Note on module replacement

Caution

For CPX terminals with a continuously illuminated or flashing “Modify” LED (M),
parameterisation is not automatically created by the higher-level system when
the CPX terminal is replaced during servicing.
 Before replacement, note required settings and make them again after re­

placement.

When replacing a bus node with the setting [System start with saved para­
meters], the CPX terminal is not parameterised automatically by the high­
er-order controller.

The bus node CPX-FB36 is compatible with the bus node CPX-FB32:
A bus node CPX-FB32 can be replaced in existing applications by a bus
node CPX-FB36 (Revision 13 or higher) without changing the configuration
of the host system.

10

Start-up behaviour of the CPX terminal

If the “Modify” LED (M) lights up or flashes permanently after the system start,
“System start with saved parameterisation and saved CPX expansion” is set or
“Force” is active.

Additional information on parameterisation, module replacement and
start behaviour of the CPX terminal can be found in the module descrip­
tion (

è

 

CPX-FB36-…).

11

Technical data

Characteristic

Specification/value

General technical data

è

 

CPX system description

P.BE-CPX-SYS-…

Degree of protection through housing 
in accordance with IEC 60529, completely
mounted, plug connector in plugged-in status or
equipped with cover caps.

IP65/IP67

1)

Protection against electric shock
Protection against direct and indirect contact in
accordance with IEC 60204-1/EN 60204-1

Through the use of PELV circuits
(Protected Extra-Low Voltage)

Operating voltage supply U

EL/SEN

[V DC]

24 ± 25 %

Intrinsic current consumption at nominal
operating voltage 24 V from operating voltage
supply U

EL/SEN

[mA]

Typ. 100 (internal electronics)

Separation of network interface from operating
voltage supply U

EL/SEN

Galvanic

Load voltage supply U

VAL/OUT

[V DC]

24 ± 10 %

Mains buffering time

[ms]

10

Module code (CPX-specific)

Remote I/O

224

Remote controller

171

Module identifiers (CPX-MMI)

EtherNet/I P

Remote I/O

FB36 EtherNet/IP remote IO V2

Remote controller

FB36-RC EtherNet/IP Node

Modbus TCP

Remote I/O

FB36-MB Modbus TCP remote IO

Remote controller

FB36-MB-RC Modbus TCP node

Network-specific characteristics

Connection technology

2× socket, M12, D-coded, 4-pin

Protocol

EtherNet/I P or Modbus TCP

2)

Transmission technology

Switched fast Ethernet

Specification

IEEE 802.3u (100Base-TX)

Transmission rate

[Mbit/s]

10/100 (full duplex/half duplex)

Minimum cycle time (RPI)

[ms]

1

Maximum data field size (input/output size)

Remote I/O

[byte]

64 I/64 O

Remote controller

[byte]

8 I/8 O, 16 I/16 O, 32 I/32 O or
64 I/64 O

3)

Crossover detection

Auto-M DI/MDI-X

Cable specification

Cable type

Ethernet twisted pair cable,
screened

Transmission class

Category Cat 5/Cat 5e

Cable diameter

[mm]

6 … 8

4)

Wire cross section

[mm

2

]

0.14 … 0.75; 22 AWG

4)5)

Maximum cable length

[m]

100

1)

Connected products may only satisfy a lower degree of protection.

2)

Based on the Ethernet protocol IEEE 802.3

3)

Dependent on the setting of the DIL switch 2 and the revision of the bus node

4)

When using the plug NECU-M-S-D12G4-C2-ET from Festo

5)

Required for maximum connection length between network participants

Fig. 11

12

Specified standards

Version status

IEC 60204-1:2009-02

IEEE 802.3:2014-00

IEC 60529:2001-02