INSTALLATION INSTRUCTIONS 

FW4-H and FW2-H 

These installation instructions are for the FW-4, FW4-H, FW-2 and the FW2-H FIREWOLF Smoke Detectors.   

CAUTION!!! 

Install this and all life safety devices in accordance with 
applicable NFPA standards, local codes, and the au-
thorities having jurisdiction.  Failure to follow these in-
structions may result in failure of the detector to initiate 
an alarm condition.  Napco Security Systems, Inc. and 
the original equipment manufacturer, are not responsi-
ble for detectors that have been improperly installed, 
tested, or maintained. 

For testing and cleaning information, refer to these in-
structions and/or call the NAPCO fax request line at 
(631) 842-3291.  Also refer to NFPA-72 Chapter 5 for 
Automatic Fire Detectors for installation guidelines and 
Chapter 7 for testing and maintenance requirements. 
 
Use “3M” Weatherban # 606 non-flammable sealing 
compound to seal field wiring conduit openings in the 
mounting back box.  Compliance with this request may 
reduce the occurrence of the “STACK EFFECT”. 

SPECIFICATIONS 

SMOKE DETECTOR DATA 

Detector 

FW-2 

FW2-H 

FW-4 

FW4-H 

Type of Detector 

Photoelectric 

(2 wire baseless) 

Photoelectric 

(2 wire baseless) 

Photoelectric 

(4 wire baseless) 

Photoelectric 

(4 wire baseless) 

Working Voltage 

8.0 - 35.0 VDC 

8.0 - 35.0 VDC 

8.0 - 35.0 VDC 

8.0 - 35.0 VDC 

Voltage  

Waveform 

Filtered DC 

15% ripple max. 

Filtered DC 

15% ripple max. 

Filtered DC 

15% ripple max. 

Filtered DC 

15% ripple max. 

Max. Alarm 

Current 

Limit current to 
150mA @ 35.0 

VDC 

Limit current to 
150mA @ 35.0 

VDC 

55mA @ 35.0 

VDC 

55 mA @ 35.0 

VDC 

Max. Surge 

Current 

200µA 

200µA 

200µA 

200µA 

Average 

Standby Current 

38µA @ 12 VDC 
55µA @ 24 VDC 
70µA @ 35 VDC 

38µA @ 12 VDC 
55µA @ 24 VDC 
70µA @ 35 VDC 

38µA @ 12 VDC 
55µA @ 24 VDC 
70µA @ 35 VDC 

38µA @ 12 VDC 
55µA @ 24 VDC 
70µA @ 35 VDC 

Compatibility 

Identifier 

HD-6 

HD-6 

N/A 

N/A 

Sensitivity Test 

Feature 

Built-In Test 

Feature 

Built-In Test 

Feature 

Built-In Test 

Feature 

Built-In Test 

Feature 

NAPCO  

Control Panel  

Compatibility 

See Wiring 

Diagram Below 

See Wiring 

Diagram Below 

N/A 

N/A 

Heat Element 

Rating 

N/A 

135° F 

N/A 

135° F 

Note:  

When mounting detector on a wall, it must be between 4” and 12” from the ceiling. 

Trim Ring 

3” OCT 

4” Oct 

Box Mounting 

Wiring

:  

Connect wiring to the bases as shown in the wiring diagrams that follow.  Detectors may be mixed on the same initiating 

loop as long as the number of two-wire powered detectors does not exceed the specifications of the control panel.  See Specification 
Table above. 

 

CAUTION:  Connect wiring to terminals as shown.  Do not loop wire under terminals.  Break wire run to provide supervision. 

FW-4 Wiring Diagram 

FW-2 Wiring Diagram 

Compatible Control Panels: 

FW-C2Z, FW-C4Z, FW-C4EZ 
GEM-P3200 
GEM-P9600 
GEM-P800, GEM-P801 
GEM-P816, GEM-P1632 
NAPCO Express XP600 

MA3000 

 

Note:  

For cross listings with additional manufacturers and models pending, 

contact the NAPCO Technical Support Department for the latest listings at 
(800) 645-9440.  Also available online at www.napcosecurity.com (go to the 

Firewolf 

folder and download FW2_WI1009_ADDM). 

CAUTION 

The FW-2 requires current 

Limiting to no more than 150mA 

@ 35.0 VDC 

Magnum Alert

®

 is a Registered trademark of NAPCO.  Gemini,

 Signature

 and NAPCO Express

 are Trademarks of NAPCO. 

Napco Security Systems, Inc. 

333 Bayview Avenue * Amityville, NY 11701 
Phone: (800) 645-9445   (631) 842-9400   Fax: (631) 789-3383 

U.L. Listed 

Control 

Panel 

U.L. Listed 

Power  

Supply 

*24VDC 

U.L. Listed 

Power  

Supply 

*12VDC 

* = Use 12 or 24VDC - CANNOT BE USED SIMULTANEOUSLY 

LISTED  

END-OF-LINE 

RELAY  

12 OR 24VDC 

LISTED  

END-OF-LINE 

DEVICE 

R

® 

LISTED  

END-OF-LINE 

DEVICE 

U.L. LISTED  

COMPATIBLE 

CONTROL PANEL 