ProtoCessor/ProtoCarrier Start-Up Guide 

 

 

APPLICABILITY & EFFECTIVITY 

Explains the operation and installation of the following hardware: 

ProtoCessor:

       FPC-FD2; FPC-F03; FPC-F04 

ProtoCarrier:

       FPC-C01; FPC-CD2 

 

The instructions are effective for the above as of December2012 

 

 

 

 

Summary of Contents for ProtoCarrier FPC-C01

Page 1: ...or ProtoCarrier Start Up Guide APPLICABILITY EFFECTIVITY Explains the operation and installation of the following hardware ProtoCessor FPC FD2 FPC F03 FPC F04 ProtoCarrier FPC C01 FPC CD2 The instructions are effective for the above as of December2012 ...

Page 2: ...to the ProtoCarrier Boards 11 5 1 Connection using RS 232 ProtoCarrier FPC C01 11 5 1 1 Power Pin assignments 11 5 1 2 Voltage Selection 11 5 1 3 Summary of SolderLinks 11 5 2 Connection using RS 485 ProtoCarrier FPC CD2 12 5 2 1 Connection to FPC FD2 12 5 2 2 Connection to FPC F04 12 5 2 3 6 pin Phoenix Connector Pin Assignments 12 5 2 4 Voltage Selection 13 6 Software Interface Connection to the...

Page 3: ...5 FPC CD2 23 8 4 1 RS 485 Signal LEDs 23 Appendix A Useful Features 24 Appendix A 1 Enhanced Network Security 24 Appendix B Reference 25 Appendix B 1 ProtoCessor FFP Specifications 25 Appendix B 2 ProtoCarrier Specifications 25 Appendix B 3 Mounting Drawings 26 Appendix B 3 1 FPC FD2 on FPC CD2 26 Appendix B 3 2 FPC F03 on FPC CD2 26 Appendix B 3 3 FPC F04 on FPC CD2 27 Appendix B 4 Address DIP Sw...

Page 4: ...tion Equipment device e g a modem Full serial status indication is provided with LED s The ProtoCarrier 485 FPC CD2 board provides an RS 485 interface to the TTL socket serial port provided on the ProtoCessor The board uses a screw terminal connection 1 1 BTL Mark BACnet Testing Laboratory The BTL mark is a symbol that indicates to a consumer that a product has passed a series of rigorous tests co...

Page 5: ... 3 FFP LON ProtoCessor FPC F04 RS 485 Phoenix connector for Field serial protocol support Ethernet port for Diagnostics and Host or Field protocol support Dip Switches See 4 End of line termination switch Soft Reset button Ethernet port for Diagnostics and Host or Field protocol support ProtoCessor TTL Socket Supporting RX and TX signals 5VDC Underneath ProtoCessor TTL Socket Supporting RX and TX ...

Page 6: ... 408 964 4444 Fax 408 262 2269 Toll Free 888 509 1970 x141 email support protocessor com 2 4 Powering up the ProtoCessor 1 Set the DIP switches FPC FD2 See Section 4 2 Connect up the Field and Host cables 3 Connect the power 4 If the Field protocol is an Ethernet protocol refer to Section 6 for information on Software interface connections ...

Page 7: ... protocols Supports 5VDC or 9 30VAC VDC 3 1 ProtoCarrier 232 FPC C01 The ProtoCarrier 232 FPC C01 board is a carrier board for ProtoCessor devices providing a serial port interface to the TTL socket serial port provided on the ProtoCessor The board allows easy connection to the serial ports using a DB 9 connector connected as a DTE Data Terminal Equipment so that it may be connected to DCE Data Co...

Page 8: ...ket serial port provided on the ProtoCessor The board can be powered from a fixed 5V DC supply or a 9V 30V AC DC The input voltage is rectified and regulated to meet the requirements of the ProtoCessor devices 3 2 1 Board Layout The following diagram shows the layout of the ProtoCarrier 485 board indicating the most important ports and devices RS 485 Port Signal LED s See 8 4 1 Connector labeled a...

Page 9: ...the field by editing the configuration file Refer to the ProtoCessor Configuration Manual If the FPC FD2 is used with the FPC CD2 the DIP switches on the FPC CD2 must be used The switches on the FPC FD2 are disabled The DIP switch settings are the same for FPC FD2 and FPC CD2 Physical DIP Switch Settings ProtoCessor FFP 485 Equals ProtoCarrier Bank A A1 A0 A2 A1 A3 A2 A4 A3 A5 A4 A6 A5 A7 A6 A8 A7...

Page 10: ... Off Off On Off 600 Off Off On On 1200 Off On Off Off 2400 Off On Off On 4800 Off On On Off 9600 Off On On On 19200 On Off Off Off 20833 On Off Off On 28800 On Off On Off 38400 On Off On On 57600 On On Off Off 76800 On On Off On 115200 On On On Off 4 1 3 Using S0 S3 to select and load Configuration Files The S bank of DIP switches S0 S3 can be used to select and load a particular configuration fil...

