Fire Alarm Control Panel

MS-5210UD/MS-5210UDE

PN: 50193:E          ECN 01-685

E

Document   #50193        
01/30/02                   Rev.

Summary of Contents for MS-5210UD

Page 1: ...Fire Alarm Control Panel MS 5210UD MS 5210UDE PN 50193 E ECN 01 685 E Document 50193 01 30 02 Rev ...

Page 2: ...explosions caused by escaping gas improper storage of flammable materials etc Heat detectors do not sense particles of combustion and alarm only when heat on their sensors increases at a prede termined rate or reaches a predetermined level Rate of rise heat detectors may be subject to reduced sensitivity over time For this reason the rate of rise feature of each detector should be tested at least ...

Page 3: ...terferences proper grounding will reduce susceptibility Overhead or outside aerial wiring is not recommended due to an increased sus ceptibility to nearby lightning strikes Consult with the Techni cal Services Department if any problems are anticipated or encountered Disconnect AC power and batteries prior to removing or in serting circuit boards Failure to do so can damage circuits Remove all ele...

Page 4: ...Notes 4 Document 50193 Rev E 01 30 02 P N 50193 E ...

Page 5: ...sions and Knockout Locations 24 FIGURE 2 2 FACP Backbox and Battery Box 25 2 3 Operating Power 26 FIGURE 2 3 Operating Power Connections 26 2 4 Input Circuits 27 FIGURE 2 4 Style B Initiating Device Circuit Connections 28 2 5 Output Circuits 28 FIGURE 2 5 Auxiliary Power Connections 28 FIGURE 2 6 Notification Appliance Circuit Connections 29 FIGURE 2 7 Programmable Relay Terminals 29 2 6 Digital C...

Page 6: ...on 62 3 3 5 Default Programming 64 CHAPTER 4 Operating Instructions 65 FIGURE 4 1 New and Old Keypad Display 65 4 1 Switch Functions in Normal Mode 65 4 2 LED Display and Status LEDs 67 FIGURE 4 2 Phone Connectors and LEDs 68 4 3 Operation 69 4 3 1 Fire Alarm Response 69 4 3 2 Fire Alarm Restoral 70 4 3 3 System Supervisory Condition Response 70 4 3 4 System Supervisory Restoral Response 70 4 3 5 ...

Page 7: ...89 6 5 Simultaneous Data Transfers 90 Appendix A Battery Calculations 91 TABLE A 1 Battery Calculation 91 A 1 Main Power Supply 92 TABLE A 2 Regulated Load in Standby 24 VDC 92 TABLE A 3 Regulated Load in Alarm 24 VDC 93 Appendix B Main Panel Options Program Sheets 94 Appendix C Event Codes Transmission Format Programming Sheets 99 Appendix D Ademco Contact ID Format Event Code Descriptions 109 Ap...

Page 8: ...Notes 8 Document 50193 Rev E 01 30 02 P N 50193 E ...

Page 9: ...le Signaling Appliances UL 521 Heat Detectors for Fire Protective Signaling Systems UL 864 Standard for Control Units for Fire Protective Signaling Systems UL 1481 Power Supplies for Fire Protective Signaling Systems UL 1638 Visual Signaling Appliances UL 1971 Signaling Devices for Hearing Impaired Other NEC Article 250 Grounding NEC Article 300 Wiring Methods NEC Article 760 Fire Protective Signa...

Page 10: ...10 Document 50193 Rev E 01 30 02 P N 50193 E MS 5210UD Terminals and Connectors ...

Page 11: ...rve as a Service Terminal This allows downloading of any portion or all of the program and upload of any portion or all of the program history file walktest data current status and system voltages The MS 5210UDE offers the same features as the MS 5210UD but allows connection to 220 240 VAC input Note that unless otherwise specified the term MS 5210UD shall be used in this manual to refer to both t...

Page 12: ...iance Circuit Auto Silence per Notification Appliance Circuit Touchtone Rotary Dialing per telephone line Programmable Make Break Ratio Fuseless Design Printer Interface Module PRT 24 NAC REM Option Module adds two Form C relays and two Style Z Class A NACs Print Real time System Status Print History Walktest Files Program Contents and Troubleshoot mode voltages PK 5210UD Upload Download Software ...

Page 13: ...fer to the MS 5210UD MS 5210UDE Field Software Change Procedure Document 50479 Transformer Transformer Four Character 7 Segment LED Display Keypad NAC REM Expander Module 24 VDC Power Programmable Relays Notification Appliance Circuits Class A Converter Module 10 Input Zones LED 10IM Interface Module Connector Printer Interface Module Connector PROM U14 1 Primary Secondary Phone Lines Holds up to ...

Page 14: ...or current Smoke Detector Identifier A Refer to Fire Lite Device Compatibility Chart for listed compatible devices Notification Appliance Circuits TB4 NAC REM Option Module TB2 TB3 Nonregulated special purpose power Styles Y Z supported Power limited circuitry Operating Voltage Nominal 24 volts Current for all external devices 3 0 amps expandable to 6 0 amps Current Limit TB4 via electronic protec...

Page 15: ...Station green LED Silence yellow LED Modem green LED Local Sounder A piezo sounder provides separate and distinct sounds for alarm trouble supervisory and critical process monitor ing conditions 1 4 Circuits Input Circuits Ten input circuits provide Style B Class B configuration standard and may be converted to Style D Class A by installing the CAC 10F module Input circuits may be used as standard...

Page 16: ...ort Consult the factory for recommended printers EIA 485 Port EIA 485 compatible port on the LED 10IM option module supports up to 32 LED 10 Remote Annunciators or 32 sets of ACM 8RF Relay Modules or 32 AFM Series Annunciators or 32 LDM Series Annunciators or any combi nation of the four devices totalling 32 Telephone Lines Fully supervised at all times voltage is sensed to 4 volts and current is ...

Page 17: ...he cabinet Cabinet The cabinet is red with an attractive navy blue front overlay The backbox measures 16 900 42 9 cm X 14 500 36 8 cm X 4 625 11 8 cm and provides space for two bat teries up to 12 Amp Hours Also available is an optional dress panel DP 5210UD which mounts inside the cabinet Transformer Assembly One 100VA transformer is provided standard with the panel An optional 100VA trans former...

Page 18: ...2 13 Remote Printer Connections on page 34 The Baud rate is programmable Program Options on page 40 CAC 10F Module The CAC 10F Module can be used to convert the 10 Style B Class B Initiating Device Circuits to 10 Style D Class A IDCs and the two Style Y Class B Notification Appliance Circuits to two Style Z Class A NACs The CAC 10F module connects to J10 on the main circuit board Refer to Figure 2...

