BG-12LR and BG-12LRA

Agent Release Pull Stations

Document 51370   Revision A   ECN 00-190   06/16/2000

Door Reattachment

If the door becomes detached,

 complete the following steps to

reattach the door to the backplate.  The door cannot be connected

to the pull station if the unit is mounted to a backbox.
1. Position the door and backplate side by side in the full open

position (i.e. 180-degrees with respect to each other).

2. With the backplate position fixed, move the door behind

the backplate, as shown in the illustration, part A.

3. Align the hinge posts and holes by bringing the door up to

meet  the  backplate,  paying  particular  attention  to  the

‘keying’ that occurs when the door’s post hole is aligned to

the backplate’s hinge post.  Refer to the illustration, part B.

4. With the two pieces aligned and ‘keyed’ together, slide the

holes down onto the posts.  Refer to the illustration, part C.

5. Holding the backplate, close the door slightly to lock the

door and backplate together.

BG1

2L

R

fac

e.c

dr

Switch Contact Rating

Switch contacts are rated for 0.25 A at 30 volts (AC or DC).

Description

The BG-12LR and BG-12LRA Agent Release Pull Stations are

designed for use with Fire•Lite control panels that include agent

release capabilities, such as the Sensiscan 2000 and MRP-4424.

These stations are ideally suited for areas such as clean rooms

and  computer  rooms,  where  a  chemical  agent  is  used  to

extinguish  a  fire.    Both  pull  stations  provide  a  dual-action,

normally open contact, release initiating point. The BG-12LRA

also includes a manual abort switch, System  Normal LED, and

System  Activated  (release)  LED.    The  dual-action  stations

require pushing the handle, then pulling the handle down for

activation.  Like the entire BG-12 Series of manual fire alarm

stations, the releasing stations are UL listed and meet the ADA

requirement of a 5-lb. Maximum pull force to activate.  Operating

instructions are molded into the handle.

Agent Releasing Models Available

BG-12LR.  

Dual action with screw terminal connections and

key lock/reset.  Front of station (door) is identified with the words

"AGENT RELEASE" and a symbol illustrating discharge. This

model can be semi-flush-mounted to a standard single-gang

electrical box or surface-mounted to a SB-10 backbox.

BG-12LRA.

  All features as BG-12LR plus manual abort switch,

System Normal (power-on) LED, and System Activated (release)

LED.    This  model  must  be  surface-mounted  to  an  SBA-10

backbox.

Dual Action BG-12LR

Operation

To initiate an agent release, push in the pull

station  handle  then  pull  it  down.  The  word

"ACTIVATED"  appears  after  the  handle  is

pulled  down.  The  agent  release  pull  station

remains in the activated position until reset.
To reset the BG-12LR or BG-12LRA:
1)Unlock and open the station door.  Once open, the handle

will return to the "NORMAL" position.

2)Close and lock the door.  Closing the door automatically

resets the alarm switch to the "NORMAL" position.

Note: Opening the door will not activate or deactivate the alarm

switch.

BG1

2L

R

A

ac

tiv

at

ed.c

dr

Dual Action BG-12LRA

(Shown activated)

ac

than

dle

.c

dr

Abort Feature (BG-12LRA only)

The  operation  and  reset  of  the

BG-12LRA  agent  release  pull

station  is  the  same  as  the  BG-

12LR,  with  the  addition  of  the

Abort Feature:
The System Normal LED will stay

illuminated  when  the  Agent

Release  Control  Panel  is  "All

Systems  Normal."    When  the

station  has  been  activated,

initiating the agent release process

in the control panel, the System

Activated LED will illuminate. If

the  control  panel  has  been

configured to abort the releasing

of  an  extinguishing  agent,  then

pushing and holding-in the abort

switch will cancel the agent release

sequence.    Please  refer  to  the

respective  agent  release  control

panel  manual  for  further

instructions about using the Abort

feature.