FlameSpec
IR3-H2-HD
User Manual
F140V0020.03
For more information & Technical support: (+1) 714-671-8500 · [email protected]
25
6.8
Approvals
Note: All items are designed and tested to meet the relevant requirements.
•
Explosion proof:
o
ATEX: II 2 G D
Ex db IIC T5 Gb or Ex db eb IIC T5 Gb and Ex tb IIIC T95°C Db -55°C<Ta<75°C
Ex db IIC T4 Gb or Ex db eb IIC T4 Gb and Ex tb IIIC T105°C Db -55°C<Ta<85°C
o
FM & FMC:
Class I, Div. 1, Groups B, C & D; T4
T4 -50°C
≤
Ta
≤
85°C
T5 -50°C
≤
Ta
≤
75°C
•
Performance:
o
ANSI FM 3260
o
EN 54-10 (pending)
•
Functional safety (pending): SIL 2 per IEC 61508
•
DNV GL (pending):
Standard DNVGL-CG-0339 for open deck locations
Temperature class D; Vibration Class A, B and C
•
EAC CU TR (pending)
6.9
Electromagnetic Compatibility
The detector fully complies with EMC directive 2014/30/EU and protected against interference caused by RFI
and EMI. The cables to the detector must be shielded and the detector must be grounded in order to comply
to the EMC directive.