11

 

Further details about the response characteristics of the detector at the different sensitivity settings 
can be found in Appendix A. 

3.2

 

Ultra-Fast Detection 

The ultra-fast detection feature allows detection of fireballs and explosions at 40 milliseconds. This 
feature can be disabled or enabled regardless of the alarm delay configuration.

 

3.3

 

Alarm Delay 

When a flame is detected, the flame detector delays the execution of the alarm outputs by the 
configured time period. After this time delay, the detector re-evaluates the situation. If a flame is still 
detected the alarm outputs are activated.

 

 

3.4

 

Alarm Latch 

If alarm latch is enabled, the detector outputs will remain in alarm mode even after a flame is no 
longer detected. To return the detector outputs to normal mode the detector must be powered 
down and restarted.  

3.5

 

Window Heater 

The detector is equipped with a heater to prevent condensation and icing on the window. If enabled, 
the heater is operated automatically depending on temperature.  

3.6

 

Modbus Address 

The detector can communicate with the “FGD communicator” software using a Mod

bus RTU 

compatible protocol on RS-485. This protocol allows for a network of detectors to be connected, 
each with a unique Modbus address. The address of the detector can be set to any value in the range 
1

247. 

3.7

 

Manual BIT 

 Alarm Output Test 

When enabled, the alarm outputs are activated when a 

Manual

 BIT is initiated. See section 5.2 

 

Testing

” for details.

 

 

WARNING

  

Make sure to disable all fire extinguishing actions or alarms connected to the detector when the 

manual BIT is initiated and the “Manual BIT –

 

Alarm Output Test” is enabled as the 

Manual BIT will 

set the 0-20mA terminal to 20mA and close the alarm relay.

 

 

 

Summary of Contents for FlameSpec IR3-H2

Page 1: ...FlameSpec IR3 H2 User Manual Doc No F150V0020 04 590 W Central Ave Suite K Brea CA 92821 USA T 1 714 671 8500 www fg detection com support fg detection com FlameSpec IR3 H2...

Page 2: ...or transmitted for commercial purposes such as selling copies of this publication or for providing paid for support services The Fire Gas Detection Technologies logo is a trademark of Fire Gas Detect...

Page 3: ...stallation 5 2 3 Required Tools 5 2 4 Certification Instructions 5 2 5 Installing the Tilt Mount 7 2 6 Installing the detector 8 3 Configuration options 10 3 1 Sensitivity 10 3 2 Ultra Fast Detection...

Page 4: ...Specifications 19 6 1 Fire Detection 19 6 2 Electrical Specifications 19 6 3 Outputs 19 6 4 Mechanical Specifications 20 6 5 Environmental Specifications 20 6 6 Label Figures 21 6 7 Approvals 22 6 8 E...

Page 5: ...Figure 2 Tilt mount base Side View 8 Figure 3 Detector on Tilt Mount Side View 9 Figure 4 Source 4 Wire Scheme 13 Figure 5 Sink 4 Wire Scheme 13 Figure 6 Source 3 Wire Scheme 14 Figure 7 Sink 3 Wire S...

Page 6: ...l means to study the cause and development of fire events 1 1 Key Features High immunity to false alarm Ultra fast detection mode detection within 40 milliseconds for Hydrogen fireballs or explosions...

Page 7: ...tor performs self tests of its optics electronics and software These include a periodic BIT Built In Test in which the sensors and window cleanliness are tested Any detected fault is indicated as show...

Page 8: ...have to the extent that is required an unobstructed view of the protected area Whenever possible the detector face should be tilted aimed down at an angle to prevent the accumulation of dust and dirt...

Page 9: ...inhibited during welding operations in situations where the possibility of a false alarm cannot be tolerated Gas welding requires a system inhibit since the gas torch is an actual fire Arc welding rod...

Page 10: ...ngs or labels for the wiring You may use 12 to 22 AWG 2 5 2 to 0 3 2 wires for the site wiring The selection of wire gauge should be based on the number of detectors used on the same line and the dist...

Page 11: ...checks as part of routine inspections or establishing from the material s data sheet that it is resistant to specific chemicals 2 4 1 Specific conditions for use The equipment is not intended to be re...

Page 12: ...method However with a designated adapter the tilt mount can hold the detector from above Other designated adapters may be used to connect the detector to some other vendors tilt mounts useful when rep...

