background image

LED status

Meaning

Error handling

1)

flashing
green

Undervoltage:
Operating voltage outside the tol-
erance range.

Rectify undervoltage.

off

Operating voltage is not present.

Check operating voltage

supply.

1) General information on the  PS LED 

è

 System description of CPX terminal (CPX-SYS)

Tab. 14: ‘Operating power supply’ ([PS] LED)

8.1.7

System errors

LED
(red)

Sequen
ce

Meaning

Error handling

off

Normal operating status:
No error

flashes
red 1x

Minor error/information
(error class 1)

è

 System description of the

CPX terminal (CPX-SYS)

flashes
red 2x

Error
(error class 2)

flashes
red 3x

Serious error, internal error,
e.g. hardware error
(error class 3)

Tab. 15: System errors ([SF] LED)

8.2

Malfunction messages

8.2.1

Reset gateway to factory setting

1. Switch off the power supply.
2. Set DIL switch 2 to [ON].
3. Switch on the power supply.

Ä

The [M] LED flashes quickly for a few seconds.

• Do not switch off the power supply.
• Do not actuate the DIL switch.

4. If the LED  [M] stops flashing, set the DIL switch  2 to [OFF].

Ä

The gateway has returned to the factory setting.

8.2.2

Resetting web server SSL certificates to factory setting

1. Switch off the power supply.
2. Set DIL switch 2.1 to [ON].
3. Set DIL switch 2.2 to [OFF].
4. Switch on the power supply.

Ä

The [M] LED flashes quickly for a few seconds.

• Do not switch off the power supply.
• Do not actuate the DIL switch.

5. When the [M] LED stops flashing, set DIL switch 2 to [OFF].

Ä

The web server SSL certificates are reset to factory settings.

9

Disassembly

1. Switch off the power supply and secure it against being switched on again.
2. Unscrew the screws.
3. Pull the gateway out of the interlinking block without tilting it.

10

Technical data

Property

Specification/value

General technical data

è

 System description of the CPX terminal

(CPX-SYS)

Power supply
Operating power supply U

EL/SEN

[V DC]

24 ± 25 %

Intrinsic current consumption at nominal
operating voltage 24 V from operating
voltage supply U

EL/SEN

[mA]

Typically 80
(internal electronics)

Mains buffering time

[ms]

10

Separation of network interface from oper-
ating voltage supply U

EL/SEN

Galvanic

Property

Specification/value

Degree of protection by housing in accord-
ance with IEC 60529, completely mounted,
plug connector inserted or cover cap
installed.
With power supply connection:

via interlinking block

IP65/IP67

via end plate

IP20

Connection technology
Network connections

2 × sockets, M12, D-coded, 4-pin,
SPEEDCON-compatible

Interface to terminal CPX
without a network connection

1 × socket, M12, A-coded, 5-pin

Network-specific characteristics
IP configuration (factory settings)

Cloud

DHCP

Device

IP address: 192.168.0.1
Subnet mask: 255.255.255.0

Data transfer to the MQTT broker

MQTT version 3.1.1

Transmission technology

Industrial Ethernet, Switched Fast Ethernet

Specification

IEEE 802.3u (100Base-TX)

Transmission rate

[Mbit/s]

10/100 (full duplex/half duplex)

Crossover detection

Auto-MDI/MDI-X

Number of devices (‘Device’ network con-
nection)

maximum 10
More devices can be operated depending
on the application.

Cable specification
Cable type

Ethernet twisted pair cable, shielded
(Shielded Twisted Pair, STP)

Transmission class (Link Class)

Cat 5 category

Cable diameter

1)

[mm]

6 … 8

Wire cross section

)2)

[mm

2

]

0.14 … 0.75

Cable length

[m]

maximum 100

1) When using the plug NECU-MS-D12G4-C2-ET
2) 22 AWG required for max. connection length between network participants (end-to-end link)

Tab. 16: Technical data

Summary of Contents for CPX-IOT

Page 1: ...liar with installation of electrical control systems 3 Additional information Contact the regional Festo contact if you have technical problems è www festo com Accessories and spare parts è www festo com catalogue 4 Product overview 4 1 Licence information This product uses open source software Licence Version GNU General Public License Version 2 GNU Lesser General Public License Version 2 1 Tab 2...

Page 2: ...f injury due to electric shock For the electric power supply use PELV circuits that guarantee a reliable electric disconnection from the mains network Observe IEC 60204 1 EN 60204 1 Connect all circuits for the operating and load voltage supply NOTICE Material damage due to incorrect mounting Select screws that are suitable for the material of the interlinking block Polymer thread grooving screws ...

Page 3: ...work status LED status Meaning Error handling green light Normal operating status The gateway is connected with field devices flashing green No connection to field devices The gateway has received an IP address but is not yet connected with field devices Check configuration Check module status Restart module Repeat Onboarding red light Communication with the field devices has failed non permitted ...

Page 4: ...ateway out of the interlinking block without tilting it 10 Technical data Property Specification value General technical data è System description of the CPX terminal CPX SYS Power supply Operating power supply UEL SEN V DC 24 25 Intrinsic current consumption at nominal operating voltage 24 V from operating voltage supply UEL SEN mA Typically 80 internal electronics Mains buffering time ms 10 Sepa...

Reviews: