All relay switch contacts are shipped as shown in Figure 3, but may have transferred during shipping. To ensure that the switch con-
tacts are in their correct state, modules must be made to communicate with the panel before connecting circuits controlled by the mod-
ule.

Relay Contact Ratings:

Figure 3. Relay module wiring diagram:

A78-2286-10

F300-04-00

2

I56-1190-01

©1999 Fire•Lite Alarms, Inc.

CURRENT RATING

MAXIMUM VOLTAGE

LOAD DESCRIPTION

APPLICATION

3 A

2 A

.9 A

.9 A

.5 A

1 A

.5 A

30 VDC

30 VDC

110 VDC

125 VAC

30 VDC

30 VDC

125 VAC

Resistive

Resistive

Resistive

Resistive

Inductive (L/R=5ms)

Inductive (L/R=2ms)

Inductive (PF=.35)

Non Coded

Coded

Non Coded

Non Coded

Coded

Coded

Non Coded

.7 A

75 VAC

Inductive (PF=.35)

Non Coded

IF ANY WIRING TO TERMINALS 3 – 9 IS NONPOWER
LIMITED, THE CB500 BARRIER IS REQUIRED. THE CB500
INCLUDES A NONPOWER LIMITED LABEL, WHICH MUST
BE PLACED OVER THE POWER LIMITED TERMINAL
INFORMATION ON THE NAMEPLATE LABEL.

MODULE

FROM PANEL OR

(+)

(—

)

TO NEXT

(+)

(—

)

DEVICE

(+)

(—

)

CONTROL

CONNECT MODULES TO LISTED COMPATIBLE

RELAY COMMON 1

RELAY COMMON 2

NORMALLY CLOSED 1

NORMALLY OPEN 2

NORMALLY CLOSED 2

 MODULE DOES NOT SUPERVISE CONTROLLED CIRCUITS

NORMALLY OPEN 1

FIRE  LITE CONTROL PANELS ONLY

PREVIOUS DEVICE

COMMUNICATION LINE

32 VDC Max.

SHIELDED-TWISTED PAIR

IS RECOMMENDED

9

8

7

6

5

4

3

2

1

0

ADDRESS

LOOP