INSTALLATION AND MAINTENANCE INSTRUCTIONS

UL 268 listed for Open Air Protection 
UL 268A listed for Duct Applications
UL 521 listed for Heat Detectors

This sensor must be installed in compliance with the control panel 
system installation manual. The installation must meet the require-
ments of the Authority Having Jurisdiction (AHJ). Sensors offer maxi-
mum performance when installed in compliance with the National 
Fire Protection Association (NFPA); see NFPA 72. For a complete list 
of compatible bases, refer to the Base/Sensor Cross Reference Chart at 

 

systemsensor.com.

GENERAL DESCRIPTION

FIK-2351TIR is a plug-in type multi-criteria smoke sensor that offers a photo-
electric sensing chamber combined with a 135°F (57.2°C) fixed temperature 
heat detector and infrared (IR) sensors. The FIK-2351TIR also transmits an 
alarm signal due to heat (135°F/57.2°C) per UL 521.

All sensors transmit an analog representation of smoke density over a commu-
nication line to a control panel. Rotary dial switches are provided for setting 
the sensor’s address. (See Figure 2.) 

Two LEDs on the sensor are controlled by the panel to indicate sensor status. 
An output is provided for connection to an optional remote LED annunciator  
(P/N RA100Z). 

Fike panels offer different features sets across different models. As a result, 
certain features of the photoelectric sensors may be available on some control 
panels, but not on others. 

FIK-2351TIR supports Fike IDP mode systems. The possible features available 
in the multi-criteria smoke sensors, if supported by the control unit are:

1.   The sensor’s LEDs can operate in three ways—on, off, and blinking–and 

they can be set to red, green, or amber. This is controlled by the panel. 

2.   The remote output may be synchronized to the LED operation or con-

trolled independent of the LEDs.

3.   Devices are point addressable up to 159 addresses.

Please refer to the operation manual for the UL listed control panel for specific 
operation. The photoelectric sensors require compatible addressable com-
munications to function properly. Connect these sensors to listed-compatible 
control panels only. 

SPACING

Fike recommends spacing sensors in compliance with NFPA 72. In low air 
flow applications with smooth ceilings, space sensors 30 feet apart (9.1 m). 
For specific information regarding sensor spacing, placement, and special ap-
plications, refer to NFPA 72 or the System Smoke Detector Application Guide, 
available from System Sensor. 

WIRING GUIDE

All wiring must be installed in compliance with the National Electrical Code, 
applicable local codes, and any special requirements of the Authority Having 
Jurisdiction. Proper wire gauges should be used. The installation wires should 
be color-coded to limit wiring mistakes and ease system troubleshooting. 
Improper connections will prevent a system from responding properly in the 
event of a fire.

Remove power from the communication line before installing sensors.

1.   Wire the sensor base (supplied separately) per the base wiring diagram. 

(See Figure 1.) 

2.   Set the desired address on the sensor address switches. (See Figure 2.)

3.   Install the sensor into the sensor base. Push the sensor into the base while 

turning it clockwise to secure it in place.

4.   After all sensors have been installed, apply power to the control panel and 

activate the communication line.

5.   Test the sensor(s) as described in the TESTING section of this manual.

FIGURE 1. WIRING DIAGRAM

2

3

1

2

3

3

1

2

1

(–)

(+)

+

-

UL LISTED COM

PA

TIBLE

CONTR

OL 

PA

NE

L

CLASS A OPTIONAL WIRING

REMOTE 

ANNUNCIATOR

(–)
(+)

C0129-04

CAUTION

Do not loop wire under terminal 1 or 2. Break wire run to provide supervision 
of connections.

FIGURE 2. ROTARY ADDRESS SWITCHES

 

TENS

ONES

9

10

11

12

13

14

15

8

7

6

5

4

3

2

1 0

9

8

7

6

5

4

3

2

1 0

 C0162-00

I56-6639-00

1

 704 SW 10th Street

 Blue Springs, MO 64015

 Phone: 816.229.3405; Fax: 816.228.9277 

www.fike.com

FIK-2351TIR 

Multi-Criteria Photoelectric,  

Thermal and Infrared Sensor

SPECIFICATIONS

Operating Voltage Range: 

15 to 32 VDC

Operating Current @ 24 VDC:   200 uA (one communication every 5 sec. with green LED blink on communication)

Maximum Alarm Current:  

2 mA @ 24 VDC (one communication every 5 seconds with red LED solid on)

Maximum Current:  

4.5 mA @ 24 VDC (one communication every 5 seconds with amber LED solid on)

Operating Humidity Range: 

15% to 90% Relative Humidity, Non-condensing

Operating Temperature Range:  32°F to 115°F (0°C to 47°C)

Air Velocity: 

0 to 300 ft./min. (0 to 91.4 m/min.) 

Height: 

2.0˝ (51 mm) installed in B300-6 Base

Diameter: 

6.2˝ (156 mm) installed in B300-6 Base; 4.1˝ (104 mm) installed in B501 Series Base

Weight: 

3.4 oz. (95 g) 

Isolator Load Rating:  

0.0063*

*Please refer to your isolator base/module manual for isolator calculation instructions.

R

http://www.fike.com/06-912

For system/product documentation including 

installation, operation, and maintenance, 

scan QR code or enter URL provided. 

  

I56-6639-001 

 