Page 19: ...us In addition they provide remote Acknowledge Silence Reset and Drill functions The ACS Series Annunciators require the use of the LED 10IM Interface Module For more detailed information refer to the appropriate annunciator manual ACM 16ATF The Annunciator Control Module 16ATF contains 16 red alarm and 16 yellow trouble LEDs a system trou ble LED an ON LINE POWER LED and a local piezo sounder wit...

Page 20: ...es power and control for a maximum of three expander modules expander modules are not required when interfacing to the MS 5210UD The LDM 32F and LDM E32F have output connectors which are used to drive lamps or LEDs and input connectors which are used for remote switch functions The LDM Series requires the use of the LED 10IM Interface Module Refer to the LDM Series Lamp Driver Modules Manual for a...

Page 21: ...ts corresponding outputs NAC Control Input 1 controls power supply output circuits 1 and 2 NAC Control Input 2 controls output circuits 3 and 4 During the inactive state the remote power supply supervises its NAC field wiring for short and open circuits If a fault is detected the supply will enter a trouble condition and illuminate the corresponding NAC trouble LED Output Circuits 1 4 however once...

Page 22: ...ocated on the inside of the FACP door 1 9 3 Telephone Company Rights and Warnings The telephone company under certain circumstances may temporarily discontinue services and or make changes in its facilities services equipment or procedures which may affect the operation of this control panel The telephone company however is required to give advance notice of such changes or interruptions If the co...

Page 23: ...the number of conductors required for the devices to be installed Sufficient knockouts are pro vided for wiring convenience Select the appropriate knockout s and pull the required conductors into the box Note that there are no knockouts on the left hinged side of the cabinet All wiring should be in accordance with the National and or Local codes for fire alarm systems 2 2 Backbox Mounting Open the...

Page 24: ...ox 2 00 2 00 2 00 2 00 2 00 2 00 1 75 4 445 cm 4 445 cm 1 50 3 81 cm 3 81 cm 3 81 cm 3 81 cm 3 81 cm 4 445 cm 4 445 cm 11 43 cm 3 81 cm 36 83 cm 29 21 cm 5 08 cm 1 75 1 50 4 5 1 50 4 6 1 58 11 5 1 75 1 75 Back of Box Back of Box 4 115 cm 3 14 cm 4 115 cm 42 926 cm 11 68 cm 29 21 cm 4 115 cm 28 10 cm 11 062 1 62 FIGURE 2 1 Cabinet Dimensions and Knockout Locations Top Left Side Right Side Bottom ...

Page 25: ... installed To install the BB 17F 1 Mount the FACP cabinet to the wall 2 Remove knockouts on the bottom of the FACP cabinet and top of the BB 17F 3 Using conduit hang the BB 17F from the FACP cabinet making sure there is at least of clearance between the two cabinets 4 Anchor the BB 17F to the wall FIGURE 2 2 FACP Backbox and Battery Box TR 4 R Optional BB 17F ...

Page 26: ...tain any power disconnect devices A separate Earth Ground connection must be made to ensure proper panel operation and lightning and transient protection Connect the Earth Ground wire minimum 14 AWG 2 00 mm2 to one of the transformer mounting studs Do not use conduit for the Earth Ground connection since this does not provide reliable protection Secondary Power Source Batteries Observe polarity wh...

Page 27: ...m of five waterflow devices may be used on any circuit programmed as a waterflow zone per NFPA 72 Four wire smoke detectors may be connected to any zone Resettable power is provided via TB2 Terminals 3 and 4 Refer to the Fire Lite Device Compatibility Document for a list of compatible smoke detectors It is allowable to mix an assortment of device types i e smoke detectors heat detectors pull stati...

Page 28: ...ge 30 FIGURE 2 4 Style B Initiating Device Circuit Connections Style B Class B Initiating Device Circuit supervised and power limited 4 7K watt P N 71252 UL listed UL listed compatible 2 wire smoke detector UL listed compatible 2 wire smoke detector Manual Pull Station Manual Pull Station Heat Detector Heat Detector Dummy Load all unused circuits P N 71245 FIGURE 2 5 Auxiliary Power Connections No...

Page 29: ...able Silence Inhibited March Time Temporal or California rates Standard Relays The control panel provides two Form A relays rated for 2 0 amps 30 VDC resistive Two Form C relays can be added by installing the optional NAC REM NAC Relay module FIGURE 2 6 Notification Appliance Circuit Connections Style Y Class B Notification Appliance Circuit supervised and power limited 4 7K ohm watt N 71252 UL li...

Page 30: ... function The control panel s digital communicator is built into the main circuit board Connection and wiring of two phone lines is required as shown in Figure 2 8 FIGURE 2 8 Wiring Phone Jacks Primary Lines Incoming Telco Phone Lines Secondary Lines Incoming Telco Phone Lines Ring Ring Ring Ring Tip Tip Tip Tip Green Wire Green Wire Red Wire Red Wire To premise phones To premise phones Note Short...

Page 31: ...imited circuit wiring Furthermore all power limited and nonpower limited circuit wiring must enter and exit the cabinet through different knockouts and or conduits A typical wiring diagram for the MS 5210UD is illustrated in Figure 2 9 FIGURE 2 9 Typical Wiring Diagram for UL Power limited Requirements Power limited Circuits Nonpower limited Circuits Power limited Circuit Note that power lim ited ...

Page 32: ... metal standoff This is necessary in order to help protect against electrical transients Wire the Style Z Class A Notification Appliance Circuits NACs using TB4 of the MS 5210UD and TB1 of the CAC 10F module Wire the Style D Class A Initiating Device Circuits IDCs using TB5 of the MS 5210UD and TB2 of the CAC 10F module Make certain to observe polarity when connecting the devices to the circuits T...

Page 33: ...prevent bending or breaking of any pins It is important that the supplied screw and washer be used to secure the module to the metal standoff This is nec essary in order to help protect against electrical transients PRT 24 Printer Interface Module A remote printer may be permanently or temporarily connected to provide a hardcopy printout of normal current system status and activity program entries...

Page 34: ... 232 port on the printer The printer may be placed a maximum of 50 feet 15 24 m from the panel Note that a ground fault may occur on the control panel when this con nection is made For this reason it is important that there be no preexisting ground fault on the panel For permanent printer connection a ground fault is not allowed Printer Configuration The PRT 24 is required Also refer to the docume...

Page 35: ... pins are properly aligned to prevent bending or breaking of any pins It is important that the supplied screw and washer be used to secure the module to the metal standoff This is necessary in order to help protect against electrical transients LED 10 Series Remote LED Annunciator The LED 10 Series Annunciator connects to the MS 5210UD via the LED 10IM Interface Module It is recom mended that over...

Page 36: ...rface mount backbox ACM 8RF Address and SW3 DIP Switch Settings Each of the ten MS 5210UD IDCs can be assigned to an ACM 8RF relay Two relay modules are required with both set to the same address Use the decade rotary switches to set the address i e for address 01 position the first left switch so the arrow points to 0 and the second right switch so the arrow points to 1 Level Three Option Module ...

Page 37: ... enable or disable the onboard piezo sounder enable remote switch functions select a flashing LED function for new alarms and troubles and other functions A green ON LINE LED flashes to indicate ongoing communications with the host FACP The LDM 32F is supplied with four standoffs and screws for mounting to a CHS 4L chassis or custom backbox The LDM 32F is installed on the EIA 485 line using the LE...

Page 38: ...F has rotary address switches and is installed on the EIA 485 line using the LED 10IM Interface Module AFM 16AF Annunciator The Annunciator Fixed Module 16AF has 16 red alarm LEDs The annunciator address is fixed at 1 and com munication is via the EIA 485 line using the LED 10IM Interface Module The Local Silence Acknowledge switch functions as a local lamp test and silence for the annunciator pie...

Page 39: ...ire protection and places the panel into trouble A system off normal message is transmitted to the central station Programming via the PK 5210UD upload download software is accomplished with the fire protection active on 3 1 Entering Program Mode Program Mode is divided into four levels 1 Main Panel Options 2 Event Codes Transmission Formats 3 Option Module Selections 4 Upload Download Each level ...

Page 40: ...trated below 3 3 Program Options 3 3 1 Level 1 Main Panel Options Note that the factory default setting for Location 56 is 0 for Control Panel only This keeps the communicator off until location 56 is changed to 1 for panel communicator Once location 56 is set to 1 and a valid phone number is entered entry into the program mode will cause transmission of the System Off Normal report Primary Centra...

Page 41: ...rrier 2300 Hz ACK 7 4 1 Expanded 1800 Hz Carrier 2300 Hz ACK 8 4 1 Standard 1900 Hz Carrier 1400 Hz ACK 9 4 1 Expanded 1900 Hz Carrier 1400 Hz ACK A 4 2 Standard 1800 Hz Carrier 2300 Hz ACK B 4 2 Expanded 1800 Hz Carrier 2300 Hz ACK C 4 2 Standard 1900 Hz Carrier 1400 Hz ACK D 4 2 Expanded 1900 Hz Carrier 1400 Hz ACK E Contact ID DTMF 1400 2300 ACK F Future use Note Consult you Central Station for...

Page 42: ...elow 0 4 1 Ademco Express Standard DTMF 1400 2300 ACK 1 4 2 Ademco Express Standard DTMF 1400 2300 ACK 2 3 1 Standard 1800 Hz Carrier 2300 Hz ACK 3 3 1 Expanded 1800 Hz Carrier 2300 Hz ACK 4 3 1 Standard 1900 Hz Carrier 1400 Hz ACK 5 3 1 Expanded 1900 Hz Carrier 1400 Hz ACK 6 4 1 Standard 1800 Hz Carrier 2300 Hz ACK 7 4 1 Expanded 1800 Hz Carrier 2300 Hz ACK 8 4 1 Standard 1900 Hz Carrier 1400 Hz ...

Page 43: ...his time if the Silence or Acknowledge switch is pressed the piezos are silenced and the notification appliances may be held off for up to three minutes See Alarm Presignal Delay Timer Address 53 55 After the programmed delay period the notification appliances will activate if the source of the alarm is not cleared Presignal does not function for zones defined as Waterflow Supervisory Process Moni...

Page 44: ...tch causes the switch function to occur The switch must be returned to its normal position Zone 1 Function Selection 64 Factory default for zone 1 is 0 for 2 wire smoke detector Enter 1 for Pull Station 2 for Normally Open contact device 3 for Supervisory 4 for Supervisory autoresettable 5 for Waterflow silenceable 6 for Waterflow nonsilenceable 7 for critical and noncritical process monitoring 8 ...

Page 45: ... 9 for remote reset switch A for remote silence switch B for remote acknowledge switch or C for remote manual evacuate drill switch Zone 6 Function Selection 69 Factory default for zone 6 is 0 for 2 wire smoke detector Enter 1 for Pull Station 2 for Normally Open contact device 3 for Supervisory 4 for Supervisory autoresettable 5 for Waterflow silenceable 6 for Waterflow nonsilenceable 7 for criti...

Page 46: ... zone restoral event codes change automatically as shown in Table 3 2 Be certain to reprogram alarm event codes when selecting process monitoring functions Zone fault and disable event codes may also be user programmed refer to Ademco Contact ID Format Event Code Descriptions on page 109 Programming a zone as a remote switch causes no transmission of an alarm or alarm restoral event code The zone ...

Page 47: ... 20 hours D 21 hours E 22 hours F 23 hours Programmable Relay 1 78 Relay 1 on TB3 of the MS 5210UD main circuit board can be programmed to activate for any one of seven FACP conditions The factory default for address 78 is 0 for activation on alarm Program a 1 for supervisory 2 for supervisory autoresettable 3 for trouble 4 for communication fail 5 for process monitoring or 6 for pro cess monitori...

Page 48: ...lifornia 10 seconds On 5 seconds Off or 3 for Temporal second On second Off second On sec ond Off second On 1 seconds Off and then repeat Factory default is 0 for steady no coding Trouble Reminder 88 Factory default 0 disables the trouble reminder feature Selecting 1 will cause a reminding beep after the Silence or Acknowledge switch is pressed every 15 seconds during an alarm and beep every two m...

Page 49: ...n between each number while entering the code After pressing the ENTER STORE key the control panel will be in Program Mode and display P__1 with the 1 flashing Press 2 on the keypad and then the ENTER STORE key to select the Event Code Transmission Formats Level for program ming You are allowed up to ten minutes of idle time at this point before starting your programming otherwise the control pane...

Page 50: ... 4 16 Primary Zone 7 Disabled Code 4 17 Primary Zone 8 Disabled Code 4 18 Primary Zone 9 Disabled Code 4 19 Primary Zone 10 Disabled Code 4 20 Primary Drill Code 9 21 Primary AC Fault Code 9 22 Primary Zone 1 Fault Code F 23 Primary Zone 2 Fault Code F 24 Primary Zone 3 Fault Code F 25 Primary Zone 4 Fault Code F 26 Primary Zone 5 Fault Code F 27 Primary Zone 6 Fault Code F 28 Primary Zone 7 Fault...

