Description

The BG-12 Series Pull Stations are non-coded manual pull
stations which provide a Fire Alarm Control Panel (FACP)
with a single alarm initiating input signal.  The BG-12 series
includes both single-action and dual-action models equipped
with either a hex or key lock / reset.  A single-action pull-
station is activated by a single pull-down of the alarm handle.
The dual-action versions require pushing in the handle, then
pulling the handle down for activation.  The BG-12 series
manual pull stations are UL listed and meet the ADA require-
ment of a 5-lb. maximum pull force to activate.  Operating
instructions are molded into the handle along with Braille
text.  Molded terminal numbers can be found adjacent to the
wiring terminals.

 Document: 50964   Revision: B   ECN: 98-461   08/04/99

BG-12 Series Models available:
BG-12S

 – Single action with ‘pigtail’ connections and a hex

lock reset.  Pigtail wires are provided for connection to the
FACP Initiating Device Circuit (IDC).

BG-12 

– Dual action model with screw terminal connections

and a hex lock reset.

BG-12L

 – Same as BG-12 except with a key lock reset.

BG-12LSP

 – Same as BG-12L except with both English and

Spanish operating instructions.

BG-12 Series Manual Pull Stations

Installation

Surface mount the BG-12 pull station to a SB-10 surface backbox.
Semi-flush mount the BG-12 to a standard single gang, double-gang,
or 4-inch (10.16cm) square electrical box.  Mount the optional Trim
Ring (BG-TR) if necessary when semi-flush mounting the unit.

Dual Action BG-12L

Switch Contact Rating

All switch contacts are rated for 0.25 A at 30 volts (AC or DC).

The word ‘ACTIVATED’

is displayed

DOOR ATTACHMENT

If, during mounting of the pull station, the door becomes de-
tached

, complete the following steps to reattach the door to the

backplate.  The door cannot be connected to the pull station if the
unit is mounted to the backbox.
1.

Position the door and backplate side by side in the full open
position.  (i.e. 180-degrees with respect to each other.)

2.

With the backplate position fixed, move the door behind the
backplate, as shown in the illustration below, part A.

3.

Align the hinge posts and holes by bringing the door up to meet
the backplate,  paying particular attention to the ‘keying’ that
occurs when the door’s post hole is aligned to the backplate’s
hinge post.  Refer to the illustration, part B.

4.

With the two pieces aligned and ‘keyed’ together, slide the holes
down onto the posts.  Refer to the illustration, part C.

5.

Holding the backplate, close the door slightly to lock the door
and backplate together.

on the pull station’s
pulled-down handle

P/N  509 97   REV.

REFER TO DOCU MENT
NUMBER  5101 5 RE V.

LOOP

A DDR ESS

1 0

11

1 2

1 3

P/ N 5099 7  REV.

REFER TO D OCU MENT
NUMB ER 51 015  RE V.

LOOP

A DD R ESS

1 0

1 1

1 2

1 3

1 4

9

C

B

A

P O S T

D O O R   K E Y S  IN T O

B A C K P LA T E AT  TH IS  PO IN T

P O S T

P O S T

H O LE

H O LE

With the door and
backplate aligned and
‘keyed’ together, slide
the holes down onto
the posts.

Closing the door slightly
locks the door and
backplate together.

DOOR MATED TO BACKPLATE

Summary of Contents for BG-12 Series

Page 1: ...x Mount the optional Trim Ring BG TR if necessary when semi flush mounting the unit Dual Action BG 12L Switch Contact Rating All switch contacts are rated for 0 25 A at 30 volts AC or DC The word ACTIVATED is displayed DOOR ATTACHMENT If during mounting of the pull station the door becomes de tached complete the following steps to reattach the door to the backplate The door cannot be connected to ...

Page 2: ...nd then proceed with steps 4 and 5 following 4 Connect the field wiring from the FACP s IDC or the previous device on the IDC to the pull station s pigtails Connect the positive IDC wire to a red pigtail and the negative IDC wire to a black pigtail Next connect the positive wire going to the next device or an ELR to the remaining red positive pigtail Connect the negative wire going to the next dev...

Page 3: ...ciones Pulsadoras Manuales de la Serie BG 12 Instalación Instale en la superficie la estación BG 12 a una caja posterior de superficie SB 10 Instale semi empotrada la BG 12 a una caja eléctrica cuadrada de 4 pulgadas 10 16cm de grupo doble o singular Instale el Anillo Embellecedor BG TR si es necesario cuando la unidad está siendo semi empotrada BG 12L de Doble Acción La palabra ACTIVATED es mostr...

Page 4: ...bre positivo que está yendo al próximo dispositivo o a un ELR al cable flexible positivo rojo restante Conecte el alambre negativo que está yendo al proximo dispositivo o a un ELR al cable flexible negativo negro restante 5 Mantenga la polaridad consistente con todas las conexiones a través del IDC BG 12S de Acción Singular S T R IP G AU G E AVISO Instale la estación de acuerdo a las instrucciones...

Reviews: