Emergency Command Center Manual —
P/N LS10001-000FL-E:D 9/3/2014
63
Main Menu - User Programming
Programming
Aux Power
Selects whether this power is
Constant
or
Resettable
use from TB17.
Speaker Volume Control NAC
If the Cooper Wheelock SP-SVC module is installed on TB23
of the main control board, allowing manual volume setting for telephone paging and background
music for a specific speaker or speaker zone, select
Enabled
.
Console Control
Console Priority
Priority can be assigned to the operator consoles so that the primary operator
interface can always override the functions at the local operator consoles or remote microphones.
Select
POC->LOC->RM
for console priority. Selecting
Equal
for priority allows users with access
to the system on a a “first come, first served” basis.
Device Control Timeout
Enter the maximum amount of time (
30-300
seconds) that one of the
devices (Primary Operator Console, Local Operator Console, Remote Page Unit, or Remote Micro-
phone) can remain in manual control of the ECC system.
Paging Timeout
Enter the maximum amount of time (
30-300
seconds) that the microphone’s
PTT switch can be held.
3.1.3 Address Assignment
Remote Microphone / Operator Console Address Assignments
Any combination of up to eight (8) remote consoles (ECC-LOC, ECC-RPU, and ECC-RM) can be
used in the system. Odd numbered addresses are not selectable. Addresses must be sequential,
even numbers. Identify which consoles are installed at addresses 4, 6, 8, 10, 12, 14, 16, and 18 as
either
Local Operator Console
or
Remote Microphone
. Note that the ECC-RPU and ECC-RM are
both considered remote microphones. Refer to Section 2.14, “Addressing External Data Bus
Devices” for information on dipswitch settings.