ES-200X Series Manual —
P/N LS10131-000FL-E:C 7/25/2018
117
Read Status
Operating Instructions
Pressing
2
while viewing the Program Check screen #1 will display a screen which will indicate if any output zones have not been pro-
grammed to at least one input zone. Use the up and down arrow keys to view all zones.
Pressing
3
while viewing the Program Check screen #1 will display a screen which will indicate if any input zones have not been pro-
grammed to at least one output zone. Use the up and down arrow keys to view all zones.
4.24.8 History
Pressing
3
while viewing Read Status Screen #3 will display the following screen:
The operator can view all events which have been stored in the history file, only alarms or other events, such as troubles or supervisories,
by pressing the corresponding number key.
4.24.9 Annunciators
Pressing
1
while viewing Read Status Screen #4 will display the following screens:
Pressing
1
or
2
for
ANN-BUS
while viewing the Annunciator Screen allows the operator to view the settings and devices for each ANN-
BUS. Press
1
for the
Primary ANN-BUS
and
2
for the
Secondary ANN-BUS
.
The ANN-BUS Screen #1 indicates if the ANN-BUS has been enabled
Yes
or disabled
No
.
Pressing
2
for
Modules Installed
while viewing ANN-BUS Screen #1 will display screens for ANN-BUS Addresses 1 -8 and the devices
installed at each address. A subscreen will display the options that have been programmed for each device.
Pressing
3
for
ANN-BUS Options
while viewing the Annunciator Screen allows the operator to view the
settings for any ANN-S/PG, ANN-LED, ANN-80, and ANN-100 installed in the system.
Pressing
1
for
ANN-S/PG Options
while viewing ANN-BUS Screen #2 will display the options selected for the installed ANN-S/PG
annunciators.
Pressing
2
for
ANN-LED Options
while viewing ANN-BUS Screen #2 will display the options selected for the installed ANN-LED
annunciators.
Pressing
3
for
ANN-80/100 Options
while viewing ANN-BUS Screen #2 will display the options selected for the installed ANN-80 or
ANN-100 annunciators.
4.24.10 Communicator
Pressing
2
while viewing Read Status Screen #4 will display the following screens:
The Communicator Screen #1 indicates if an IPOTS-COM has been installed
Yes
or
No
.
HISTORY
1=VIEW ALL
2=VIEW ALARMS
3=VIEW OTHER EVENTS
READ STATUS
1=ANNUNCIATORS
2=COMMUNICATOR
Read Status Screen #4
ANN-BUS SELECT
1=PRIMARY
2=SECONDARY
3=ANN-BUS OPTIONS
Annunciator Screen
ANN-BUS
ENABLED NO
2=MODULES INSTALLED
CLASS A NO
ANN-BUS Screen #1
ANN-BUS SELECT
1=PRIMARY
2=SECONDARY
3=ANN-BUS OPTIONS
Annunciator Screen
ANN-BUS
1=ANN-S/PG OPTIONS
2=ANN-LED OPTIONS
3=ANN-80/100 OPTIONS
ANN-BUS Screen #2
READ STATUS
1=ANNUNCIATORS
2=COMMUNICATOR
Read Status Screen #4
COMMUNICATOR
INSTALLED YES
2=POTS SETTINGS
3=IP SETTINGS
COMMUNICATOR
1=PRI COMM PATH
2=SEC COMM PATH
TBL REPORT LIMIT 0
COMMUNICATOR
1=EVENT CODES
TEST TIME INT 24
24HR TEST TIME 0100
Communicator Screen #1
Communicator Screen #2
Communicator Screen #3
COMMUNICATOR
REPORT STYLE POINT
Communicator Screen #4