background image

Bus node
CPX-FB36

Festo SE

 & Co.

 KG

 

Postfach
73726 Esslingen

 

Germany
+49 711 347-0
www.festo.com

Brief description

8067482
1611a
[8067484]

Original: de

Bus node CPX-FB36

English

. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

1

Use for intended purpose

The module described in this document is intended for use as a participant in net­
works with the protocols EtherNet/IP or Modbus TCP in an industrial environment.
The module is intended exclusively for use in CPX terminals from Festo for installa­
tion in machines or automated systems and may be used only in the following
ways:
– in an excellent technical status
– in original status without unauthorised modifications, except for the adapta­

tions described in this documentation

– within the limits of the product defined through the technical data.
Outside of industrial environments, e.g. in commercial and mixed-residential
areas, actions to suppress interference may have to be taken.

You will find detailed information in the following documentation:

– Description on the module (

è

 CPX-FB36-…)

– CPX system description (

è

 P.BE-CPX-SYS-…).

EtherNet/IP

®

, MODBUS

®

, SPEEDCON

®

 are registered trademarks of the

respective trademark holder in certain countries.

2

Safety

 Before assembly or installation work, switch off the power supply, switch off the

compressed air supply, exhaust any pneumatic components.

 For the electrical power supply, use only PELV circuits in accordance with

IEC 60204-1/EN 60204-1.

 Observe the handling specifications for electrostatically sensitive devices.
 Seal unused connections with cover caps to achieve the required degree of

protection.

 Use connection hardware with the required degree of protection.
 Observe specifications in the description for the module and the CPX system

description.

 Place only a completely mounted and wired CPX terminal into operation.

3

Connection and display components

1

2

3

4

1

LED indicators

2

Network connections [X1], [X2]

1)

3

DIL switches

4

Service interface

2)

1)

2× socket, M12, D-coded, 4-pin

2)

Socket, M12, A-coded, 5-pin; for the operator unit CPX-MMI or Festo Maintenance Tool CPX-FMT

Fig. 1

3.1 Network connections

There are two 4-pin, D-coded M12 sockets on the bus node for the network con­
nection. The sockets are compatible with SPEEDCON plugs. Both connections have
Auto-Negotiation and Crossover Detection (factory setting).

When crossover detection is activated, the bus node automatically
exchanges the transmitted and received data.
If Crossover detection is deactivated, assignment of the pins for transmit­
ted and received data at the XP2 connection is crossed. As a result, several
bus nodes in a row can each be connected with a patch cable.

Connection

1)

Pin

X1

2)

X2

2)

Signal

Explanation

Signal

Explanation

1

TD+

Transmitted
data +

RD+

Received data +

2

RD+

Received data +

TD+

Transmitted
data +

3

TD–

Transmitted
data –

RD–

Received data –

4

RD–

Received data –

TD–

Transmitted
data –

3)

Shield

Functional earth

Shield

Functional earth

1)

Socket, M12, D-coded, 4-pin

2)

Pin activation with deactivated crossover detection

3)

Housing; equipotential bonding 

è

 CPX system description P.BE-CPX-SYS-…

Fig. 2

If the QuickConnect function has been activated, the crossover detection
function is not available.

3.2 LED indicators – normal operating status

Behaviour of the LED indicators in normal operating status:
– The green LEDs [PS], [PL], [MS] and [NS] are illuminated.
– The green LEDs [TP1] and/or [TP2] light up or flash.
– The red LED [SF] is off.

The yellow LED [M] lights up only when “System start with saved paramet­
erisation and CPX extension” is set.

Network-specific LED indicators

1)

CPX-specific LED indicators

2)

MS (red, green) Module status

PS (green)

Power system

NS (red, green)

Network status

PL (green)

Power load

TP1 (green)

“Link/traffic” X1

SF (red)

System Failure

3)

TP2 (green)

“Link/traffic” X2

M (yellow)

Modify

4)

1)

Detailed information (

è

 Description on the module CPX-FB36-…)

2)

Detailed information (

è

 CPX system description P.BE-CPX-SYS-…)

3)

Flashes in case of error, error diagnostics (

è

 CPX system description P.BE-CPX-SYS-…)

4)

Parameterisation revised or “Force” active.

Fig. 3

4

Mounting and removal

Warning

Uncontrolled movements of the actuators and loose tubing, undefined switching
states of the electronic components
Injury caused by moving parts, damage to machine and to system
Before mounting and installation work:
 Switch off the power supply.
 Switch off the compressed air supply.
 Exhaust any pneumatic components.

2

1

3

2

1

Bus node CPX-FB36

2

Screw

3

Interlinking block

Fig. 4