background image

 

Driver Version: 

1.00 

Document Revision:   6 

 

 

  

 

 

 

 

 

 

 

 

 

 

 

 

A Sierra Monitor Company

APPLICABILITY & EFFECTIVITY 

Effective for all systems manufactured after May 2010 

 

Driver Manual  

(Supplement to the FieldServer Instruction Manual)

 

 

FS-8700-12 AB DH+ 

 

Summary of Contents for FS-8700-12

Page 1: ...ion 1 00 Document Revision 6 A Sierra Monitor Company APPLICABILITY EFFECTIVITY Effective for all systems manufactured after May 2010 Driver Manual Supplement to the FieldServer Instruction Manual FS 8700 12 AB DH ...

Page 2: ...ection Parameters 6 5 3 Client Side Node Parameters 7 5 4 Client Side Map Descriptor Parameters 7 5 4 1 FieldServer Related Map Descriptor Parameters 7 5 4 2 Driver Related Map Descriptor Parameters 8 5 4 3 Map Descriptor Example 9 6 FieldServer as a DH Server 10 6 1 Driver Specific FieldServer Parameters 10 6 2 Server Side Connection Parameters 10 6 3 Server Side Node Parameters 11 6 4 Server Sid...

Page 3: ...Server Technologies for this Driver FieldServer Technologies PART Description FS 8917 19 Connector AB DH Driver Config csv Template loaded if no custom configuration ordered otherwise Custom configuration loaded 2 2 Provided by the supplier of 3rd Party Equipment 2 2 1 Hardware Part Description AB DH compatible PLC e g SLC5 03 PLC 5 40 etc 1 DH Client e g RSView Wonderware Intellution FIX GE Cimpl...

Page 4: ...SH PLC FS 8917 19 Card Slots into FS X40 FieldServer FS X40 Configuration PC DH configuration cable P N 23083 Connector Pinouts DataCard 3 pin A NET connection to PC Datacard Function Datacard Pin DH RIO Network PLC 5 DH Program Port Color Phoenix Connector Phoenix Connector DB 9M Connector Signal A1 1 1 Clear Ground A2 2 7 Shield Signal A3 3 5 Blue Connector Pinouts DataCard 5 Pin B Serial connec...

Page 5: ... facilitate correct storage of the relevant data Section Title Data_Arrays Column Title Function Legal Values Data_Array_Name Provide name for Data Array Up to 15 alphanumeric characters Data_Array_Format Provide data format Each Data Array can only take on one format FLOAT BIT UInt16 SInt16 Byte Data_Array_Length Number of Data Objects Must be larger than the data storage area required by the Map...

Page 6: ...e driver independent FieldServer buffers need to be declared in the Data Arrays section the destination device addresses need to be declared in the Client Side Nodes section and the data required from the servers needs to be mapped in the Client Side Map Descriptors section Details on how to do this can be found below Note that in the tables indicates an optional parameter with the bold legal valu...

Page 7: ... 255 Protocol Specify protocol used AB_DH PLC_Type Specify PLC Type Being Polled PLC3 PLC5 SLC5 Port Port name DH Example Client Side Nodes Nodes Node_Name Node_ID Protocol PLC_Type Port PLC 1 1 AB_DH SLC5 DH 5 4 Client Side Map Descriptor Parameters 5 4 1 FieldServer Related Map Descriptor Parameters Column Title Function Legal Values Map_Descriptor_Name Name of this Map Descriptor Up to 32 alpha...

Page 8: ...ecified in Section 5 3 File_Type File type in PLC N F B I O 4 File_Number File Number in PLC 0 255 Address Starting address of read block 0 255 Length Length of read block 1 255 Scan_Interval Rate at which data is polled 0 32000s 1 0s Data_Array_Low_Scale Scaling zero in Data Array 32767 to 32767 0 Data_Array_High_Scale Scaling max in Data Array 32767 to 32767 100 Node_Low_Scale Scaling zero in Co...

