Specifications
16
Document #15140 Rev.G 01/02/02 P/N 15140:G
1.6.5 PRT-24 Printer Interface Module
The Printer Interface Module may be used to connect a printer to the control panel for the purpose of printing a his-
tory report, walktest file, troubleshoot report, program entries or current system status. Printers require separate
external primary power. Connect the PRT-24 module (with cable) to the serial EIA-232 port on the printer. The
module mounts to the J2 connector on the main circuit board.
Note that an EDP listed printer must be used if the
printer will be permanently attached to the control panel. Refer to Figure 2-15, “Remote Printer Connections,” on
page 30.
1.6.6 DP-5024UD Dress Panel
A red dress panel is available as an option. The dress panel restricts access to the system wiring while allowing
access to the membrane switch panel. Refer to Figure 1-1, “Optional DP-5024UD,” on page 11.
1.6.7 BB-17F Battery Box
The BB-17F battery box may be used to house two batteries, from 12 Amp Hour to 18 Amp Hour. The battery box
mounts directly below the cabinet and main circuit board. Refer to Figure 2-3, “Backbox and Battery Box,” on page
21. The BB-17F is red and is provided with knockouts.
1.6.8 PK-5024UD Programming Kit
This kit includes one 3½" diskette plus Instruction Manual P/N 50041. When the software is loaded into an IBM
compatible computer, it creates an off-line Service Terminal that allows any MS-5024UD panel to be uploaded or
downloaded over standard telephone lines.
1.7
Specifications
AC Power - TB1
MS-5024UD: 120 VAC, 60 Hz, 2.3 amps
MS-5024UDE: 220/240 VAC, 50 Hz, 1.2 amps
Wire size: minimum #14 AWG (2 mm
2
) with 600V insulation
Battery (lead acid only) - J1
Maximum Charging Circuit: Normal Flat Charge - 27.6V @ 0.8 amp
Maximum Charger Capacity: 17 Amp Hour battery. (MS-5024UD cabinet holds maximum 7 Amp Hour battery.
Larger batteries require Fire•Lite BB-17F or other UL listed battery cabinet).
Initiating Device Circuits - TB2
Detector Zones 1, 2, 3, 4, 5
Power-limited Circuitry
Operation: All zones are NFPA Style B, Zone 3 is NFPA Style B or Style D. Use CAC-5F module for Style D
operations
Normal Operating Voltage: 24 VDC (ripple = 100 mV maximum)
Alarm Current: 26 mA
Short Circuit Current: 42 mA maximum
Maximum Loop Resistance: 100 ohms
End-of-Line Resistor: 4.7K ohms, ½ watt (P/N 27072 UL listed)
Detector Loop Current is sufficient to ensure operation of one alarmed detector per zone
Standby Current: 7.26 mA (includes ELR and 2 mA maximum detector current)
Smoke Detector Identifier A
Refer to Fire•Lite Device Compatibility Document for listed compatible devices