INSTALLATION INSTRUCTIONS
FW4-H and FW2-H
These installation instructions are for the FW-4, FW4-H, FW-2 and the FW2-H FIREWOLF Smoke Detectors.
CAUTION!!!
Install this and all life safety devices in accordance with
applicable NFPA standards, local codes, and the au-
thorities having jurisdiction. Failure to follow these in-
structions may result in failure of the detector to initiate
an alarm condition. Napco Security Systems, Inc. and
the original equipment manufacturer, are not responsi-
ble for detectors that have been improperly installed,
tested, or maintained.
For testing and cleaning information, refer to these in-
structions and/or call the NAPCO fax request line at
(631) 842-3291. Also refer to NFPA-72 Chapter 5 for
Automatic Fire Detectors for installation guidelines and
Chapter 7 for testing and maintenance requirements.
Use “3M” Weatherban # 606 non-flammable sealing
compound to seal field wiring conduit openings in the
mounting back box. Compliance with this request may
reduce the occurrence of the “STACK EFFECT”.
SPECIFICATIONS
SMOKE DETECTOR DATA
Detector
FW-2
FW2-H
FW-4
FW4-H
Type of Detector
Photoelectric
(2 wire baseless)
Photoelectric
(2 wire baseless)
Photoelectric
(4 wire baseless)
Photoelectric
(4 wire baseless)
Working Voltage
8.0 - 35.0 VDC
8.0 - 35.0 VDC
8.0 - 35.0 VDC
8.0 - 35.0 VDC
Voltage
Waveform
Filtered DC
15% ripple max.
Filtered DC
15% ripple max.
Filtered DC
15% ripple max.
Filtered DC
15% ripple max.
Max. Alarm
Current
Limit current to
150mA @ 35.0
VDC
Limit current to
150mA @ 35.0
VDC
55mA @ 35.0
VDC
55 mA @ 35.0
VDC
Max. Surge
Current
200µA
200µA
200µA
200µA
Average
Standby Current
38µA @ 12 VDC
55µA @ 24 VDC
70µA @ 35 VDC
38µA @ 12 VDC
55µA @ 24 VDC
70µA @ 35 VDC
38µA @ 12 VDC
55µA @ 24 VDC
70µA @ 35 VDC
38µA @ 12 VDC
55µA @ 24 VDC
70µA @ 35 VDC
Compatibility
Identifier
HD-6
HD-6
N/A
N/A
Sensitivity Test
Feature
Built-In Test
Feature
Built-In Test
Feature
Built-In Test
Feature
Built-In Test
Feature
NAPCO
Control Panel
Compatibility
See Wiring
Diagram Below
See Wiring
Diagram Below
N/A
N/A
Heat Element
Rating
N/A
135° F
N/A
135° F
Note:
When mounting detector on a wall, it must be between 4” and 12” from the ceiling.
Trim Ring
3” OCT
4” Oct
Box Mounting
Wiring
:
Connect wiring to the bases as shown in the wiring diagrams that follow. Detectors may be mixed on the same initiating
loop as long as the number of two-wire powered detectors does not exceed the specifications of the control panel. See Specification
Table above.
CAUTION: Connect wiring to terminals as shown. Do not loop wire under terminals. Break wire run to provide supervision.
FW-4 Wiring Diagram
FW-2 Wiring Diagram
Compatible Control Panels:
FW-C2Z, FW-C4Z, FW-C4EZ
GEM-P3200
GEM-P9600
GEM-P800, GEM-P801
GEM-P816, GEM-P1632
NAPCO Express XP600
MA3000
Note:
For cross listings with additional manufacturers and models pending,
contact the NAPCO Technical Support Department for the latest listings at
(800) 645-9440. Also available online at www.napcosecurity.com (go to the
Firewolf
folder and download FW2_WI1009_ADDM).
CAUTION
The FW-2 requires current
Limiting to no more than 150mA
@ 35.0 VDC
Magnum Alert
®
is a Registered trademark of NAPCO. Gemini,
™
Signature
™
and NAPCO Express
™
are Trademarks of NAPCO.
Napco Security Systems, Inc.
333 Bayview Avenue * Amityville, NY 11701
Phone: (800) 645-9445 (631) 842-9400 Fax: (631) 789-3383
U.L. Listed
Control
Panel
U.L. Listed
Power
Supply
*24VDC
U.L. Listed
Power
Supply
*12VDC
* = Use 12 or 24VDC - CANNOT BE USED SIMULTANEOUSLY
LISTED
END-OF-LINE
RELAY
12 OR 24VDC
LISTED
END-OF-LINE
DEVICE
R
®
LISTED
END-OF-LINE
DEVICE
U.L. LISTED
COMPATIBLE
CONTROL PANEL