Page 11: ...nd select Voltage as described in Sections 5 1 1 to 5 1 3 5 1 1 Power Pin assignments Pin No Pin Assignment Pin 1 V Pin 2 V Pin 3 FRAME GND 5 1 2 Voltage Selection By default the Voltage is set for 9V 30V AC DC input To use a fixed 5V DC input the SolderLink P1 needs to be cut and SolderLinks P2 and P3 need to be connected 5 1 3 Summary of SolderLinks Link Function 9V 30V AC DC input Select Desele...

Page 12: ... are disabled Plug the ProtoCessor into the ProtoCessor socket on the ProtoCarrier board as depicted below The ProtoCarrier 485 s 6 pin green connector connects to Power and to the serial RS 485 port on a third party device The pinouts for the 6 connector are located at the base of the 6 pin connector Select Voltage as described in Section 5 2 4 5 2 1 Connection to FPC FD2 5 2 2 Connection to FPC ...

Page 13: ...1970 x141 email support protocessor com 5 2 4 Voltage Selection Voltage selection is done using a jumper on Headers JP3 and JP4 For 9V 30V AC or DC input the Jumpers on JP3 and JP4 should be in the position shown in blue For a fixed 5V DC input the Jumpers on JP3 and JP4 should be in the position shown in orange A power LED is included to display whether the board is using 5V power or not ...

Page 14: ...oCarrier via the Ethernet port Figure 1 Ethernet port location of ProtoCessor Connect a standard CAT5 Ethernet cable straight through or cross between the PC and ProtoCessor ProtoCarrier The Default IP Address of the ProtoCessor is 192 168 1 24 Subnet Mask is 255 255 255 0 If the PC and the ProtoCessor ProtoCarrier are on different IP Networks assign a static IP Address to the PC on the 192 168 1 ...

Page 15: ...een 6 3 Set IP Address for BACnet IP From the GUI main home page click on setup and then Network Settings to enter the Edit IP Address Settings menu Modify the IP address N1 IP address field of the ProtoCessor ProtoCarrier Ethernet port If necessary change the Netmask N1 Netmask field Type in a new Subnet Mask If necessary change the IP Gateway Default Gateway field Type in a new IP Gateway Note I...

Page 16: ...rotoCarrier Start Up Guide Page 16 of 34 ProtoCessor 1991 Tarob Court Milpitas California 95035 USA Web www protocessor com Tel 408 964 4444 Fax 408 262 2269 Toll Free 888 509 1970 x141 email support protocessor com ...

Page 17: ...elimited file called CONFIG CSV If a custom configuration was ordered the ProtoCessor will be programmed with the relevant device registers in the Config csv file for the first time start up If not the product is shipped with a sample config csv that shows an example of the drivers ordered In the main menu of the FS GUI screen go to Setup File Transfer Retrieve Click on config csv and open or save...

Page 18: ...pport protocessor com 7 3 Load the Updated Configuration file In the main menu of the FS GUI screen go to Setup File Transfer Update Browse and select the csv file open then click Submit Once download is complete click the System Restart Button or simply cycle power to the ProtoCessor to put the new file into operation Note that it is possible to do multiple downloads to the ProtoCessor before res...

Page 19: ...o the third party device s and test the application From the main menu of FS GUI click on View Connections to see the number of messages on each protocol For troubleshooting assistance refer to any of the troubleshooting Appendices in the related Driver Supplements and Configuration Manual FieldServer Technologies also offers a Technical support page on the FieldServer website at www FieldServer c...

Page 20: ...offline To establish the cause of the error go to the error screen of the RUI interface Config ERR Config ERR LED will go on solid 15 seconds after power up It will turn off after 5 seconds A steady amber light will indicate a configuration error exists in the active configuration See the Error Screen in the Remote User Interface for a description of the configuration error Node Offline Node Offli...

Page 21: ...econds after power up signifying normal operation The ProtoCessor will be able to access RUINET shortly after this LED comes on During the first 45 60 seconds the LED should be dark Upon successful operation of GP105 the ProtoCessor will go through diagnostics of the field port communications RX On normal operation of FFP F04 the RX LED will flash when a message is received on the LON port of the ...

Page 22: ...hooting Tips If PWR LED does not come on and LA and LB don t flash call or email ProtoCessor support support ProtoCessor com If PWR LED does not come on but the LA and LB flash then the PWR LED is broken If LA and LB don t start to flash there could be a problem with the ProtoCessor and you need to contact support ProtoCessor com If GP105 never comes on then you need to contact ProtoCessor support...

Page 23: ...ocessor com Tel 408 964 4444 Fax 408 262 2269 Toll Free 888 509 1970 x141 email support protocessor com 8 4 ProtoCarrier 485 FPC CD2 8 4 1 RS 485 Signal LEDs The RS 485 Signal LEDS are each labeled and correspond to the respective data lines sent from the ProtoCessor The following signals are provided RS 485 TX and RS 485 RX ...

