Festo — CPX-AP-A-EC-M12 — 2022-07
Diagnostics and fault clearance
27
ID hex (dec)
Message
Description
08 | 01 | 0215
(134283797)
Device forced to com-
munication loopback
Diag-
nostic
status
Maintenance Required
08 | 01 | 0225
(134283813)
Invalid Topology
The current topology contains invalid connections.
Remedy
–
Check wiring
Diag-
nostic
status
Maintenance Required
08 | 01 | 880F
(134318095)
AP process data
internal error
The AP process data controller returns an error.
Remedy
–
Restart device
Diag-
nostic
status
Error
08 | 04 | 0191
(134480273)
State change request
State change request from: %d to: %d
Remedy
–
None
Diag-
nostic
status
Error
08 | 04 | 0193
(134480275)
Sync Manager invalid
address
Sync Manager %d invalid address (%d)
Remedy
–
Setup correct sync manager address
Diag-
nostic
status
Error
08 | 04 | 0194
(134480276)
Sync Manager invalid
size
Sync Manager %d invalid size (%d)
Remedy
–
Correct I/O size
Diag-
nostic
status
Error
08 | 04 | 0195
(134480277)
Sync Manager invalid
settings
Sync Manager %d invalid settings (%d)
Remedy
–
Correct I/O settings
Diag-
nostic
status
Error
08 | 04 | 0196
(134480278)
DC activation register
invalid
DC activation register is invalid
Remedy
–
Correct DC activation register