Filters itm HYDRAULIC-200-H User Manual Download Page 1

 

 

 

 

www.itmfilters.com 

 

 

 

 

 

 

 

 

 

 

Self-cleaning Mesh Filter 

User manual HYDRAULIC-200-H 

 

 

Serial number:  

_________________ 

 

 

Purchase date: 

_________________ 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

  

Summary of Contents for HYDRAULIC-200-H

Page 1: ...www itmfilters com Self cleaning Mesh Filter User manual HYDRAULIC 200 H Serial number _________________ Purchase date _________________...

Page 2: ...3 Exploded view table 9 7 Control panel 10 7 1 Features listing 10 7 2 How to program the controller 11 7 3 The chain of editable fields 11 7 4 Wash time 12 7 5 DP preset value 12 7 6 Wash mode 12 7...

Page 3: ...eplate 1 2 Basic concepts Filtration surface Area that allows water to pass while retaining suspended particles Recommended flow Optimal filtration must take into account the quality of the source wat...

Page 4: ...dance with the applicable European Directives Directive 2006 42 CE on Machines Annex IIA Directive 2014 68 EU on Pressure Equipment and Directive 2014 35 EU on Electrical Material These quality requir...

Page 5: ...ge 10 585 323 273 195 14135 235 177 HYDRAULIC 212 H COMPACT Flange 12 645 355 300 215 14135 235 181 TABLE 1 Manufacturing technical characteristics Materials o Carbon steel metal components o Zinc pla...

Page 6: ...C 206 H 355 1455 352 900 203 1865 400 1300 HYDRAULIC 208 H COMPACT 355 1455 352 900 203 1865 400 1300 HYDRAULIC 208 H 355 1741 438 1100 203 2150 400 1585 HYDRAULIC 210 H COMPACT 355 1741 438 1100 203...

Page 7: ...operation with automatic cleaning OPEN cleaning cycle CLOSE filter operation without automatic cleaning USER MANUAL HYDRAULIC 200 H 5 IMAGE 4 SOLENOID CALIBRATED ORIFICE HYD REL MANUAL ACTUATOR SUCTIO...

Page 8: ...ge When the mesh filter becomes clogged it produces a pressure difference between the inlet and outlet manifolds The automatic cleaning cycle starts when it reaches a pressure difference of 0 3 kg cm...

Page 9: ...nology used in the manufacture of the HYDRAULIC 200 H filter offers high filtration surfaces with compact lengths due to the maximization of the filter cartridge 6 Maintenance and spare parts 6 1 Main...

Page 10: ...ilters com you can find a video tutorial with the maintenance process 6 2 Exploded view USER MANUAL HYDRAULIC 200 H 8 23 25 24 20 30 29 28 27 26 33 32 31 34 17 22 21 1 2 3 4 5 6 7 3 8 9 11 10 12 13 15...

Page 11: ...rogrammer 1 1 1 1 28 Filter Cartridge 1 HYD 204 H 04 00 1 HYD 206 H 04 00 1 HYD 208 H 04 00 1 HYD 210 H 04 00 29 Centering Disk 1 HYD 206 H 05 07 1 HYD 206 H 05 07 1 HYD 206 H 05 07 1 HYD 206 H 05 07...

Page 12: ...ump The AC model contains an internal transformer that can be powered by 110V or 220V from which 24v AC is generated for the solenoids The wash cycles can be triggered either by time or by means of th...

Page 13: ...ntered the user will not be able to go back and must keep pressing the ENTER key repeatedly to go through the chain of editable fields until reaching the WASH TIME field again Please note that before...

Page 14: ...ash cycles will be triggered The options are as follows OFF There will be no washing By time In this case the wash cycles will be repeated at a selected interval or triggered by the DP signal dependin...

Page 15: ...roblem The options are 1 10 or no which means to ignore the loop problem Yes No assigning an output for alarm activation Yes No assigning an output for Delay Valve activation This is a special mode th...

Page 16: ...start from the beginning instead of continuing from the stop point 7 11 Connecting the DP sensor to the filter system The DP sensor is connected to the filter system by 2 command tubes one that comes...

Page 17: ...www itmfilters com 7 14 Timing diagram Without delay valve With delay valve Main valve Valve 1 Valve 2...

Page 18: ...The external DP sensor is optional and is intended to be used in cases where the integrated electronic DP sensor is not included 2 The unit can be powered by 6v DC or 12v DC 3 The solenoids are 12v D...

Page 19: ...ensor is optional and is intended to be used in cases where the integrated electronic PD sensor is not included 2 The unit is powered by 24v AC transformed from 220 110 v AC 3 In the solenoids it will...

Page 20: ...ted analog electronic DP sensor or external dry contact DP sensor Pressure sensor Dry contact pressure sensor Operating temperature AC model 0 60 C Power source 220 or 110 v AC 50 or 60 Hz with includ...

Page 21: ...ablished quality or is outside the specifications indicated in the technical tables vi A use of flow discordant with the water quality according to the parameters defined in the technical tables vii P...

Page 22: ...www itmfilters com INTRAMESA MZ S A Pol gono Armentera P 99 22400 Monz n Huesca www itmfilters com info itmfilters com Tel 974 10 50 05...