Translation of the original instructions, SilentCare room air filter, Filtration Group GmbH, 01.02.21, Mat. No. 72488984, Version 01
7
Technical data
•
The room air filter is suitable for rooms up
to approx. 45
m
2
(max. 70
m
2
)
in size
(max. purification in booster mode).
•
According to current RKI studies, with 5-
fold exchange (5 air changes per hour)
and a room height of 2.5 m, 15 minutes
without air purification mean an increased
risk of infection.
Ambient temperature:.............................. +10°C to +40°C
Noise level: ....................................................... 42 dB(A)
Air flow: .......................................... 600 m
3
/h +/-50 m
3
/h
........................................ (max. 900 m
3
/h +/-50 m
3
/h (1)
Pressure: ................................................... Max. 18 mbar
Material: .......... Sheet steel housing, powder-coated, grey
Power [V]: .......................................... 220-240 V / 170 W
Insulation [IP]: ............................................ IP20 / class 1
Filter surface [m²]: .................................................. 15 m
2
Dimensions: ........... Height approx. 1100 mm, Ø 500 mm
Weight: ..................................................... Approx. 32 kg
8
Transport and storage
WARNING!
Risk of injury if the equipment is tilted!
•
Do not install the room air filter on an uneven surface
and be careful not to tilt it during transport.
•
Two people are required to transport the equipment!
As-delivered condition
•
Completely assembled, packed and upright on a pallet.
Storage
•
Always store in the original packaging.
•
Always store in a dry, frost-free room.
Transport
•
Always transport upright on a pallet.
•
Do not remove the straps until the equipment reaches its
place of use.
•
Separate the packaging material and dispose of it in an
environmentally responsible way.
9
Installing the room air filter
WARNING!
Risk of reduced efficiency!
•
The equipment should always be installed in a dry,
frost-free environment!
•
The equipment is not suitable for outdoor use!
WARNING!
Danger of tripping!
•
Lock the casters at the place of use!
•
Lay the power cable so that no-one can trip over it!
A minimum distance of 2 metres is required
from the wall!
•
Ensure that the air outlet is unobstructed at all times. It
must neither be closed nor altered.
•
Install the equipment such that the air and heat vents
cannot be obstructed.
9.1
Electrical connections
DANGER!
Danger of electric shock!
•
Risk of serious or fatal injury in case of
contact with electrical components.
The plug must be removed in order to
disconnect the room air filter from the
mains!
The power cable must have the following
fuse protection:
Time delay 6.3 A / 250 V
•
Compare the data indicated on the name-plate with the
values for the power supply system.
•
Avoid using extension cables.
•
Connect the plug to the mains.
The system is now ready for operation.