5. Diagnostics and error handling
5-8
Festo P.BE-SBO-Q-EN en 1602e
Problem
Remedy
Cause
The programming environment
CoDeSys provided by Festo
cannot connect to the Compact
Vision System
– Incorrect cable
For a direct connection to the
PC, you will probably require
a connecting piece and a
so-called crossover cable in
addition to the original cable.
This is not necessary for a
connection via a hub or a
switch (
è
– Firewall of the PC or network
does not permit a
connection.
Enable program or ports in
firewall.
– CoDeSys run-time system is
not activated
Activate the run-time system
(
è
– Incorrect communication
parameters in the CoDeSys
project
Change the communication
parameters in the CoDeSys
project to reflect the current
Compact Vision System
settings (
è
Programming
environment online Help)
Tab. 5/5:
Error elimination
Summary of Contents for SBO***-Q Series
Page 2: ......
Page 19: ...System overview 1 1 Festo P BE SBO Q EN en 1602e Chapter 1 System overview...
Page 39: ...Mounting 2 1 Festo P BE SBO Q EN en 1602e Chapter 2 Mounting...
Page 47: ...Installation 3 1 Festo P BE SBO Q EN en 1602e Chapter 3 Installation...
Page 62: ...3 Installation 3 16 Festo P BE SBO Q EN en 1602e...
Page 63: ...Commissioning 4 1 Festo P BE SBO Q EN en 1602e Chapter 4 Commissioning...
Page 162: ...4 Commissioning 4 100 Festo P BE SBO Q EN en 1602e Fig 4 34 Structure of an imported data type...
Page 183: ...Technical appendix A 1 Festo P BE SBO Q EN en 1602e Appendix A Technical appendix...
Page 247: ...Index B 1 Festo P BE SBO Q EN en 1602e Appendix B Index...
Page 248: ...B Index B 2 Festo P BE SBO Q EN en 1602e Table of contents B Index B 1...