Festo — MSE6-C2M — 2022-08b
Technical data
97
Error
channel
Meaning
Remedy
Activation
parameter
m = module
number 0
Am.0
–
Check the parameterisation and carry out the
parameterisation again with correct parame-
ters.
Pm.0.7:
Monitoring of
parameters
Error in setting
the auto-control
flow rate limit
value parameter
Am.2
Error when cre-
ating the param-
eters:
–
Auto
setpoint pres-
sure
normal
and/or
–
Auto
setpoint pres-
sure
Standby
Tab. 81: Module-specific error numbers
11
Removal
The settings are not saved in the product. Save the settings if necessary, e.g. on the higher-level
controller.
Disassemble the product in the following sequence:
1. De-energise the compressed air supply and power supply.
2. Exhaust the energy efficiency module.
3. Disconnect the pneumatic ports.
4. Disconnect all electrical cables.
5. Loosen the screws from all mounting brackets, one after the other. Start with the screws beneath
the product.
6. Remove the entire product.
12
Technical data
12.1
Technical data, general
MSE6-C2M
Certificates, declaration of conformity
Mounting position
Horizontal ± 5°