Page 51: ...ault Restore Code D 79 Primary Zone 7 Fault Restore Code D 80 Primary Zone 8 Fault Restore Code D 81 Primary Zone 9 Fault Restore Code D 82 Primary Zone 10 Fault Restore Code D 83 Primary Earth Fault Restore Code A 84 Primary Low Battery Fault Restore Code A 85 Primary No Battery Fault Restore Code A 86 Primary Telco Primary Line Fault Restore Code A 87 Primary Telco Secondary Line Fault Restore C...

Page 52: ...8 Disabled Code 48 36 37 Primary Zone 9 Disabled Code 49 38 39 Primary Zone 10 Disabled Code 4A 40 41 Primary Drill Code 97 42 43 Primary AC Fault Code 92 44 45 Primary Zone 1 Fault Code F1 46 47 Primary Zone 2 Fault Code F2 48 49 Primary Zone 3 Fault Code F3 50 51 Primary Zone 4 Fault Code F4 52 53 Primary Zone 5 Fault Code F5 54 55 Primary Zone 6 Fault Code F6 56 57 Primary Zone 7 Fault Code F7 ...

Page 53: ...8 159 Primary Zone 7 Fault Restore Code D7 160 161 Primary Zone 8 Fault Restore Code D8 162 163 Primary Zone 9 Fault Restore Code D9 164 165 Primary Zone 10 Fault Restore Code DA 166 167 Primary Earth Fault Restore Code A1 168 169 Primary Low Battery Fault Restore Code A2 170 171 Primary No Battery Fault Restore Code A3 172 173 Primary Telco Primary Line Fault Restore Code A4 174 175 Primary Telco...

Page 54: ...Zone 10 Disabled Code 570 010 60 62 Primary Drill Code 604 000 63 65 Primary AC Fault Code 301 000 66 68 Primary Zone 1 Fault Code 380 001 69 71 Primary Zone 2 Fault Code 380 002 72 74 Primary Zone 3 Fault Code 380 003 75 77 Primary Zone 4 Fault Code 380 004 78 80 Primary Zone 5 Fault Code 380 005 81 83 Primary Zone 6 Fault Code 380 006 84 86 Primary Zone 7 Fault Code 380 007 87 89 Primary Zone 8 ...

Page 55: ...3 Secondary Zone 8 Disabled Code 4 234 Secondary Zone 9 Disabled Code 4 235 Secondary Zone 10 Disabled Code 4 236 Secondary Drill Code 9 237 Secondary AC Fault Code 9 238 Secondary Zone 1 Fault Code F 239 Secondary Zone 2 Fault Code F 240 Secondary Zone 3 Fault Code F 241 Secondary Zone 4 Fault Code F 242 Secondary Zone 5 Fault Code F 243 Secondary Zone 6 Fault Code F 244 Secondary Zone 7 Fault Co...

Page 56: ...295 Secondary Zone 7 Fault Restore Code D 296 Secondary Zone 8 Fault Restore Code D 297 Secondary Zone 9 Fault Restore Code D 298 Secondary Zone 10 Fault Restore Code D 299 Secondary Earth Fault Restore Code A 300 Secondary Low Battery Fault Restore Code A 301 Secondary No Battery Fault Restore Code A 302 Secondary Telco Primary Line Fault Restore Code A 303 Secondary Telco Secondary Line Fault Re...

Page 57: ...isabled Code 49 254 255 Secondary Zone 10 Disabled Code 4A 256 257 Secondary Drill Code 97 258 259 Secondary AC Fault Code 92 260 261 Secondary Zone 1 Fault Code F1 262 263 Secondary Zone 2 Fault Code F2 264 265 Secondary Zone 3 Fault Code F3 266 267 Secondary Zone 4 Fault Code F4 268 269 Secondary Zone 5 Fault Code F5 270 271 Secondary Zone 6 Fault Code F6 272 273 Secondary Zone 7 Fault Code F7 2...

Page 58: ... Secondary Zone 7 Fault Restore Code D7 376 377 Secondary Zone 8 Fault Restore Code D8 378 379 Secondary Zone 9 Fault Restore Code D9 380 381 Secondary Zone 10 Fault Restore Code DA 382 383 Secondary Earth Fault Restore Code A1 384 385 Secondary Low Battery Fault Restore Code A2 386 387 Secondary No Battery Fault Restore Code A3 388 389 Secondary Telco Primary Line Fault Restore Code A4 390 391 Se...

Page 59: ...10 Disabled Code 570 010 276 278 Secondary Drill Code 604 000 279 281 Secondary AC Fault Code 301 000 282 284 Secondary Zone 1 Fault Code 380 001 285 287 Secondary Zone 2 Fault Code 380 002 288 290 Secondary Zone 3 Fault Code 380 003 291 293 Secondary Zone 4 Fault Code 380 004 294 296 Secondary Zone 5 Fault Code 380 005 297 299 Secondary Zone 6 Fault Code 380 006 300 302 Secondary Zone 7 Fault Cod...

Page 60: ...ming Level to be accessed During Program Mode if no key is pressed within 10 min utes the panel will revert to Normal Mode Following are the various option modules and their addresses CAC 10F Class A Converter Card 00 The factory default entry of 0 in address 00 informs the FACP that there is no CAC 10F Class A Converter Card installed in the panel When a CAC 10F is installed 1 must be entered for...

Page 61: ...upervisory autoresettable 3 for trouble 5 for process monitoring 6 for autoresettable process monitoring NAC 3 Type Selection 09 This address programs NAC 3 if the NAC Relay Option Module has been enabled in address 06 The factory default entry for NAC 3 is 0 for enabled and silenceable Enter 1 for enabled and nonsilenceable or 2 for dis abled NAC 3 Silence Inhibit 10 This address is used for the ...

Page 62: ...n alarm It blinks at a 1 second ON 1 second OFF rate if the supervisory zone is in fault Should both an alarm and a fault occur on a supervisory zone at the same time the alarm takes priority and the blink rate is second ON second OFF The non supervisory function will turn on the red zone alarm LED for any type of zone function The blink rate at the annunciators is 1 second ON 1 second OFF for fir...

Page 63: ... gram this 4 digit code at the job site the first time that downloading is performed so that the called Service Termi nal can identify the control panel Factory default is 0000 Future use Service Terminal Number 1 Phone Number 04 19 Addresses 04 through 19 are reserved for the Service Terminal Number 1 phone number Factory default is all Fs Valid entries are 0 9 plus A B C D and E Use F to designa...

Page 64: ...s Factory default is 0 for secondary backup only Enter 1 to transmit to both Central Station phone numbers Enter 2 to transmit to the first available receiver CAUTION Do not alter entry while the communicator is active 3 3 5 Default Programming To return all program entries in all four levels to their factory original settings perform the following steps only when the system is idle in Normal stan...

