background image

Heated Diode

Refrigerant

Leak Detector

Model: SRL8

OPERATOR’S MANUAL

Description

The SRL8 uses a tin dioxide semiconducting gas

detector (heated diode) and microprocessor to cre-

ate  a  highly  sensitive  portable  refrigerant  leak

detector technology with superior battery life, porta-

bility, and ease of use.  

Gas is pumped through the tip of the wand into

the  sensor  at  the  base  of  the  snoot.  The  sensor

chemically reacts with any refrigerant in the incom-

ing gas, sending a mV signal into a microprocessor

controlled circuit. 

The  SRL8  can  detect  leaks  smaller  than  0.1

oz/year,  which  exceeds  the  toughest  SAE  J1627

standards.  The  SRL8  comes  with  wall  and  car

charger  for  its  ultra-compact  Li-ion  battery  which

powers the SRL8 for 15 hours of continuous opera-

tion  before  a  recharge  is  needed.  That's  long

enough  to  last  your

entire workday.

The  SRL8  has

variable  sensitivity

settings,  to  give  you

the  sensitivity  you

need  while  eliminat-

ing  'nuisance  tripping'. A quick,  automatic  30  sec-

ond self-calibration upon power-up ensures optimal

performance. 

A built  in  replaceable  filter  blocks  moisture  and

harmful  particulates.  The  SRL8  also  has  manual

and automatic "Zeroing" function to ensure the best

sensitivity  possible  by  canceling  out  background

contamination. Use the MUTE button to silence the

detector's audio indicators when needed.

Operation

ON/OFF Protection

To  turn  on/off  the  SRL8  press  and  hold  the

ON/OFF  button  for  one  second.  This  slight  delay

protects  against  inadvertent  powering  on  or  off,

conserving  battery  life.  If  you  forget  to  turn  the

SRL8 off, it will automatically turn off after 10 min-

utes of inactivity.

LED Bar Graph Display

The  eight  segment  LED  display  indicates  the

concentration  of  refrigerant  detected. As  the  con-

centration of refrigerant in the air increases so does

the number of lit bars on the display.

L/M/H Button (Sensitivity)

Set  the  sensitivity  level  by  pressing  the  L/M/H

button. Low (L), medium (M), or high (H) sensitivity

will be indicated by the respective LEDs. 

The higher the concentration of refrigerant in the

ambient air, the lower the sensitivity setting should

be to minimize false trips.

MUTE Button and Battery check

Pressing the MUTE button toggles the sound of

the SRL8 on and off. In addition, holding the MUTE

button down for one second will display the remain-

ing percent of battery charge on the LED bar graph.

ZERO Button and Auto-Zeroing function

The SRL8 has two zeroing modes, manual and

automatic,  which  are  indicated  by  the  "Auto-Zero"

LED  being  off  or  on  respectively.  These  modes

allow the user to achieve the best sensitivity possi-

ble by setting the baseline signal equal to any back-

ground contamination.

The  SRL8  defaults  to  the  automatic  zeroing

mode  when  turned  on.  In  automatic  mode,  the

SRL8  will  zero  itself  to  the  ambient  environment

every two seconds if not triggered. Zeroing is indi-

cated  by  a  quick  double  flash  of  the  "Auto-Zero"

LED.

To switch between the auto and manual zeroing

modes hold the ZERO button down for one second.

The "Auto-Zero" LED will no longer be lit when in

manual  mode.  To  manually  zero  the  SRL8  in  this

mode, simply press the ZERO button in a non-con-

taminated environment. The SRL8 will indicate suc-

cessful zeroing by a quick double flash of the "Auto-

Zero" LED.

Leak Detection Procedure

Keep the SRL8 away from any areas of potential

refrigerant leakage until the warm-up and calibration

period  is  over.  The  warm-up  and  calibration

sequence lasts about 30 seconds after ON/OFF is

pressed.  Allow  the  SRL8  to  fully  warm-up  before

using. On startup, meter defaults to high sensitivity

and auto-zeroing.

The most likely points for refrigerant leaks are at

the soldered joints in refrigerant lines and changes

in cross section or direction of these lines.  

The  SRL8  detects  concentration  of  refrigerant.

The zeroing function lets the user easily detect leaks

in places that may have refrigerant in the air, such

as  a  refrigerator  leaking  into  an  enclosed  space.

When detecting:

1. The tip of the snoot should be fairly close to the

line. You may need to be within 1/4” (0.64cm) of

a small leak to detect it. In this case, using a

second hand to guide the tip along refrigerant

lines may be helpful.

2. Keep the tip moving along refrigerant lines at a

rate of 1-3 inches per second.

3. As the SRL8 detects a leak its alarm will sound

and the LED bar graph will light up. As you move

the snoot closer to the point of the leak, more

LEDs light up as the concentration increases.

(Note: If the SRL8 wand moves through a very

high concentration of refrigerant, you may need

to wait for the SRL8 to re-zero or manually zero

it in order to let the sensor readjust, before mov-

ing to step 4.)

4. Once the maximum refrigerant concentration is

located, allow the meter to zero away from the

leak. Then do a second sweep of the suspected

leak point, to verify its location.

Filter Assessment & Replacement

The filter blocks moisture and other contaminants

from the sensor. When it gets wet, it constricts flow

of air, and the filter should be replaced. Unscrew the

sensor  tip  and  replace  the  white  filter  so  that  the

rounded end is at the tip of the wand. Use only the

Fieldpiece supplied filter. 

Extra filters can be ordered from a distributor.

Model RFL2 contains 10 filters and 5 O-rings. 

Installing and Replacing Sensor

Replacement sensors (model RHD1) can be

ordered for the SRL8. To install or replace the sen-

sor, make sure the unit is turned off. Then,

unscrew the snoot on the SRL8 and if replacing

gently pull the sensor from the base. 

Carefully insert the new sensor and replace

snoot. The sensor can be inserted in two different

configurations, either of which will allow the SRL8

to function correctly. 

If no sensor is installed or the installed sensor is

broken when the unit is turned on an alarm will

sound and the unit will turn off.

Quick Tips

1.

To pinpoint larger leaks, adjust sensitivity.

2.

Make sure the SRL8 is zeroing between detec-

tions. Look for the double flash of the auto-zero

LED.

Comparing Leak Detectors

Fieldpiece has two leak detectors. The SRL8 

uses a heated diode sensor. The heated diode's 

advantage is that it detects absolute concentration 

levels so it can be held on a leak and will continue 

to beep. It is also initially very sensitive. Its major 

disadvantages are that the sensor becomes less 

sensitive over life, eventually needing replacement 

and it is more sensitive to some refrigerants than

others.

The SRL2 uses an infrared (IR) sensor. It 

detects a CHANGE in concentration, so the wand 

must keep moving. The main advantages of the

Fieldpiece IR sensor are that its sensitivity will 

remain the same over the life of the instrument, 

the sensor will last the lifetime of the instru

ment, it will not trigger on humidity or on oil, 

and it has nearly the same sensitivity to most 

refrigerants.The main disadvantage of infrared 

sensors is their sensitivity to mechanical 

disturbances.

SRL8 testing an A-coil, 1/4” (0.64cm) from the line.

1/4”

(0.635cm)

SENSITIVITY

H
M
L

AUTO-ZERO

LOW-BATT

SRL8

ON/OFF

MUTE

ZERO

L/M/H

Heated Diode
Refrigerant
Leak Detector

PRESS FOR

1 SECOND

BATTERY

CHECK

SENSITIVITY

H
M
L

AUTO-ZERO

LOW-BATT

Caution

DO NOT use the SRL8 without the proper fil-

ter  correctly  installed.    Doing  so  may  result  in

damage to the instrument.

!

Warning

The sensor may be hot after use. 

!

!

!

99 Washington Street 
Melrose, MA 02176 

Phone

 781-665-

1400

Toll Free 1-800-517-8431

Visit us at www.T

estEquipmentDepot.com

Reviews: