110
Audio Command Center Series Manual —
P/N 51889:E1 6/8/2010
Programmed Activation by FACP
MS-9600, MS-9200UDLS and MS-9200UD
Note that Zone 32 is assigned to all speaker circuits. If an addressable device programmed to Zone
32 is activated, the message programmed to Zone 32 will be generated to
all
speaker circuits. The
exception is when one or more devices programmed to Zones 33 through 40 is also activated. If the
newly activated zone is programmed to a message with a higher priority then Zone 32, the higher
priority message will be generated to all circuits.
IMPORTANT!
Messages have a priority scheme with Message 1 having the highest priority and
Message 5 having the lowest priority. For example, If an addressable device activates a speaker cir-
cuit programmed to generate Message 5, that message will be generated over the selected speaker
zone. If later, another device activates a speaker circuit programmed to generate Message 3, Mes-
sage 3 has a higher priority then Message 5 and will therefore be generated over both activated
speaker zones. The highest priority message will always be generated over all activated speaker
circuits.
Programming Tips for MS-9600, MS-9600LD, MS-9200UDLS, and MS-9200UD
It is important to note that Message 1 is assigned to Zone 00 (General Alarm) as a default. A mes-
sage, however, will not be generated over the speaker circuits unless one of the following program-
ming steps is completed:
•
For General Alarm applications, all input points must have an audio zone assigned to it:
Z32 to activate all audio zones
OR
Z33 to Z56 for specific audio zone control
•
For non-General Alarm applications where input devices and/or messages are mapped to spe-
cific zones, Message 1 must be removed from Zone 00 programming.
Message Assignment - Speaker Specific
The ACC-25/50ZS and ACC-25/50ZST have the capability of generating up to five different mes-
sages. Any one of the five messages can be programmed to each of the speaker circuit Zones 32
through 56. For example:
9 (on 1st ACC-25/50DAZS)
41
10 (on 1st ACC-25/50DAZS)
42
11 (on 1st ACC-25/50DAZS)
43
12 (on 1st ACC-25/50DAZS)
44
13 (on 1st ACC-25/50DAZS)
45
14 (on 1st ACC-25/50DAZS)
46
15 (on 1st ACC-25/50DAZS)
47
16 (on 1st ACC-25/50DAZS)
48
17 (on 2nd ACC-25/50DAZS)
49
18 (on 2nd ACC-25/50DAZS)
50
19 (on 2nd ACC-25/50DAZS)
51
20 (on 2nd ACC-25/50DAZS)
52
21 (on 2nd ACC-25/50DAZS)
53
22 (on 2nd ACC-25/50DAZS)
54
23 (on 2nd ACC-25/50DAZS)
55
24 (on 2nd ACC-25/50DAZS)
56
Table D.5 Speaker Circuit Zone Assignments