FIREtec FTEP SERIES Installation Instructions And User Manual Download Page 1

 
 
 
 
 
 
 

FIRETEC 

 

FTEP 1-8 ZONE FIRE PANEL 

 
 
 

INSTALLATION INSTRUCTIONS 

 

USER GUIDE 

 

LOG BOOK 

 
 

 

 
 
 

 

9M347541 V5.0 

 
 

Summary of Contents for FTEP SERIES

Page 1: ...1 FIRETEC FTEP 1 8 ZONE FIRE PANEL INSTALLATION INSTRUCTIONS USER GUIDE LOG BOOK 9M347541 V5 0...

Page 2: ...SPECIFICATIONS 5 SYSTEM DESIGN GUIDE 5 INSTALLATION PROCEDURE 6 ADDITIONAL INSTRUCTIONS FOR ELECTROMAGNETIC COMPATIBILITY 6 PANEL COMMISSIONING 9 LEVEL 3 PANEL SETUP 9 SUMMARY OF MAINTENANCE REQUIREME...

Page 3: ...a power supply fault has occurred Check mains and battery 7 DISABLED yellow led illuminates when a fire zone and or alarm has been disabled the relevant zone and or alarm fault led is illuminated ste...

Page 4: ...ly one zone at a time is tested all other zones operate as normal Press 5 Exit walktest and the menu system 5 LAMP TEST and EXIT This option illuminates all the LED s and sounds the internal buzzer Af...

Page 5: ...terminal 14 Enable delay input This feature is enabled at level 3 When enabled a pre set delay to alarms activating during a fire condition will occur The delay can be over ridden 15 TTL fault output...

Page 6: ...ed either way round For any unused circuits leave the end of line component resistor in the terminal block located on the pcb F The panel has several optional inputs and outputs AUX 1 2 Are volt free...

Page 7: ...LED IF FITTED CALL POINT IN IN OUT OUT BELL A B C D 1 2 3 4 5 6 7 8 1 CONT or OUT 2 CONT or IN 3 TONE OUT 4 TONE IN 5 POS OUT 6 POS IN If selected Switches set tone type Sets Volume C D High D A Med A...

Page 8: ...R 10K Tolerance 1 4w 5 ON LAST SOUNDER EOL COMPONENT DIODE EOL COMPONENT RESISTOR IN UNUSED ZONES IN UNUSED ALARM CLASS CHANGE SWITCH ENABLE ALARM DELAY SWITCH F8 6 3A T F7 NOTE Red Battery Lead to BA...

Page 9: ...PC using a free file provided via email 11 HAND OVER TO THE USER as follows a Teach the user how to operate the panel and test the system using the USER GUIDE b Issue drawings of the wiring c Issue a...

Page 10: ...ng to 470R or Short CCT Repeat above process to set remaining zones On the last zone press Key 1 Function moves setup to setting Monitor Input Setting Monitor Input This is an input that when set up r...

Page 11: ...y Switch PRESS Key 2 Change Setting moves flashing led to make option either ON or OFF PRESS Key 1 Function moves setting flashing led to Alarm Delay Time only if Alarm Delay is set to ON If set to OF...

Page 12: ...se 45 Inspection and Servicing Clause 45 1 Commentary The inspection and servicing should be undertaken by organisations with the appropriate competence This can be assured by the used of organisation...

Page 13: ...mponent manufacturers should be undertaken Outstanding defects should be reported and the servicing certificate issued Clause 46 4 4 Recommendations for action to address an unacceptable rate of false...

Page 14: ...anted faults tests temporary disconnection s or zone isolations and the dates of service engineers visits and the work carried out Name and Address Person responsible Date Person responsible Date The...

Page 15: ...15 DATE TIME EVENT ACTION REQUIRED DATE COMPLETED INITIALS...

Page 16: ...light to the required zone 5 EXIT Exit from Level 2b function INDICATORS COLOUR INDICATION FAULT TEST DISABLE COMMON Yellow On when a fault condition has occurred or if no other fault Led is on this...