INDICATORS

COLOUR

INDICATION

COMMON FAULT

Yellow

On when a fault condition has occurred, or if

no other fault Led is on, this indicates 24v

auxiliary fuse failure.

COMMON FIRE

Red

On when a FIRE condition has occurred or 

EVACUATE has been operated.

ZONES 1-4 FAULT

Yellow

Flashes if a detector is removed from its base,

or an open/short circuit zone wiring fault.

Illuminated when a zone is disabled and

flashes when in walktest.

ZONES 1-4 FIRE

Red

Illuminated during a FIRE condition in this

zone. Flashes when a device is being tested

during walktest.

SUPPLY

Green

Illuminated while power is being supplied to

the panel.

SUPPLY FAULT

Yellow

Flashes during a mains or battery supply

failure.

ALARM FAULT/

Yellow

Flashes when a fault on the sounder wiring 

DISABLED

occurs. Illuminated if alarm lines are disabled.

DISABLED

Yellow

Illuminated when Zones and/or alarm are

disabled. The specific zone or alarm fault led

will also be lit.

TEST

Yellow

Illuminated when Walktest function selected.

SYSTEM FAULT

Yellow

Illuminated if the panel has malfunctioned and

an attempt to reset the system automatically

has been made. Flashes if an error in the

system software has been detected – Requires

attention.

ALARM SILENCED

Yellow

Illuminated if the sounders on the alarm

circuits during a fire/evacuation condition

have been switched off or silenced.

EARTH FAULT

Yellow

Will flash if a fault occurs with the earthing.

QUICK USER GUIDE FOR 1, 2 & 4 ZONE FIRE PANELS

FTEN

1

, FTEN

2

, & FTEN

4

1, 2 & 4 ZONE 

FIRE DETECTION AND

ALARM CONTROL PANELS

INSTALLATION INSTRUCTIONS

USER GUIDE

LOG BOOK

tec 

tec 

EN54

EN54

EN54

EN54

FIRE

FIRE

FIRE

FIRE

Document EN02/08.02

 

Summary of Contents for FTEN1

Page 1: ...when a fault on the sounder wiring DISABLED occurs Illuminated if alarm lines are disabled DISABLED Yellow Illuminated when Zones and or alarm are disabled The specific zone or alarm fault led will a...

Page 2: ...EN54 4 1997 SILENCE BUZZER SILENCE SILENCE BUZZER BUZZER 1 1 1 tec tec EN54 EN54 EN54 FIRE FIRE FIRE TYPICAL PANEL WIRING NO SPURS ALLOWED END OF LINE COMPONENT ON LAST DETECTOR Zone Ve RED Zone Ve B...

Page 3: ...rs and callpoints used are compatible with the panel and that only devices recommended by the supplier are used 7 The correct end of line component is used on the detection and alarm circuits includin...

Page 4: ...the common fault indicator Used to drive a remote fault indicator TYPICAL PANEL WIRING NO SPURS ALLOWED END OF LINE COMPONENT ON LAST DETECTOR Zone Ve RED Zone Ve BLACK EOL COMPONENT ON ANY UNUSED ZO...

Page 5: ...5 5 5 EN54 2 1997 EN54 2 1997 EN54 2 1997 EN54 4 1997 EN54 4 1997 EN54 4 1997 SILENCE BUZZER SILENCE SILENCE BUZZER BUZZER 1 1 1 tec tec EN54 EN54 EN54 FIRE FIRE FIRE SYSTEM FAULT SYSTEM FAULT SYSTEM...

Page 6: ...SYSTEM FAULT SYSTEM FAULT SYSTEM FAULT EARTH FAULT EARTH FAULT EARTH FAULT SUPPLY SUPPLY SUPPLY ZONES ZONES ZONES 2 2 2 1 1 3 3 3 4 4 4 SUPPLY FAULT SUPPLY FAULT SUPPLY FAULT DISABLED DISABLED DISABLE...

Page 7: ...ENERAL FIRE FAULT DISABLE TEST FAULT DISABLE FAULT DISABLE TEST TEST FIRE FIRE FIRE SILENCE BUZZER SILENCE SILENCE BUZZER BUZZER SILENCE ALARMS SILENCE SILENCE ALARMS ALARMS EXIT EXIT EXIT EVACUATE EV...

Page 8: ...rmal state then isolate the mains supply and perform an EVACUATE to ensure that the battery is capable of supplying the alarm sounders 4 Annual Test As in 2 and 3 above but test all call points and de...

Page 9: ...DATE TIME EVENT ACTION REQUIRED DATE INITIALS COMPLETED DATE TIME EVENT ACTION REQUIRED DATE INITIALS COMPLETED...

Page 10: ...bout 3 seconds 5344 1 Reset Return the system to a normal condition after a fire or fault has occurred This should only be performed when the fire or fault has been identified and alarms have been sil...