7.9

 

 

Handling endless loop problems      

  
As explained above, an endless loop problem will be declared when the number of consecutive 

wash cycles triggered by the DP sensor exceeds the “Loop Limit” defined during setup. When an 

endless loop problem is detected, it will be indicated on the screen (LOOPING) and the alarm 
output will be activated. In addition, the indication of DP should no longer be taken into account 
as a trigger for washing. Subsequent wash cycles will only be triggered by a countdown interval. 
The problem will be considered solved when the constant indication of the DP sensor has been 
eliminated. 

  

7.10

 

Handling low pressure 

  
When  an  indication  of  closed  contact  is  received  at  the  controller's  low  pressure  input,  the 
symbol            will  begin  to  appear  flashing  on  the  display.  All  activities  will  stop  including  the 
countdown to the next wash cycle. If there is low pressure while a flush sequence is in progress, 
when the low pressure condition ends, the flush sequence will start from the beginning instead 
of continuing from the stop point. 

 

 

7.11

 

Connecting the DP sensor to the filter system  

The  DP  sensor  is  connected  to  the  filter  system  by  2  command 
tubes, one that comes from the filter inlet (high pressure) will be 
connected to the red point, and the one that comes from the outlet 
(low  pressure  will  go  towards  the  black  point.  It  is  important  to 
install a small 120 mesh filter (not provided) between the red dot 
and the high pressure connection point. 

 

  

  

7.12

 

Low battery 

 

The unit has two levels of low battery indication. The first level is when the battery voltage drops 
to  the  first  level,  the  sign            will  start  to  appear  on  the  screen.  When  the  battery  voltage 
continues  to  drop  and  reaches  the  second  level,  all  outputs  will  close,  the  screen  will  clear 
displaying only the low battery icon. 

 

 

7.13

 

Manual activation 

 

The wash sequence can be activated manually by using the “MANUAL” key. When activated 

manually, the icon        will appear on the screen. The same key will be used to manually end the 
sequence in progress. 

 

U

SER 

M

ANUAL 

HYDRAULIC-200-H 

14 

The small filter to be added between the high pressure inlet 

and the red dot

. It is the user's responsibility to add this filter 

 

Summary of Contents for HYDRAULIC-200-H

Page 1: ...www itmfilters com Self cleaning Mesh Filter User manual HYDRAULIC 200 H Serial number _________________ Purchase date _________________...

Page 2: ...3 Exploded view table 9 7 Control panel 10 7 1 Features listing 10 7 2 How to program the controller 11 7 3 The chain of editable fields 11 7 4 Wash time 12 7 5 DP preset value 12 7 6 Wash mode 12 7...

Page 3: ...eplate 1 2 Basic concepts Filtration surface Area that allows water to pass while retaining suspended particles Recommended flow Optimal filtration must take into account the quality of the source wat...

Page 4: ...dance with the applicable European Directives Directive 2006 42 CE on Machines Annex IIA Directive 2014 68 EU on Pressure Equipment and Directive 2014 35 EU on Electrical Material These quality requir...

Page 5: ...ge 10 585 323 273 195 14135 235 177 HYDRAULIC 212 H COMPACT Flange 12 645 355 300 215 14135 235 181 TABLE 1 Manufacturing technical characteristics Materials o Carbon steel metal components o Zinc pla...

Page 6: ...C 206 H 355 1455 352 900 203 1865 400 1300 HYDRAULIC 208 H COMPACT 355 1455 352 900 203 1865 400 1300 HYDRAULIC 208 H 355 1741 438 1100 203 2150 400 1585 HYDRAULIC 210 H COMPACT 355 1741 438 1100 203...

Page 7: ...operation with automatic cleaning OPEN cleaning cycle CLOSE filter operation without automatic cleaning USER MANUAL HYDRAULIC 200 H 5 IMAGE 4 SOLENOID CALIBRATED ORIFICE HYD REL MANUAL ACTUATOR SUCTIO...

Page 8: ...ge When the mesh filter becomes clogged it produces a pressure difference between the inlet and outlet manifolds The automatic cleaning cycle starts when it reaches a pressure difference of 0 3 kg cm...

Page 9: ...nology used in the manufacture of the HYDRAULIC 200 H filter offers high filtration surfaces with compact lengths due to the maximization of the filter cartridge 6 Maintenance and spare parts 6 1 Main...

Page 10: ...ilters com you can find a video tutorial with the maintenance process 6 2 Exploded view USER MANUAL HYDRAULIC 200 H 8 23 25 24 20 30 29 28 27 26 33 32 31 34 17 22 21 1 2 3 4 5 6 7 3 8 9 11 10 12 13 15...

Page 11: ...rogrammer 1 1 1 1 28 Filter Cartridge 1 HYD 204 H 04 00 1 HYD 206 H 04 00 1 HYD 208 H 04 00 1 HYD 210 H 04 00 29 Centering Disk 1 HYD 206 H 05 07 1 HYD 206 H 05 07 1 HYD 206 H 05 07 1 HYD 206 H 05 07...

Page 12: ...ump The AC model contains an internal transformer that can be powered by 110V or 220V from which 24v AC is generated for the solenoids The wash cycles can be triggered either by time or by means of th...

Page 13: ...ntered the user will not be able to go back and must keep pressing the ENTER key repeatedly to go through the chain of editable fields until reaching the WASH TIME field again Please note that before...

Page 14: ...ash cycles will be triggered The options are as follows OFF There will be no washing By time In this case the wash cycles will be repeated at a selected interval or triggered by the DP signal dependin...

Page 15: ...roblem The options are 1 10 or no which means to ignore the loop problem Yes No assigning an output for alarm activation Yes No assigning an output for Delay Valve activation This is a special mode th...

Page 16: ...start from the beginning instead of continuing from the stop point 7 11 Connecting the DP sensor to the filter system The DP sensor is connected to the filter system by 2 command tubes one that comes...

Page 17: ...www itmfilters com 7 14 Timing diagram Without delay valve With delay valve Main valve Valve 1 Valve 2...

Page 18: ...The external DP sensor is optional and is intended to be used in cases where the integrated electronic DP sensor is not included 2 The unit can be powered by 6v DC or 12v DC 3 The solenoids are 12v D...

Page 19: ...ensor is optional and is intended to be used in cases where the integrated electronic PD sensor is not included 2 The unit is powered by 24v AC transformed from 220 110 v AC 3 In the solenoids it will...

Page 20: ...ted analog electronic DP sensor or external dry contact DP sensor Pressure sensor Dry contact pressure sensor Operating temperature AC model 0 60 C Power source 220 or 110 v AC 50 or 60 Hz with includ...

Page 21: ...ablished quality or is outside the specifications indicated in the technical tables vi A use of flow discordant with the water quality according to the parameters defined in the technical tables vii P...

Page 22: ...www itmfilters com INTRAMESA MZ S A Pol gono Armentera P 99 22400 Monz n Huesca www itmfilters com info itmfilters com Tel 974 10 50 05...

Reviews: