Festo — CPX-AP-A-PN-M12 — 2022-07
Diagnostics and fault clearance
11
ID
Parameter
Instances Data type
Access
1
)
Array
size
20093
Hardware version
1
UINT8
ro
–
20196
Diagnostics status
–
Index 0: diagnostics status of the entire
automation system CPX-AP
–
Index 1: diagnostics status of module 1
(address 1)
–
Index 2: diagnostics status of module 2
(address 2)
–
...
Every entry is of the data type UINT8 with
the following meaning:
–
Bit 0: degree of severity information (1)
–
Bit 1: degree of severity maintenance (1)
–
Bit 2: degree of severity warning (1)
–
Bit 3: degree of severity error (1)
–
Bit 4: reserved
–
Bit 5: reserved
–
Bit 6: module present (1), module lost (0)
–
Bit 7: reserved
Bit 6 is not valid for index 0
1
UINT8
ro
Number
of mod-
ules + 1
1) ro = read only; rw = read write
Tab. 7: AP parameter
9
Diagnostics and fault clearance
9.1
Diagnostics options
Diagnostics via LED displays
System status and network status and errors are displayed directly on the module by LED indicators
Diagnostics via Web Server
Read access to diagnostics messages via the integrated webserver
9.4 Diagnostics via Web Server.
Diagnostics via PROFINET IO
Diagnostics as part of PROFINET IO functions
9.5 Diagnostics via PROFINET IO via control software
through the network.
9.2
Diagnostics messages
The following table contains the diagnostic messages of the interface.
ID hex (dec)
Message
Description
02 | 01 | 0016
(33619990)
Undervoltage in logic
supply (PS) 24 V DC
Undervoltage in logic supply (PS) 24 V DC
Remedy
–
Check power supply.