This manual must remain with the householder once installation is complete

BLUE FLAME ENVIROMAX

CONDENSING BOILER

TECHNICAL MANUAL

Summary of Contents for BLUE FLAME ENVIROMAX

Page 1: ...HEATING SOLUTIONS Working towards a greener planet This manual must remain with the householder once installation is complete BLUE FLAME ENVIROMAX CONDENSING BOILER TECHNICAL MANUAL...

Page 2: ...Enviromax condensing oil boiler This instruction manual is produced for the reference and guidance of qualified installation engineers preferably OFTEC Oil Firing Technical Association registered EU l...

Page 3: ...8 2012 A1 2014 EN 12831 2003 and the statutory requirements of the Building Regulations To ensure the highest standards of installation safety it is important that the boiler be installed in complianc...

Page 4: ...attention should be sought following eye contact or prolonged reddening of the skin The small quantities of adhesives and sealants used in the product are cured They present no known hazards when used...

Page 5: ...is factory fitted with a burner control box lockout safety feature which operates automatically if a fault occurs in the burner operation Should this occur the light on the top of the burner will illu...

Page 6: ...ntrols to ensure return values are as stated above Magnetic Filtration It is recommended at the time of installation of this boiler to install a permanent effective magnetic filter on the return pipew...

Page 7: ...service The condensate line should be plastic and have a minimum diameter of 22mm have a fall from the boiler of 1 100 minimum have as few bends as possible to reduce the risk of trapping condensate...

Page 8: ...Out Inlet Out to drain Control panel Condensate Pump can be positioned within the casing of the boiler on the base or fixed to the casing of the boiler house boiler or mounted on the wall alongside t...

Page 9: ...ECK FOR ANY BUILDING REGULATIONS AMENDMENTS WHICH MAY HAVE BEEN ISSUED AFTER THE PUBLICATION OF THIS MANUAL A A C B C A Horizontal from opening airbrick opening window etc B From an internal or extern...

Page 10: ...or a balcony without protection 1000 E From vertical sanitary pipe work 300 F From an internal or external corner or surface or boundary alongside the terminal 300 G Above ground or balcony level 300...

Page 11: ...been approved for low level flue and low level balanced flue discharge when tested to BS EN 303 1 5 Terminating positions must be at least 1 8m distant from an oil storage tank unless a wall with at l...

Page 12: ...where air can pass freely across them to disperse vapours 3 The effect of the moisture generated must be considered in relation to the possible corrosion of metal parts it might reach and to the possi...

Page 13: ...ipe system is required Ensure that valves and filters are not fitted in the return line as this must be unobstructed at all times The oil burner pump is set for two pipe operation as detailed in accom...

Page 14: ...13 All tanks either deemed to be at risk or with a capacity of more than 2 500 litres will require to be bunded Those externally installed tanks with a capacity of less than 2 500 litres will require...

Page 15: ...9 1 Condensate Hose 111537 10 1 1 2 Drain Valve 111329 11 1 Heat De ector 210904 12 1 MHG Rocket Burner 95201000840 13 1 Casing Top 214062 14 1 Casing Front 214061 15 1 Casing Door 214063 16 1 Casing...

Page 16: ...1000840 12 1 Flue Kit 412031 13 1 1 2 Drain Valve 111329 14 1 Front Panel 211527 15 1 7 Pin Control Panel 310453 16 1 Back Panel 211547 17 1 Fixed Panel Right 213990 18 1 Removable Panel 212004 19 1 F...

Page 17: ...rner 95201000840 12 1 Flue Kit 411982 13 1 Front Panel 211604 14 1 Control Panel 311146 15 1 Casing Right Side 214052 16 1 Casing Left Side 214051 17 1 Casing Top 214055 18 1 Back Panel 211605 19 1 Fl...

Page 18: ...wiring in accordance with current ETCI IET Regulations and any local regulations which may apply 16 Permanent live from high limit stat Power to burner Temperture control dial max 80 C min 60 C High...

Page 19: ...live Neutral Timed switch live Earth Permanent live Blue Flame Enviromax Heatpac Imit dual thermostat Pump over run thermostat 87 C Bi metal frost thermostat 5 C 14 C Please note a permanent live conn...

Page 20: ...ure that the boiler is properly commissioned when first used The boiler should be commissioned by an OFTEC registered or competent qualified engineer familiar with Firebird products The installation c...

Page 21: ...of the fuel The burner air setting should not be adjusted 6 If the CO reading is greater than 40ppm when commissioning this boiler contact the Firebird technical desk for assistance before leaving th...

Page 22: ...n boiler passport Annual servicing must be carried out by an OFTEC registered or a competent qualified engineer familiar with Firebird products Do not commence service until both the electrical and oi...

Page 23: ...commissioning of the product must be in accordance with a instruction technical manuals b all relevant standards and codes of practice 4 An OFTEC registered or competent qualified engineer using the...

Page 24: ...ts please contact Firebird Heating Solutions Ltd dar s Industrial Estate Baile Mhic re Co Cork Ireland t 353 0 26 45253 f 353 0 26 45309 e info firebird ie web www firebird ie Firebird Heating Solutio...