4
INSTALLATION
21
4-E Ventilation and Combustion Air
1. Conventional Flue Boilers
An adequate supply of
combustion and ventilation air
is essential for
efficient and safe boiler operation and the openings for this should be
positioned to cause least possible draught,
with no possibility of being
accidentally blocked.
Please note: The British Standard Code of Practice for Oil Firing BS5410:
Part 1, requires a permanent air inlet opening of
550mm
2
per kW (above 5 kW)
of boiler rated output. (Note: 1kW = 3412 Btu/h).
Also, when the boiler is installed in a compartment or confined space,
ventilation
openings are required to ventilate and to avoid overheating in
the boiler area.
FULL TEXT of both BS 5410 Part 1: 1997 and appropriate Building
Regulations for each country should be obtained and fully applied
N.B. Please Carefully Note:
A.
For boiler installations in domestic garages in Scotland, Part F of
Building Regulations permits
only
Room Sealed appliances to be used (Ref.
OFTEC Bk. Three May 1999 page 1 (18).
B.
Technical annex T1/127 to OFTEC Book Three, May 1999 page 2
(19) Para. 1, 2 states “In Scotland and the Republic of Ireland
only
Room
Sealed Balanced Flue Appliances can be used in that
location” (i.e. domestic garages).
Definitions
Combustion Air
: Air required directly by boiler oil burner for combustion
process.
Ventilation Air
: Air required in room for ventilation, cooling, etc. and to
promote a healthy living environment.
Conventional open flue (a) or open flue low level discharge (b)
Combustion & Ventilation air supply for conventional
open flue boilers
The figures shown are free areas of grilles in mm
2
per kw of appliance rating (output).
☛
☛
☛
☛
Summary of Contents for Combi 120
Page 10: ...2 TECHNICAL SPECIFICATION 9 2 E F Riello Burner Specification...
Page 31: ...30...
Page 32: ...Combi Oil Boiler PART 2 Sealed System Domestic Hot Water 31...
Page 40: ...39 Combi Oil Boiler PART 3 Spare Parts...
Page 41: ...9 FAULT FINDING 40 T Repair or Replace Oil Pump r No...
Page 52: ...NOTES...