31
confIguratIon
156.
First button – Switch ON value sent to 2nd and 3rd
association groups
Description
This parameter defines value sent with Switch
ON command to devices associated in 2nd and
3rd association group.
Parameter size
2B
Default value
255
Available
values
0 – turn off
1-99 – set level
255 – turn on with previous level
157.
First button – Switch OFF value sent to 2nd and 3rd
association groups
Description
This parameter defines value sent with Switch
OFF command to devices associated in 2nd and
3rd association group.
Parameter size
2B
Default value
0
Available
values
0 – turn off
1-99 – set level
255 – turn on with previous level
158.
First button – Double Click value sent to 2nd and 3rd
association groups
Description
This parameter defines value sent with Double
Click command to devices associated in 2nd and
3rd association group.
Parameter size
2B
Default value
99
Available
values
0 – turn off
1-99 – set level
255 – turn on with previous level
159.
Second button – Switch ON value sent to 4th and 5th
association groups
Only in Double Switch Mode
Description
This parameter defines value sent with Switch
ON command to devices associated in 4th and
5th association group.
Parameter size
2B
Default value
255
Available
values
0 – turn off
1-99 – set level
255 – turn on with previous level