Page 65: ... ten zones programmed as a remote reset switch remotely on any of the LED 10 Series annunciators the LDM graphic annunciators or the AFM series annunciators If any of the System Reset Switches are pressed the control panel will Clear the display and status LEDs Turn off the Notification Appliance Circuits Reset all zones by temporarily removing power Silence the onboard piezo sounder Store reset m...

Page 66: ...ashing system LEDs to steady The second press of the switch stops the scrolling and holds the event on the display for five seconds Subsequent pressing of the switch steps through each active event The Acknowledge Step switch must be pressed within 15 seconds to prevent NACs from turning on if alarm presignal is selected For additional information on alarm presignal refer to Programming Instructio...

Page 67: ...AC Bell 2 Disabled bEL2 Bell 2 Fault d_b3 NAC Bell 3 Disabled bEL3 Bell 3 Fault d_b4 NAC Bell 4 Disabled bEL4 Bell 4 Fault drLL Fire Drill no_1 Primary Phone Line Fault E__1 Zone 1 Enabled no_2 Secondary Phone Line Fault E__2 Zone 2 Enabled PA_1 Process Monitoring Alarm Zone 1 E__3 Zone 3 Enabled PA_2 Process Monitoring Alarm Zone 2 E__4 Zone 4 Enabled PA_3 Process Monitoring Alarm Zone 3 E__5 Zon...

Page 68: ...need for action in connection with the supervision or maintenance of sprinklers extinguishing systems or other protective systems System Silence LED A yellow LED that turns on to indicate that an Alarm or Trouble condition exists in the system but Notification Appliance Circuits if programmed as silenceable and local piezo sounder have been silenced Primary Line Active LED A red LED that indicates...

Page 69: ...system Pressing the 1st Event key or one of the ACK keys will stop the scrolling The 1st Event key will also cause the display to show the First alarm that occurred after the panel was last reset cleared of all active events and placed into normal mode Operation of the Up and Down arrow keys will display all remaining events in sequence If events to be displayed include system troubles only one ev...

Page 70: ...ink the FACP supervisory LED second On second Off Display the following message SUXX XX Zone Number Communicate the supervisory condition to the Central Station Store the supervisory message in the History File Pulse system piezo sounders second On second Off Turn on appropriate zone relay output ACM 8RF Turn on any system relays main circuit board programmed for supervisory activation Output syst...

Page 71: ...abled F__10 Trouble Zone 10 d__2 Zone 2 Disabled d_b1 Bell 1 Disabled d__3 Zone 3 Disabled d_b2 Bell 2 Disabled d__4 Zone 4 Disabled d_b3 Bell 3 Disabled d__5 Zone 5 Disabled d_b4 Bell 4 Disabled d__6 Zone 6 Disabled F__A Annunciator Fault d__7 Zone 7 Disabled F__P Printer Fault d__8 Zone 8 Disabled F__E Earth Fault d__9 Zone 9 Disabled Lo_b Low Battery d_10 Zone 10 Disabled no_b No Battery F__1 T...

Page 72: ...zone Store the alarm restoral message in the History File Turn off the piezo sounder Turn off appropriate zone relay output ACM 8RF Turn off any system relays main circuit board programmed for process alarm activation Output alarm restoral message to printer Terminate upload or download communications Turn off all remote annunciator zone alarm LEDs Note that for any zone programmed for autoresetta...

Page 73: ...eft of the display Next press the b key followed by the NAC number to be disabled The b and the NAC number will appear on the far right display characters Pressing ENTER STORE will disable the NAC All system annunciators will show general trouble status and the main panel display will show the NAC disabled message turn on the system trouble LED and activate relays programmed for system trouble The...

Page 74: ...re will disconnect any local premises phones sharing the same telephone line All transmissions to central stations will be sent over the Primary Central Station phone line In the event of noisy phone lines transmissions will be sent over the backup Secondary phone line Two phone numbers must be programmed the Primary Central Station phone number and the Secondary Central Sta tion phone number Ther...

Page 75: ...S SSS S TS TSTSTS TS Y SSSS TSTS2 SSSS TSY System Trouble Restore SSS S RTS SSS S RTS RTSRTSRTS RTS Y SSSS RTSRTS2 SSSS RTSY Zone Disable SSS S DZ SSS S DZ DZDZDZ DZ Z SSSS DZDZ2 SSSS DZZ Zone Disable Restore SSS S RDZ SSS S RDZ RDZRDZRDZ RDZ Z SSSS RDZRDZ2 SSSS RDZZ Bell Disable SSS S DB SSS S DB SSSS DBDB2 SSSS DBDB2 Bell Disable Restore SSS S RB SSS S RB SSSS RBRB2 SSSS RBRB2 Low Battery SSS S ...

Page 76: ...ble Restore 1st digit RB2 Bell Disable Restore 2nd digit L Low Battery 1st digit L2 Low Battery 2nd digit RL Low Battery Restore 1st digit RL2 Low Battery Restore 2nd digit N No Battery 1st digit N2 No Battery 2nd digit RN No Battery Restore 1st digit RN2 No Battery Restore 2nd digit P AC Loss 1st digit P2 AC Loss 2nd digit RP AC Loss Restore 1st digit RP2 AC Loss Restore 2nd digit FD Fire Drill 1...

Page 77: ...its fault Communication Trouble Printer Trouble Annunciator Trouble EIA 485 fault System Off Normal Process Monitoring Alarm 4 Restoral Reports Zone Alarm Supervisory Zone s enabled Fire Drill AC Zone fault Earth Battery Telephone Line Notification Appliance Circuits Communication Printer Annunciator EIA 485 System Off Normal Process Monitoring Restored 5 System Test Lowest Priority Red LEDs are p...

Page 78: ...1 4 software and Rev C line card at Rev 1 5 software 8 Model 2 only 9 Version 1 62 software TABLE 4 3 Compatible UL Listed Receivers Format Addresses 16 42 Ademco 685 1 Silent Knight 9000 2 ITI CS 4000 3 FBI CP220FB Osborne Hoffman Models 1 2 Radionics 6000 6 Radionics 6500 5 Sescoa 3000R 7 Surguard MLR 2 9 0 4 1 Ademco Express 1 4 2 Ademco Express 8 2 3 1 Standard 1800 2300 4 3 3 1 Expanded 1800 ...

Page 79: ...t character For audible walktest press the ENTER STORE key For silent walktest press the 1 key followed by the ENTER STORE key Once in Walk Test Mode the control panel will immediately Blink the trouble LED Activate the trouble relay If an audible walktest is performed the MS 5210UD will turn on the Notification Appliance Circuits for four seconds for the first alarm on a zone Subsequent alarms wi...

Page 80: ...ible when the system is in Walk Test Mode 5 2 History Mode All Normal Mode events are stored in a History File list for future recall Recall is possible via the 4 character dis play or via an optional printer See the following page for a list and description of each event displayed This History File list is a first in first out FIFO buffer Only the most recent events may be called up from memory O...

Page 81: ...U_5 Supervisory 5 Alarm E__1 Enable Zone 1 SU_6 Supervisory 6 Alarm E__2 Enable Zone 2 SU_7 Supervisory 7 Alarm E__3 Enable Zone 3 SU_8 Supervisory 8 Alarm E__4 Enable Zone 4 SU_9 Supervisory 9 Alarm E__5 Enable Zone 5 SU10 Supervisory 10 Alarm E__6 Enable Zone 6 PA_1 Process Alarm Zone 1 E__7 Enable Zone 7 PA_2 Process Alarm Zone 2 E__8 Enable Zone 8 PA_3 Process Alarm Zone 3 E__9 Enable Zone 9 P...

Page 82: ...k the FACP trouble LED Blink all remote annunciator LEDs Activate the FACP trouble relays if programmed for trouble operation Disable the Notification Appliance Circuits Output all troubleshoot voltage readings to external printer Disable the alarm relay Transmit the off normal message to the Central Station s Continue to communicate any events not yet acknowledged at the Central Station prior to ...

Page 83: ...econds the control panel goes off hook to acquire a dial tone The control panel keypad may be used as a telephone touchpad for number dialing Once the first digit is pressed the display will move the C or D character one position to the left while placing the digit to be dialed on the far thest right display position Continue to press the phone numbers to be dialed Successive depressions of the EN...

Page 84: ...Ds will stay on for five seconds then the control panel will return to Normal Mode 5267 spells LAMP on a Touch Tone phone 5 5 Print Mode Refer to Figure 2 13 Remote Printer Connections on page 34 for proper PRT 24 Interface module connection to the main circuit board before proceeding A printer may be temporarily or permanently connected to the panel Pro gram address 4 in Program Mode Level 3 to a...

Page 85: ...arm Cleared 06 26 1996 14 16 03 Low Battery Detected 06 26 1996 14 16 09 Normal Battery 06 26 1996 14 16 15 Loss of AC Power 06 26 1996 14 16 19 AC Power Restore 06 26 1996 14 16 42 Drill Mode Entered 06 26 1996 14 16 51 System Reset 06 26 1996 14 17 25 Drill Mode Cleared 06 26 1996 14 17 33 Entering Walktest Mode 06 26 96 14 32 15 Zone 2 Pull Station Active 06 26 1996 14 33 20 Entering Trouble Sh...

Page 86: ...1 Downloading Program General Any time that the control panel is downloaded whether initiated at the jobsite or remotely a secret code factory default 0000 is verified between the control panel and the Service Terminal Changing the Secret Code may only be accomplished at the Service Terminal and subsequently loaded into the control panel Future upload or download requests cause verification of the...

Page 87: ...d the Service Terminal will communicate and transfer data without first contacting a Central Station When the data transfers are completed and the control panel disconnects from the Service Terminal the control panel will call the Central Station and report one of the following conditions Upload download request received Upload and or download successful Upload download failed To prevent the reque...

Page 88: ...ssage is transmitted informing the Central Station s of one of the following downloading was successful uploading was successful uploading downloading was not successful Data Protection Integrity Options allow programming of single data entries single programming levels 1 4 and the entire programming of all four levels simultaneously Use caution when selecting programming choices and verify all en...

Page 89: ...l Station s and transmit a request for upload download message if programmed to do so If this message is accepted the control panel will proceed to the next step 7 Return call to Service Terminal 8 Verify secret code 9 Begin downloading 10 Upon completion of download call back Central Station s and report a successful download or failed upload download status if programmed to do so 6 4 Uploading I...

Page 90: ...l will proceed to the next step 7 Return call to Service Terminal 8 Verify secret code 9 Begin uploading 10 Upon completion of upload call Central Station s back and report a successful upload or failed upload down load status if programmed to do so During the uploading process the fire protection remains active Should a system trouble or alarm condition occur the control panel immediately termina...

Page 91: ...located in the backbox 2 Batteries larger than 12 Ampere Hour up to 18 Ampere Hour require the BB 17F battery box TABLE A 1 Battery Calculation Standby Load Current amps X Required Standby Time in Hours 24 or 60 Hours _______________ Alarm Load Current amps X Required Alarm Time in Hours i e 5 min 0 084 hours _______________ Add Standby and Alarm Load for Required Ampere Hour Battery _____________...

Page 92: ...ype of Devices Current amps Total Current amps Main Circuit Board 1 X 0 138 0 138 LED 10IM 1 max X 0 017 LED 10 Annunciator X 0 023 Misc Annunciators X 1 PRT 24 1 max X 0 0 CAC 10F 1 max X 0 004 NAC REM 1 max X 0 002 2 wire Detector Heads X 1 1 Refer to the Device Compatibility Document for standby current 2 wire Detector Heads X 1 4 wire Detector Heads X 1 4 wire Detector Heads X 1 Power Supervis...

Page 93: ...ions of terminals TB2 Terminals 1 and 2 0 500 amps regulated filtered 24 VDC 5 120 Hz ripple 10 mVRMS nonresettable power 100 Hz ripple if MS 5210UDE TB2 Terminals 3 and 4 0 500 amps regulated filtered 24 VDC 5 120 Hz ripple 10 mVRMS resettable power 100 Hz ripple if MS 5210UDE X 4 wire Smoke Detector X Power Supervision Relay4 4 Must use compatible listed Power Supervision Relay X 0 025 Notificat...

Page 94: ...45 46 Secondary Central Station Account Code Valid keys are 0 F 47 48 49 50 Secondary Central Station 24 Hour Test Time Enter military time i e 1400 for 2 00 PM 51 Secondary Number Test Time Interval Enter 0 for 24 hour 1 for 12 hour 2 for 8 hour 3 for 6 hour 52 Alarm Presignal Enter 0 to disable 1 to enable 53 54 55 Alarm Presignal Delay Time Enter 0 179 additional seconds default 120 seconds 56 ...

Page 95: ...on 2 for normally open contact devices 3 for supervisory devices 4 for supervisory devices autoresettable 5 for waterflow silenceable 6 for waterflow nonsilenceable 7 for process monitoring 8 for autoresettable process monitoring 9 for remote reset switch A for remote silence switch B for remote acknowledge switch C for remote manual evacuate drill switch 69 Zone 6 Function Select Enter 0 for 2 wi...

