![FGD FlameSpec UV-IR User Manual Download Page 33](http://html1.mh-extra.com/html/fgd/flamespec-uv-ir/flamespec-uv-ir_user-manual_2285568033.webp)
FlameSpec
UV-IR
User Manual
F110V0020.05
JP5
1 x 1 ft
36 (11)
1.5
Kerosene
1 x 1 ft
36 (11)
1.4
Methanol
1 x 1 ft
30 (9)
1.3
Ethanol
1 x 1 ft
31 (9.5)
1.2
Isopropanol
1 x 1 ft
36 (11)
1.4
Polypropylene
1 x 1 ft
23 (7)
1.7
Paper
1 x 1 ft
23 (7)
2.0
Low Sensitivity
Fuel
Size
Distance Feet
(m)
Average Response
Time (Seconds)
N-Heptane
1 x 1 ft
16 (5)
0.9
LPG
32-in Plume
13 (4)
1.0
JP5
1 x 1 ft
16 (5)
2.6
Methanol
1 x 1 ft
10 (3)
1.1
B.2
False Alarm Immunity
The
following table shows test results of false alarm immunity for detectors configured to “Extreme”
sensitivity. For each radiation source a distance is listed. This is the minimum tested distance, from which the
detectors did not alarm when exposed to the radiation source (either modulated or non-modulated).
False Stimuli only at Extreme Sensitivity
False Alarm Source
Maximum Distance in ft (m)
Sunlight, Direct, Reflected
Incandescent frosted glass light, 300W
2 (0.5)
Fluorescent, 70W (3x23.3W)
2 (0.5)
Electric arc
2 (0.5)
Arc welding
10 (3)
Radiation heater, 1850W
2 (0.5)
Quartz lamp (1000W) shielded
2 (0.5)
Quartz lamp (500W) non-shielded
7 (2)
Mercury vapor lamp 160Wx3
2 (0.5)
Car Exhausts
2 (0.5)
Projector led
2 (0.5)
Solenoid bell
2 (0.5)
Soldering iron
2 (0.5)
Electric Drill
2 (0.5)