Commissioning
8.3.3
Setting DIL switches
NOTICE
Damage to internal electronics.
Damage to components and malfunctions due to incorrect handling.
• Observe the handling specifications for electrostatically sensitive devices.
You can set the following parameters with the DIL switches:
–
The mode of operation and the protocol; the energy efficiency module only supports the ‘Remote
I/O’ operating mode.
–
The diagnostics mode.
–
The IP addressing.
1
2
3
Fig. 23: DIL switches on bus node CPX-M-FB36
1
DIL switch 1: setting operating mode and
protocol
2
DIL switch 2: diagnostic mode
3
DIL switch 3: IP addressing
1. Switch off the power supply.
2. Unscrew the retaining screws of the cover.
3. Remove the cover
è
3 DIL switches are visible.
4. Use DIL switch 1 to set the operating mode and protocol.
5. Set the diagnostic mode with DIL switch 2.
6. Set the IP addressing with DIL switch 3.
7. Fit the cover.
8. Screw on the retaining screws hand-tight and then tighten to 0.4 Nm ± 10%.
Setting operating mode and protocol, DIL switch 1
The energy efficiency module only supports the Remote I/O operating mode with the bus node
CPX-FB36, factory setting.
All 1.1 and 1.2 switch elements of DIL switch 1 must be in the OFF position.
DIL switch 1.1
Setting operating mode
DIL 1.1: OFF
Factory setting
‘Remote I/O’ operating mode.
All functions of the energy efficiency module are controlled directly
by the controller or by a higher-level PLC.