Page 96: ... 2 Definition Enter 0 for alarm 1 for supervisory 2 for supervisory autoresettable 3 for trouble 4 for communications fail 5 for process monitoring 6 for process monitoring autoresettable 80 Notification Appliance Circuit 1 Selection Enter 0 for enabled silenceable 1 for enable nonsilenceable 2 for disable 81 Silence Inhibit NAC 1 Enter 0 for no silence inhibit 1 to inhibit silencing of NAC 1 for ...

Page 97: ...ormat 43 44 45 46 Secondary Central Station Account Code 47 48 49 50 Secondary Central Station 24 Hour Test Time 0000 12 00 midnight 51 Secondary Number Test Time Interval 0 for 24 hour 52 Alarm Presignal 0 for no alarm presignal 53 54 55 Alarm Presignal Delay Time 120 second alarm presignal delay 56 Communicator Fire Panel Selection 0 for panel only operation 57 Backup Reporting 0 to report to Se...

Page 98: ... 00 for no delay 76 Alarm Verification 0 for no verification 77 AC Loss Delay 0 for 6 hours 78 Programmable Relay 1 Definition 0 for alarm 79 Programmable Relay 2 Definition 3 for trouble 80 Notification Appliance Circuit 1 Selection 0 for enabled silenceable 81 Silence Inhibit NAC 1 0 for no silence inhibit 82 Auto Silence NAC 1 0 for no auto silence 83 Coding NAC 1 0 for steady no coding 84 Noti...

Page 99: ... 48 49 50 51 52 53 54 55 56 57 58 59 60 61 62 63 64 65 66 67 68 69 70 71 72 73 74 75 76 77 78 79 80 81 82 83 84 85 86 87 88 89 90 91 92 93 94 95 96 97 98 99 100 101 102 103 104 105 106 107 108 109 110 111 112 113 114 115 116 117 118 119 120 121 122 123 124 125 126 127 128 129 130 131 132 133 134 135 136 137 138 139 140 141 142 143 144 145 146 147 148 149 150 151 152 153 154 155 156 157 158 159 160...

Page 100: ... 272 273 274 275 276 277 278 279 280 281 282 283 284 285 286 287 288 289 290 291 292 293 294 295 296 297 298 299 300 301 302 303 304 305 306 307 308 309 310 311 312 313 314 315 316 317 318 319 320 321 322 323 324 325 326 327 328 329 330 331 332 333 334 335 336 337 338 339 340 341 342 343 344 345 346 347 348 349 350 351 352 353 354 355 356 357 358 359 360 361 362 363 364 365 366 367 368 369 370 371...

Page 101: ... 113 114 115 116 117 118 119 120 121 122 123 124 125 126 127 128 129 130 131 132 133 134 135 136 137 138 139 140 141 142 143 144 145 146 147 148 149 150 151 152 153 154 155 156 157 158 159 160 161 162 163 164 165 166 167 168 169 170 171 172 173 174 175 176 177 178 179 180 181 182 183 184 185 186 187 188 189 190 191 192 193 194 195 196 197 198 199 200 201 202 203 204 205 206 207 208 209 210 211 212...

Page 102: ...2 323 324 325 326 327 328 329 330 331 332 333 334 335 336 337 338 339 340 341 342 343 344 345 346 347 348 349 350 351 352 353 354 355 356 357 358 359 360 361 362 363 364 365 366 367 368 369 370 371 372 373 374 375 376 377 378 379 380 381 382 383 384 385 386 387 388 389 390 391 392 393 394 395 396 397 398 399 400 401 402 403 404 405 406 407 408 409 410 411 412 413 414 415 416 417 418 419 420 421 42...

Page 103: ...8 69 70 71 72 73 74 75 76 77 78 79 80 81 82 83 84 85 86 87 88 89 90 91 92 93 94 95 96 97 98 99 100 101 102 103 104 105 106 107 Event Codes Transmission Format Programming Sheets for All 3 1 All 4 1 and 4 2 Expanded Formats Secondary Central Station 216 217 218 219 220 221 222 223 224 225 226 227 228 229 230 231 232 233 234 235 236 237 238 239 240 241 242 243 244 245 246 247 248 249 250 251 252 253...

Page 104: ...4 2 Expanded Formats Secondary Central Station 216 217 218 219 220 221 222 223 224 225 226 227 228 229 230 231 232 233 234 235 236 237 238 239 240 241 242 243 244 245 246 247 248 249 250 251 252 253 254 255 256 257 258 259 260 261 262 263 264 265 266 267 268 269 270 271 272 273 274 275 276 277 278 279 280 281 282 283 284 285 286 287 288 289 290 291 292 293 294 295 296 297 298 299 300 301 302 303 3...

Page 105: ... 22 23 24 25 26 27 28 29 30 31 32 33 34 35 36 37 38 39 40 41 42 43 44 45 46 47 48 49 50 51 52 53 54 55 56 57 58 59 60 61 62 63 64 65 66 67 68 69 70 71 72 73 74 75 76 77 78 79 80 81 82 83 84 85 86 87 88 89 90 91 92 93 94 95 96 97 98 99 100 101 102 103 104 105 106 107 108 109 110 111 112 113 114 115 116 117 118 119 120 121 122 123 124 125 126 127 128 129 130 131 132 133 134 135 136 137 138 139 140 1...

Page 106: ... 252 253 254 255 256 257 258 259 260 261 262 263 264 265 266 267 268 269 270 271 272 273 274 275 276 277 278 279 280 281 282 283 284 285 286 287 288 289 290 291 292 293 294 295 296 297 298 299 300 301 302 303 304 305 306 307 308 309 310 311 312 313 314 315 316 317 318 319 320 321 322 323 324 325 326 327 328 329 330 331 332 333 334 335 336 337 338 339 340 341 342 343 344 345 346 347 348 349 350 351...

Page 107: ...6 77 78 79 80 81 82 83 84 85 86 87 88 89 90 91 92 93 94 95 96 97 98 99 100 101 102 103 104 105 106 107 108 109 110 111 112 113 114 115 116 117 118 119 120 121 122 123 124 125 126 127 128 129 130 131 132 133 134 135 136 137 138 139 140 141 142 143 144 145 146 147 148 149 150 151 152 153 154 155 156 157 158 159 160 161 162 163 164 165 166 167 168 169 170 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1...

Page 108: ...2 293 294 295 296 297 298 299 300 301 302 303 304 305 306 307 308 309 310 311 312 313 314 315 316 317 318 319 320 321 322 323 324 325 326 327 328 329 330 331 332 333 334 335 336 337 338 339 340 341 342 343 344 345 346 347 348 349 350 351 352 353 354 355 356 357 358 359 360 361 362 363 364 365 366 367 368 369 370 371 372 373 374 375 376 377 378 379 380 381 382 383 384 385 386 1 1 1 1 1 1 1 1 1 1 1 ...