Page 24: ...l Features Appendix A 1 Enhanced Network Security For enhanced network security one can disable RuiNet access to a FS GUI capable FieldServer by use of the RUI_Enable FieldServer parameter Adding the following to the configuration file will disable RuiNet Access FieldServer Title RUI_Enable FieldServer Name Disabled Enabled is the default if not specified Note In order to take a FieldServer Diagno...

Page 25: ...es 8 5 x 3 0 x 2 0 cm 3 3 x 1 2 x 0 8 inches Power Requirements Multi mode power adapter 9 30VDC or VAC or 5VDC Operating Temperature 40 C to 85 C 40 F to 185 F Humidity 5 90 RH non condensing Specifications subject to change without notice Appendix B 2 ProtoCarrier Specifications FPC C01 FPC CD2 Available Ports 1x 6 pin DB9 connector RS 232 Interface 1x 3 pin Phoenix RS 485 Connector Power consum...

Page 26: ...or 1991 Tarob Court Milpitas California 95035 USA Web www protocessor com Tel 408 964 4444 Fax 408 262 2269 Toll Free 888 509 1970 x141 email support protocessor com Appendix B 3 Mounting Drawings Appendix B 3 1 FPC FD2 on FPC CD2 Appendix B 3 2 FPC F03 on FPC CD2 ...

Page 27: ... Off Off 0 Off Off Off Off Off Off Off On 1 Off Off Off Off Off Off On Off 2 Off Off Off Off Off Off On On 3 Off Off Off Off Off On Off Off 4 Off Off Off Off Off On Off On 5 Off Off Off Off Off On On Off 6 Off Off Off Off Off On On On 7 Off Off Off Off On Off Off Off 8 Off Off Off Off On Off Off On 9 Off Off Off Off On Off On Off 10 Off Off Off Off On Off On On 11 Off Off Off Off On On Off Off 12 ...

Page 28: ...ff Off On Off Off Off Off On 33 Off Off On Off Off Off On Off 34 Off Off On Off Off Off On On 35 Off Off On Off Off On Off Off 36 Off Off On Off Off On Off On 37 Off Off On Off Off On On Off 38 Off Off On Off Off On On On 39 Off Off On Off On Off Off Off 40 Off Off On Off On Off Off On 41 Off Off On Off On Off On Off 42 Off Off On Off On Off On On 43 Off Off On Off On On Off Off 44 Off Off On Off ...

Page 29: ... Off On Off Off On On On Off 78 Off On Off Off On On On On 79 Off On Off On Off Off Off Off 80 Off On Off On Off Off Off On 81 Off On Off On Off Off On Off 82 Off On Off On Off Off On On 83 Off On Off On Off On Off Off 84 Off On Off On Off On Off On 85 Off On Off On Off On On Off 86 Off On Off On Off On On On 87 Off On Off On On Off Off Off 88 Off On Off On On Off Off On 89 Off On Off On On Off On...

Page 30: ... On On 123 Off On On On On On Off Off 124 Off On On On On On Off On 125 Off On On On On On On Off 126 Off On On On On On On On 127 On Off Off Off Off Off Off Off 128 On Off Off Off Off Off Off On 129 On Off Off Off Off Off On Off 130 On Off Off Off Off Off On On 131 On Off Off Off Off On Off Off 132 On Off Off Off Off On Off On 133 On Off Off Off Off On On Off 134 On Off Off Off Off On On On 135 O...

Page 31: ...n Off On Off On Off Off Off 168 On Off On Off On Off Off On 169 On Off On Off On Off On Off 170 On Off On Off On Off On On 171 On Off On Off On On Off Off 172 On Off On Off On On Off On 173 On Off On Off On On On Off 174 On Off On Off On On On On 175 On Off On On Off Off Off Off 176 On Off On On Off Off Off On 177 On Off On On Off Off On Off 178 On Off On On Off Off On On 179 On Off On On Off On O...

Page 32: ...f 212 On On Off On Off On Off On 213 On On Off On Off On On Off 214 On On Off On Off On On On 215 On On Off On On Off Off Off 216 On On Off On On Off Off On 217 On On Off On On Off On Off 218 On On Off On On Off On On 219 On On Off On On On Off Off 220 On On Off On On On Off On 221 On On Off On On On On Off 222 On On Off On On On On On 223 On On On Off Off Off Off Off 224 On On On Off Off Off Off ...

Page 33: ...or com A7 A6 A5 A4 A3 A2 A1 A0 Address On On On On Off Off On On 243 On On On On Off On Off Off 244 On On On On Off On Off On 245 On On On On Off On On Off 246 On On On On Off On On On 247 On On On On On Off Off Off 248 On On On On On Off Off On 249 On On On On On Off On Off 250 On On On On On Off On On 251 On On On On On On Off Off 252 On On On On On On Off On 253 On On On On On On On Off 254 On ...

Page 34: ...oval or which have been subjected to accident improper maintenance installation or application or on which original identification marks have been removed or altered This Limited Warranty also will not apply to interconnecting cables or wires consumables or to any damage resulting from battery leakage In all cases FieldServer Technology s responsibility and liability under this warranty shall be l...