IPDACT-2/IPDACT-2UD 

IP Communicator

 

IPDACT-2(UD) Dm 387-Iv3

 

Quick Start Programming Guide using a PC Serial Port 

 

Model TS563/2 

1

. Requirements 

Alarm Panel 

  “Contact Id” compatible panel with tone dialing. 

  Existing PSTN Service (for backup communication lines). 

  PC with RS-232 serial port. 

 

Console cable for the IPDACT-2(UD).

 

Power 

Voltage Range 

10-28 VDC 

Current (Maximum) 12VDC 

IPDACT-2:      180 mA (NSC), 230 mA (Alarm) 

IPDACT-2UD: 185 mA (NSC), 230 mA (Alarm) 

Current (Maximum) 24VDC 

IPDACT-2:      93 mA (NSC), 136 mA (Alarm) 

IPDACT-2UD: 98 mA (NSC), 155 mA (Alarm) 

Internet Access 

Either a static IP address (always the same) or a dynamic IP address (could be different every time 
a connection is made) are possible. 

2. Checklist

¹ 

a. 

IPDACT-2(UD) console access password (default is 24680). 

b. 

Installer password, required to execute the register command. 

c. 

IP address, subnet mask and gateway for IPDACT-2(UD)

2

 

d. 

IPDACT-2(UD) account number or client number. 

e. 

IP address, and UDP Port number of the VisorALARM central station. 

1

 Please obtain the following information from your central monitoring station. 

2  

If you have a DHCP server in the network to which the IPDACT-2(UD) connects, these parameters can be obtained automatically. 

Dm387-Iv3  

 

firealarmresources.com

Summary of Contents for IPDACT-2

Page 1: ... mA NSC 155 mA Alarm Internet Access Either a static IP address always the same or a dynamic IP address could be different every time a connection is made are possible 2 Checklist a IPDACT 2 UD console access password default is 24680 b Installer password required to execute the register command c IP address subnet mask and gateway for IPDACT 2 UD 2 d IPDACT 2 UD account number or client number e ...

Page 2: ... the Fire Alarm Panel or other electric supply Ethernet Network RJ45 To a broadband modem router or a network switch hub for internet access with a IEEE 802 3 interface 4 IPDACT 2 UD Default Configuration Through a short circuit in the IPDACT 2 UD P1 jumper during the start up process you can configure the IPDACT 2 UD with the default factory settings The process for this is as follows 1 switch of...

Page 3: ...n program you will be asked for a password The factory default value is 24680 Enter this and the following menu will appear Password Accepted Main Menu Configuration a Generic MIP config b Transmission Parameters c Quick Install Monitoring d General Info e Remote Monitor f Events g IP Connectivity z Exit option c OK Quick Install a DHCP client ON b IP addr 192 168 0 100 mask 255 255 255 0 c Gatewa...

Page 4: ...VisorALARM receiver UDP port Enter the value indicated for the parameter and then press ENTER OK should now appear on the PC display which will then show the list of parameters that appear in option h the value that has just been entered 6 Press j followed by the ENTER key to reboot the device so these changes activate You will be asked for a password Enter 24680 which is the default factory passw...

Reviews: