2. MPA pressure sensor
2−12
Festo P.BE−MPA−ELECTRONIC−EN en 0804NH
Data format for pressure specifications
The data format for setting and specifying pressure values via
parameterisation is VZ+15Bit". Negative values are repre
sented in twos−complement format.
Data format
VZ + 15 Bit, negative values represented as twos−complement
D15
D14
D13
D12
D11
D10
D9
D8
D7
D6
D5
D4
D3
D2
D1
D0
VZ
B14
MSB
B13
B12
B11
B10
B9
B8
B7
B6
B5
B4
B3
B2
B1
B0
LSB
Abbreviations used:
VZ:
mathematical sign (0 = positive value, 1 = negative value)
B0...B14: input value
D0...D15: 16 bit input data field
MSB/LSB: most significant bit / least significant bit
Tab.2/10: Data format for pressure specifications (limit values, hysteresis and current
pressure value)
When making settings using the Handheld, you can directly
enter data as numerical values.
The unit for pressure specifications, defined via the para
meter in Tab.2/4, applies to all pressure v alues (upper/lower
limit values, hysteresis and current pressure value).
Note
When changing the unit for pressure specifications, the
parameters for the limit values and hysteresis are
not
automatically converted.
When changing the unit, you must therefore be sure to
also change the parameters for the upper/lower limit
values and the hysteresis.
Summary of Contents for VMPA-FB-PS Series
Page 2: ......
Page 49: ...MPA pressure sensor 2 1 Festo P BE MPA ELECTRONIC EN en 0804NH Chapter 2 Type VMPA FB PS ...
Page 83: ...Technical appendix A 1 Festo P BE MPA ELECTRONIC EN en 0804NH Appendix A ...
Page 90: ...A Technical appendix A 8 Festo P BE MPA ELECTRONIC EN en 0804NH ...
Page 91: ...Index B 1 Festo P BE MPA ELECTRONIC EN en 0804NH Appendix B ...
Page 92: ...B Index B 2 Festo P BE MPA ELECTRONIC EN en 0804NH ...
Page 96: ...B Index B 6 Festo P BE MPA ELECTRONIC EN en 0804NH ...