Fireray 5000 Technical notes
Page 1: ...Fireray 5000 Technical notes...
Page 2: ...function when in the Engineering menus as this will un align all the Detectors connected to the Controller Mark 3 this has 3 LEDs above the LCD window It can support 2 Detectors and has a Fire and a F...
Page 3: ...e goes up to between 11V and 13 5V If it goes up then the fault could be on either the Detector or Controller you can work out whether it s the Detector or Controller which is faulty but I don t think...
Page 4: ...This may be a Software bug 7 E 06 Code Amber Something has blocked the Beam and caused the IR Signal to drop to 0 Note This is a common fault in warehouses or buildings where the Beams have a process...
Page 5: ...the whole of the Beams path to align through and without shiny surfaces near the reflector s or that the Beam passes through 2 Windows or surfaces which are reflective near the Reflector s can cause a...
Page 6: ...re is an internal power fault on the Controller and there is nothing that can be done other than replace it this might also cause E 01 errors to occur to 15 E24 and E26 Code Green I ve not come across...