Page 25/43
Firemiks AB
Instruction manual version: SPFA FM
P.O. Box 8155, 104 20 STOCKHOLM, Sweden
phone +46-8-551 196 10 - [email protected] - www.firemiks.com
5 Check before first start
5.1 Commissioning parts
5.1.1 No specific commissioning parts are needed for the FIREMIKS unit. After
following all instructions in this Instruction Manual up to the next chapter to
make the unit stand-by, the unit is ready for use. This can be a
commissioning test if so desired or required to verify the whole system.
5.2 Check this:
5.2.1 Check once again that installation is made according to instructions above in
section 4 Installation.
5.2.2 Check that the drain valve on the water motor is closed
(no drain valve on FM 400
size)
5.2.3
NOTE!
Make sure that the cover over the drive shaft and the protection cap
on the back gable side are in place.
5.2.4 Check the oil level in the concentrate pump. Use the dip stick (must be
changed, see 4.6.7) or the oil level window if available on your unit. Refill if
necessary according to section 7.6.1
5.2.5 Follow the instructions for first start-up in the next chapter.