2. Commissioning
2−13
Festo P.BE−CPX−FB38−EN en 0804NH
2.3
Addressing
2.3.1
Basic rules for addressing
The field bus node counts as a module with 0inputs and
0outputs when the status bits and the I/O diagnostic
interface are deactivated.
Note the remarks regarding address assignment in
section 2.2.
The address assignment of the inputs does
not depend
on the address assignment of the outputs.
Counting is from left to right, addressing
in bytes
:
Modules with less than 8 bits occupy 8 bits of address
space, but do not use all this space.
The I/Os of different module types are assigned
separately from each other. Observe the sequence of
addressing: see Tab.2/8.
Please note
If necessary, status bits or an I/O diagnostic interface can
be activated by DIL switch (see Tab.1/2):
If the 8 status bits are activated, they will occupy the
first 16 inputs in the address range (8 used).
If the I/O diagnostic interface is activated, it will occupy
the first 16 inputs and outputs in the address range.
Summary of Contents for CPX-FB38
Page 2: ......
Page 8: ...Contents and general instructions VI Festo P BE CPX FB38 EN en 0804NH...
Page 17: ...Installation 1 1 Festo P BE CPX FB38 EN en 0804NH Chapter 1...
Page 37: ...Commissioning 2 1 Festo P BE CPX FB38 EN en 0804NH Chapter 2...
Page 91: ...Diagnosis 3 1 Festo P BE CPX FB38 EN en 0804NH Chapter 3...
Page 111: ...Technical appendix A 1 Festo P BE CPX FB38 EN en 0804NH Appendix A...
Page 115: ...Index B 1 Festo P BE CPX FB38 EN en 0804NH Appendix B...
Page 116: ...B Index B 2 Festo P BE CPX FB38 EN en 0804NH Contents B Index B 1...