Page 13: ...c Secure the detector by using the two provided screws and spring lock washers Items 3 and 4 d Release the locking screws Items 5 and 6 in such a way that enables you to rotate the detector e Point th...

Page 14: ...cal support 1 714 671 8500 support fg detection com 9 Figure 3 Detector on Tilt Mount Side View ITEM NO ITEM NAME 1 TILT MOUNT ASSEMBLY 2 HOLDING PLATE 3 4 MOUNTING HEX SCREWS M8 AND LOCK WASHERS 5 HE...

Page 15: ...30 seconds 0 seconds no delay Alarm Latch Disabled Enabled Disabled Window Heater Disabled Enabled Enabled Modbus address 1 247 1 Manual BIT Alarm Output Test Disabled Enabled Disabled Note Medium se...

Page 16: ...after a flame is no longer detected To return the detector outputs to normal mode the detector must be powered down and restarted 3 5 Window Heater The detector is equipped with a heater to prevent co...

Page 17: ...20 mA current output 4 0 20mA out 5 Fault Relay A normally open SPST contact relay that is energized closed when the detector is in normal operation and opens in case of fault 6 Fault Relay COM 7 Alar...

Page 18: ...an be 3 wire or 4 wire connected The following drawing shows how to wire the detector to act as a current source isolated transmitter 4 wire connection FIGURE 4 SOURCE 4 WIRE SCHEME The following draw...

Page 19: ...wire the detector to act as a current sink non isolated transmitter 3 wire connection FIGURE 7 SINK 3 WIRE SCHEME 4 3 RS 485 Communication Network Using the RS 485 network capability of the detector a...

Page 20: ...up to 247 on the same 4 wires Using the RS 485 network it is possible to read each detector s status fault alarm and to initiate a BIT to each detector individually The detector communicates via RS 48...

Page 21: ...reen the 0 20mA indicates 4mA and the fault relay is closed Detector configuration settings can be changed as described in section 3 To restart the detector turn off and then turn on the power 5 1 Out...

Page 22: ...0mA current output will be set to 20mA 3 The alarm relay will close WARNING Make sure to disable all fire extinguishing actions or alarms connected to the detector when the manual BIT is initiated and...

Page 23: ...Check that the power is connected to the detector Check power polarity Check wiring in the detector Yellow LED constantly on Fault Relay is open Current output at 0mA Power problems Check the voltage...

Page 24: ...ion including window heater Cable Entries 2x conduit entries 3 4 14NPT or M25x1 5 Wiring 12 20AWG 2 5 0 35mm2 6 3 Outputs Relays Volt free contacts rated 2A at 30 VDC o Alarm Normally open o Fault2 No...

Page 25: ...fications Size 5 51 x 3 54 3 54 140 90 90mm Weight o Detector Stainless Steel 316 6 6 lbs 3 kg o Tilt mount Stainless steel 316 3 3 lbs 1 5 kg 6 5 Environmental Specifications Temperature Range o Oper...

Page 26: ...FlameSpec IR3 H2 User Manual F150V0020 04 For more information Technical support 1 714 671 8500 support fg detection com 21 6 6 Label Figures 6 6 1 Ex db 6 6 2 Ex db eb...

Page 27: ...a 75 C Ex db IIC T4 Gb 50 C Ta 85 C FM FMC Class I Div 1 Groups B C D T4 Class I Zone 1 AEx Ex db IIC T4 Gb T4 50 C Ta 85 C T5 50 C Ta 5 C Performance o ANSI FM 3260 o EN 54 10 pending Functional safe...

Page 28: ...red in transit from the factory or other damage due to abuse misuse improper installation lack of maintenance or Act of God which are above and beyond its control FIRE GAS DETECTION TECHNOLOGIES INC w...

Page 29: ...s for different fire scenarios Each table lists results for a different sensitivity setting For liquid fires the size of fire refers to the size of the pan filled with the fuel For gas fires the lengt...

Page 30: ...eflected No Alarm No Alarm Incandescent frosted glass light 300W 2 0 5 No Alarm 2 0 5 No Alarm Fluorescent 70W 3x23 3W 2 0 5 No Alarm 2 0 5 No Alarm Electric arc 3 1 No Alarm 3 1 No Alarm Arc welding...

Reviews: