Operation and Function Modes
82
Document #15140 Rev.G 01/02/02 P/N 15140:G
Appendix C
Operation and Function Modes
C.1
Operation Modes
C.2
Function Modes
TABLE C-1:
Operation Modes
CODE
ACTIVITY
NOTES
6676 (NORM)
Returns to normal operation
Fire protection is on
7764 (PROG)
Enters Program Mode
4 levels of programming may be entered.
Fire protection is off
9255 (WALK)
Enters Walktest Mode
May select audible walktest function. Fire
protection is off
4478 (HIST)
View History File
Use display or printer to view History File.
Fire protection is off
8768 (TROU)
Activates internal system voltmeter for trou-
bleshooting and diagnosing problems
Fire protection is off while voltmeter function
is enabled
7746 (PRIN)
Sends status, history file, walktest file, trou-
bleshoot voltages and entire programming
selections to printer
Fire protection is off. Requires PRT-24
option module
5267 (LAMP)
Turns on all LEDs on the main circuit board
and all system annunciators for five seconds
Fire protection is on
3696 (DOWN)
Allows for downloading the entire program
file to the panel
Must have service terminal ready. Fire pro-
tection remains on
TABLE C-2:
Function Modes
CODE
ACTIVITY
NOTES
3472 (DISA)
Allows disabling of any input zone
May only disable one zone at a time. Places
system into trouble
3622 (ENAB)
Allows enabling (return to normal) of any
zone
May only enable one zone at a time
3745 (DRIL)
Performs drill function by turning on all
NAC outputs
Transmission of drill function to Central Sta-
tion is defaulted to ON
3337 (DEFP)
Reprograms all entries for programming
back to the original factory settings
Entry of code must be performed two times in
rapid succession as a safety feature. Use
caution when using this feature