from the keypad to verify pressing of the upper right hand button Then press 1 Yes or press the upper left hand button of the program tool a single short be...
Page 74: ...ad call The control hangs up and then calls back the PC via the preprogrammed telephone number The unit can then be uploaded downloaded or controlled from your office 4 Telco Hand off Allows the insta...
Page 75: ...e inactive and will display C C or MODEM COMM The control however will still be scanning its zones and looking for alarms If an alarm does occur after communication is broken off alarms are sounded an...
Page 76: ...the panel will not send its message Once the handshake frequency is received and understood by the panel the panel will send its message If there is an error in the transmission the receiver does not...
Page 77: ...rouble SSS S T SSS S T SSSS Tt TTT T t Bypass SSS S B SSS S B SSSS Bb BBB B b AC Loss SSS S E SSS S E SSSS EAC EEE E AC Low Batt SSS S L SSS S L SSSS LLB LLL L LB Open SSS S O SSS S O SSSS OU OOO O U...
Page 78: ...123 Alarm 24 hour Audible 131 Alarm Perimeter 132 Alarm Interior 134 Alarm Entry Exit 135 Alarm Day Night 143 Alarm Expansion Module 146 Silent Burglary 150 Alarm 24 Hour Auxiliary 301 AC Power 302 Lo...
Page 79: ...h partition s Master security code can be used to assign up to 12 secondary 4 digit security codes plus a babysitter code and a duress code for that partition The master code can also be used to remov...
Page 80: ...l station of an alarm condition if that service is connected Arming Functions The following is a brief list of system commands For detailed information concerning system functions refer to the User s...
Page 81: ...can manually activate or deactivate the device s for starting or stopping some action such as turning lights on or off etc These keypad entries are Security Code 7 Device activates starts that device...
Page 82: ...n standby battery is weak A display of BAT Fixed word keypads or LO BAT Alpha keypads with a zone number and a once per minute beeping at the keypad indicates that a low battery condition exists in th...
Page 83: ...s 4 Check the keypad initiated alarms that are in the system by pressing the Panic key key pairs on some keypads If the system has been programmed for audible emergency the keypad will emit a steady a...
Page 84: ...OTE System Test Mode code test will be automatically terminated after 4 hours if the installer or user does not manually terminate it This insures that Fire and Panic zones will not remain disabled Ho...
Page 85: ...c beep s from keypad 4a System is in TEST mode 4b A transmitter low battery has occurred and is displayed 4c A supervision CHECK has occurred 4a Enter Code OFF to exit TEST mode 4b Enter Code OFF and...
Page 86: ...ad 4a CC or MODEM COMM displayed 4b d1 or Busy Standby displayed 4c E4 or E8 displayed 4d Keypad address setting incorrect 4a System is in communication with downloader at central station Wait until d...
Page 87: ...this information handy will make it easier for us to serve you quickly and effectively You may contact Technical Support via Toll Free Fax Please include your return fax number You will receive a rep...
Page 88: ...mplies with Part 68 of the FCC rules On the front cover of this equipment is a label that contains among other information the FCC registration number and ringer equivalence number REN for this equipm...
Page 89: ...munication FORMATS SUPPORTED Ademco Express 10 characters sec DTMF TouchTone Data Tones 1400 2300Hz ACK 1400Hz KISSOFF Ademco Contact ID Reporting 10 characters sec DTMF TouchTone Data Tones 1400 2300...
Page 90: ...x 108mm x 32mm 2 Electrical Voltage Input 12VDC Current Drain 35mA 3 8 EOLR Loops A H Loop A can be set for fast 10 15msec response to an open 4204 RELAY MODULE 1 Physical 6 1 2 W x 4 1 4 H x 1 1 4 D...
Page 91: ...oice siren driver with English Spanish and French voice messages Separate messages for Fire and Burglary Use with 8 ohm speaker UL Listed Ademco 705 820 5 inch Round Speaker 15 watt 8 ohm speaker Adem...
Page 92: ...erefore be carried off premises BR Unsupervised Button RF Type only send fault signals They do not send low battery restore or check in signals The transmitter may be carried off premises 3 4 1 2 ALWA...
Page 93: ...7 23 5890 27 6127 7 14 90 6128 14 15 90 6128 7 6137 7 14 15 90 6138 7 14 15 90 6139 7 9 14 15 43 90 6139TRK 15 702 91 705 820 91 713 91 719 91 744 91 745X3 91 747 91 747UL 91 7720 PLUS or 7820 9 38 A...
Page 94: ...6 Hard Wired Zones 17 HAYES modem specified by Ademco 9 HAYES Modem 74 House ID 23 28 House Identification 23 IBM Compatible Personal Computer PC 74 IBM Personal Computer 43 Ideal Model 61 035 13 41 I...
Page 95: ...ers 91 Split Dual Reporting 51 Supervised Fire 46 Supplementary Power Supply 15 System Communication 76 System Operation 63 System Sensor PA400B 36 System Status And Restore Report Codes 52 System Sta...
Page 96: ...96 NOTES...
Page 97: ...97 NOTES...
Page 98: ...ors closed doors glass partitions glass doors or windows Mechanical tampering masking painting or spraying of any material on the mirrors windows or any part of the optical system can reduce their det...
Page 99: ...ION PLANNING AND REPAIR SERVICE IS TO BE PROVIDED WITH THIS EQUIPMENT RING GRAY TIP GREEN RING RED INCOMING PHONE LINE HANDSET BLACK RED SET UNIT S DIP SWITCH FOR DEVICE ADDRESS OF 1 SEE INSTRUCTIONS...
Page 100: ...YONE FOR ANY CONSEQUENTIAL OR INCIDENTAL DAMAGES FOR BREACH OF THIS OR ANY OTHER WARRANTY EXPRESS OR IMPLIED OR UPON ANY OTHER BASIS OF LIABILITY WHATSOEVER EVEN IF THE LOSS OR DAMAGE IS CAUSED BY THE...