Page 9: ...port fieldserver com 5 4 3 Map Descriptor Example Client Side Map Descriptors Map_Descriptors Map_Descriptor_Name Data_Array_Name Data_Array_Offset Function Node_Name File_Type File_Number Address Length Scan_Interval CMD_AI_01 DA_AI_01 0 Rdbc PLC 1 N 10 0 16 1 0s CMD_AO_01 DA_AO_01 0 Rdbc PLC 1 N 11 0 16 1 0s CMD_DI_01 DA_DI_01 0 Rdbc PLC 1 B 12 0 16 1 0s CMD_DO_01 DA_DO_01 0 Rdbc PLC 1 B 13 0 16...

Page 10: ... Title FieldServer Column Title Function Legal Values Title Provide name for FieldServer Up to 39 alphanumeric characters System_Station_Address FieldServer Panel number on the network 1 254 11 Example Common Information FieldServer Title System_Station_Address AB_DH Server V1 00o 11 6 2 Server Side Connection Parameters Section Title Connections Column Title Function Legal Values Port Port name D...

Page 11: ...B_DH PLC_Type Specify PLC Type Being Polled PLC3 PLC5 SLC5 Example Server Side Nodes Nodes Node_Name Node_ID Protocol PLC_Type DHP_Srv_11 11 AB_DH SLC5 6 4 Server Side Map Descriptor Parameters 6 4 1 FieldServer Specific Map Descriptor Parameters Section Title Map_Descriptors Column Title Function Legal Values Map_Descriptor_Name Name of this Map Descriptor Up to 32 alphanumeric characters Data_Ar...

Page 12: ... to fetch data from One of the node names specified in Section 6 3 File_Type File type in PLC N F B I O 5 File_Number File number in PLC 0 255 Address Starting address of read block 0 255 Length Length of read block 1 255 Data_Array_Low_Scale Scaling zero in Data Array 32767 to 32767 0 Data_Array_High_Scale Scaling max in Data Array 32767 to 32767 100 Node_Low_Scale Scaling zero in Connected Node ...

Page 13: ...ort fieldserver com 6 4 3 Map Descriptor Example Server Side Map Descriptors Map_Descriptors Map_Descriptor_Name Data_Array_Name Data_Array_Offset Function Node_Name File_Type File_Number Address Length SMD_AI_01 DA_AI_01 0 Passive DHP_Srv_11 N 10 0 200 SMD_AO_01 DA_AO_01 0 Passive DHP_Srv_11 N 11 0 200 SMD_DI_01 DA_DI_01 0 Passive DHP_Srv_11 B 12 0 200 SMD_DO_01 DA_DO_01 0 Passive DHP_Srv_11 B 13...

Page 14: ...62 2299 Fax 408 262 2269 Toll Free 888 509 1970 email support fieldserver com Appendix A Useful Features Appendix A 1 DH Card Configuration The DH card is pre configured before shipping If it is necessary to modify the configuration the following is needed DL32 Software DH configuration cable P N 23083 Refer to Section 3 for connection information ...

Page 15: ...Server Map 1 N21 0 100 no problems are experienced Appendix B 2 Reading B File Types It is advisable to read all data from one B type file into the same data array in one contiguous read if possible Doing otherwise may result in problems when reading these points Appendix B 3 Checksum When selecting checksum options for DH devices communicating to the FieldServer take note that BCC Block Check Sum...

Page 16: ...Read 0 Range Write N7 3 L5 F 1 Range Read 0 Range Write F12 3 L5 B 1 Range Read 2 Bit Write B3 4 5 l5 PLC5 N 1 Range Read 0 Range Write N7 3 L5 F 1 Range Read 67 Typed Write F12 3 L5 B 1 Range Read 26 Read Modify Write B3 4 5 L5 SLC5 N A2 Protected Typed Logical Read AA Protected Typed Logical Write N7 3 L5 F A2 Protected Typed Logical Read AA Protected Typed Logical Write B3 4 5 L7 B A2 Protected...