background image

Network-specific data

Maximum cable length per
segment

[m]

100

Cable specification

Cable type

Ethernet twisted pair cable, shielded

Transmission class

Category Cat 5 or higher

Cable diameter

[mm]

6 … 8

Wire cross section

[mm

2

]

0.14 … …0.75; 22 AWG

2)

1) Based on the Ethernet protocol IEEE 802.3
2) required for maximum connection length between network participants

Tab. 14 Network-specific Data

13.2

Technical Data UL/CSA Certification

Ambient conditions UL/CSA

Pollution degree

3

Installation site

for indoor use only

Max. installation height

[m]

2000

Tab. 15 Ambient Conditions UL/CSA

Ambient temperature

Mounting position

Vertical

Horizontal

Operating power supply U

EL/SEN

 via XD

Ambient temperature, max. current rating
of terminal strip 

£

 4 A

[°C]

–5 … +60

–5 … +50

Ambient temperature, max. current rating
of terminal strip 

>

 4 … 8 A

[°C]

–5 … +50

–5 … +40

Operating voltage U

EL/SEN

 with feed via both connections [XD]

1)

Ambient temperature, max. current rating
of terminal strip 

>

 4 … 8 A

[°C]

–5 … +60

–5 … +50

1) see chapter 'Product design' or 'Connection elements'

Tab. 16 Ambient temperature ranges