Document #15140 Rev.G 01/02/02 P/N 15140:G
55
Operation
4.3.5 Trouble Condition Response
Upon detection of one or more trouble conditions, the control panel will perform the following:
✓
Blink the trouble LED (1 second On and 1 second Off)
✓
Activate the trouble relay
✓
Display the appropriate trouble message(s) in priority fashion from the highest priority to the lowest.
Note that the Up Arrow, Down Arrow or 1st Event key must be pressed to view the messages
✓
Communicate the trouble conditions to the Central Station
✓
Store the trouble conditions in the History file
✓
Sound the piezo sounder 1 second On and 1 second Off
✓
Output the system trouble messages to the printer
✓
Terminate upload or download communications
Note: When AC brownout occurs, the AC LED is turned off and the trouble LED blinks. Should the brownout con-
dition remain, it will be transmitted to the Central Station after a delay (see program address 64).
Possible trouble messages that may appear on the display are as follows:
4.3.6 Trouble Condition Restoral
Upon restoral of all trouble conditions, the control panel performs the following:
✓
Shut off the trouble LED
✓
Deactivates the trouble relay
✓
Turn off the AC Power LED if the trouble was loss of AC
✓
Clear the display of all trouble messages
✓
Communicate the restored trouble condition(s) to the Central Station
✓
Output the system trouble restoral message to the printer
✓
Terminate upload or download communications
4.3.7 Off Normal Reporting
Removing the control panel from Normal Mode and placing it into any other mode causes the transmission of an 'off
normal' fault message to the Central Station. Returning the panel to Normal Mode causes the transmission of a
'return to normal' restoral message.
d__1
d__2
d__3
d__4
d__5
F__1
F__2
F__3
F__4
F__5
F__A
F__E
Zone 1 Disabled
Zone 2 Disabled
Zone 3 Disabled
Zone 4 Disabled
Zone 5 Disabled
Trouble Zone 1
Trouble Zone 2
Trouble Zone 3
Trouble Zone 4
Trouble Zone 5
Annunciator Fault
Earth Fault
Low Battery
No Battery
Primary C.S.# Comm. Fault
Secondary C.S. # Comm. Fault
Bell 1 Fault or Disabled
Bell 2 Fault or Disabled
Primary Phone Line Fault
Secondary Phone Line Fault
AC Power Loss (shown only when requested)
Lo_b
no_b
PH_1
PH_2
bEL1
bEL2
no_1
no_2
_AC_