7.8
Setup
In order to enter the configuration process, press and hold the ENTER key for 3 seconds. The
unit will detect how many “plug in” boards (each with 2 outputs) are used in the particular case.
The assignment of the outputs depends on the definitions made during the configuration
process. During the configuration process, the following characteristics are defined:
Main valve -
(Sustaining valve)
Waiting time -
DP delay -
Loop limit -
Alarm -
Delay Valve -
See outputs -
Yes / No. When the answer is “Yes” you
can define the Pre delay.
Wait between the opening of the main valve and the opening of
Station No. 1 The selectable delay intervals are as follows:
5, 10, 15, 20, 25, 30, 35, 40, 45, 50, 55 seconds
1, 1.5, 2, 2.5, 3, 3.5, 4, 4.5, 5, 5.5, 6 minutes
The delay between stations - 5, 10, 15, 20, 25, 30, 35, 40, 45, 50, 55,
60 seconds.
The delay that the DP sensor reading is expected to be stable before
reacting - 5, 10, 15, 20, 25, 30, 35, 40, 45, 50, 55, 60 seconds.
The number of consecutive wash cycles triggered by the DP sensor
before deciding that there is a no-end-of-loop problem. The options
are: 1-10 or "no" which means to ignore the loop problem.
Yes / No - assigning an output for alarm activation.
Yes / No - assigning an output for Delay Valve activation.
This is a special mode that allows you to review the list of outputs to
see how each of the outputs is assigned. Use the + key to change the
“no” to a “yes” and confirm with “Enter”, then use the + key to scroll
through the list. The output number is displayed in the lower left
corner and its assigned role appears in large letters in the center of
the screen. Note that the number of possible outputs that can be used
is always odd since it results from the number of plug-in boards
included (2 outputs each). However, if the number of outputs
required is not an odd number, then the last valve assigned as a filter
can be canceled by using the manual operations key.
Pressure units -
To choose the units to be used for pressure measurement. Select
between BAR or PSI.
Calibration -
Zero calibration of the integrated electronic DP sensor. If the sensor
ports are disconnected select Calibration = Yes.
Version -
The last screen in configuration indicates the version of the controller
software. The version is displayed with four digits like the following:
00
13
U
SER
M
ANUAL
HYDRAULIC-200-H