6. Multi I/O modules
6−16
Festo P.BE−CPX−EA−EN en 0705f
6.5
Diagnosis
Specific faults of the multi I/O modules are registered or
suppressed depending on the module parametrizing.
The faults are shown on−the−spot by means of the Error LED
and, if necessary, can be evaluated with the handheld (MMI).
Depending on the module parametrizing, the faults are sent
to the field bus node, where they can be evaluated according
to the field bus protocol used.
6.5.1
Error messages of the multi I/O modules
A multi I/O module can register the following standard faults:
Fault
number
Description
Fault treatment
2
Fault short circuit/overload
Short circuit/overload in
sensor supply (V
EL/SEN
).
or (see continuation)
1. Eliminate short circuit/overload or check connected
sensors.
2. Depending on the parametrizing Reaction after
short circuit/overload in sensor supply (SCS)":
·
Setting V
SEN
switch on again":
Power supply for sensors will be switched on
again
automatically
when short circuit is
eliminated.
·
Setting V
SEN
remains switched off":
Power off/on necessary
or
Modify parameter Reaction to short
circuit/overload at sensor supply (SCS)" to
V
SEN
switch on again".
Tab.6/13:
Error messages of the multi I/O modules part 1
Summary of Contents for VMPA...-FB-EPL Series
Page 2: ......
Page 22: ...Contents and general instructions XX Festo P BE CPX EA EN en 0705f ...
Page 46: ...1 Pneumatic interfaces 1 24 Festo P BE CPX EA EN en 0705f ...
Page 100: ...3 Overview and connecting technology I O modules 3 30 Festo P BE CPX EA EN en 0705f ...
Page 141: ...Output modules 5 1 Festo P BE CPX EA EN en 0705f Chapter 5 Type CPX 4DA CPX 8DA CPX 8DA H ...
Page 171: ...Multi I O modules 6 1 Festo P BE CPX EA EN en 0705f Chapter 6 Type CPX 8DE 8DA ...
Page 191: ...Technical appendix A 1 Festo P BE CPX EA EN en 0705f Appendix A ...
Page 223: ...Index B 1 Festo P BE CPX EA EN en 0705f Appendix B ...
Page 224: ...B Index B 2 Festo P BE CPX EA EN en 0705f Contents B Index B 1 ...