Page 109: ...ut from a Central Station receiver such as the Ademco 685 of alarm and trouble reports in the Ademco Contact ID Reporting Structure follows Notes 1 18 which is used in the reporting structure to identify the transmission as Contact ID is not printed out in the alarm and trouble report 2 Q which is the Event Qualifier for the reporting structure is printed out in the report as an E for New Event or...

Page 110: ... 130 Burglary BURG Burglary 131 Perimeter BURG Perimeter 132 Interior BURG Interior 133 24 Hour BURG 24 Hour 134 Entry Exit BURG Entry Exit 135 Day Night BURG Day Night 136 Outdoor BURG Outdoor 137 Tamper BURG Tamper 138 Near Alarm BURG Near Alarm General Alarms 140 140 General Alarm ALARM General Alarm 141 Polling loop open ALARM Polling Loop Open 142 Polling loop short ALARM Polling Loop Short 1...

Page 111: ...ow Battery 303 RAM checksum bad TROUBLE Bad RAM Checksum Restore not applicable 304 ROM checksum bad TROUBLE Bad ROM Checksum Restore not applicable 305 System reset TROUBLE System Reset Restore not applicable 306 Panel program changed TROUBLE Programming Changed Restore not applicable 307 Self test failure TROUBLE Self Test Failure 308 System shutdown TROUBLE System Shutdown 309 Battery test fail...

Page 112: ...tter low battery TROUBLE RF Sensor Batt Open Close 400 400 Open Close OPENING CLOSING 401 Open Close by user OPENING User CLOSING User 402 Group Open Close OPENING Group User CLOSING Group User 403 Automatic Open Close OPENING Automatic CLOSING Automatic 404 Late Open Close OPENING Late CLOSING Late 405 Deferred Open Close Opening not used Closing not used 406 Cancel OPENING Cancel Closing not use...

Page 113: ...ed DISABLE Dialer Disable 552 Radio transmitter disabled DISABLE Radio Disable Bypasses 570 570 Zone bypass BYPASS Zone Bypass 571 Fire bypass BYPASS Fire Bypass 572 24 Hour zone bypass BYPASS 24 Hour Bypass 573 Burglar bypass BYPASS Burg Bypass 574 Group bypass BYPASS Group Bypass Test Misc 600 601 Manual trigger test TEST Manually Triggered Restore not applicable 602 Periodic test report TEST Pe...

Page 114: ...r supervisory autoresettable 3 for trouble 5 for process monitoring 6 for autoresettable process monitoring 9 NAC 3 Type Selection Factory default is 0 for NAC 3 enabled silenceable enter 1 for enabled nonsi lenceable 2 for disabled 10 NAC 3 Silence Inhibit Factory default is 0 for no silence inhibit enter 1 to inhibit silencing of NAC 3 for one minute after an alarm 11 NAC 3 Autosilence feature w...

Page 115: ...ammable Relay 3 Definition 1 supervisory 8 Programmable Relay 4 Definition 4 communication fail 9 NAC 3 Type Selection 0 for NAC 3 enabled silenceable 10 NAC 3 Silence Inhibit 0 for no silence inhibit 11 NAC 3 Autosilence feature which silences signals after a selected period 0 for no autosilence for NAC 3 12 NAC 3 Signal Coding 0 for steady no coding 13 NAC 4 Type Selection 0 for NAC 4 enabled si...

Page 116: ...no sharing of phone line 1 for sharing 42 Upload Download Backup Reporting Enter 0 for Upload Download reports to go to the Secondary Central Station Phone Number on backup only 1 for Upload Download reports to always go to the Secondary 2 for Upload Download reports to go to the first available Central Station phone number Upload Download Programming Reference Sheets Factory Defaults To enter Pro...

Page 117: ...evices Untwisted unshielded wire Do not exceed 100 ohms 10 000 3 000 m 8 000 2 400 m 4 875 1 480 m 3 225 975 m 12 AWG 3 25 mm2 Belden 9583 WPW999 14 AWG 2 00 mm2 Belden 9581 WPW995 16 AWG 1 30 mm2 Belden 9575 WPW991 18 AWG 0 75 mm2 Belden 9574 WPW975 EIA 485 LED 10IM Inter face Module power limited Connects to annunciator mod ules and relay module Twisted shielded pair with a characteristic impeda...

Page 118: ...rotection is on Requires PRT 24 option module 5267 LAMP Turns on all system LEDs on the main PCB except Modem Kissoff Primary Active and Secondary Active LEDs and all system annunciators for 5 seconds Fire protection is on 3696 DOWN Allows for downloading the entire program file to the panel Must have service terminal ready Fire protection remains on TABLE 6 3 FUNCTION MODES CODE ACTIVITY NOTES 34...

Page 119: ...Fire Panel Selection 43 computer programming requirements 86 control panel 11 controls 15 D data protection 88 data transfer simultaneous 90 DC power 28 nonresettable 28 resettable 28 Default Programming 64 description of panel 11 dial tone 16 digital communicator 11 16 22 30 location 30 dimensions 24 cabinet 24 DIP switch 19 display see also indicator 15 down arrow key 15 67 download initiated at...

Page 120: ...O off normal reporting 72 off on hook 16 operating power 26 connections 26 operation 65 69 operation mode 118 Option Module Selection 60 optional modules 32 output circuit 28 DC power 28 P panel identification number 63 88 panel keypad 40 panel time out 87 piezo sounder 15 19 69 PK 5210UD 12 18 39 86 see also programming 11 power system 11 power supply 92 Primary Central Station Number 24 Hour Tes...

Page 121: ...estoral 70 switch 19 switch functions in program mode 40 normal mode 65 switches 15 system power see also power 11 system silence LED 68 system status 11 12 18 69 system test 77 system trouble 69 T telephone 11 telephone circuit 28 30 Ringer Equivalence Number REN 22 RJ31X male connector 22 wiring 30 telephone dialing see also touchtone rotary 12 telephone line supervision 16 telephone line input ...

Page 122: ...Notes 122 Document 50193 Rev E 01 30 02 P N 50193 E ...

Page 123: ...ransportation prepaid to the manufacturer This writing constitutes the only warranty made by this manufacturer with respect to its products The manufacturer does not represent that its products will prevent any loss by fire or otherwise or that its products will in all cases provide the protection for which they are installed or intended Buyer acknowledges that the manufacturer is not an insurer a...

Page 124: ...World Headquarters One Fire Lite Place Northford CT 06472 1653 USA 203 484 7161 Fax 203 484 7118 www firelite com ...