background image

Translation of the original instructions

© 2020 all rights reserved to Festo SE & Co. KG

EtherNet/IP

®

, MODBUS

®

 are registered trademarks of the respective trademark

owners in certain countries.

1

About this document

This document describes the use of the above-mentioned product.
Certain aspects of use are described in other documents and must be observed

è

 1.1 Applicable Documents.

1.1

Applicable Documents

All available documents for the product 

è

 www.festo.com/pk.

Document

Contents

Description of the automation system CPX-E
(CPX-E-SYS)

Detailed description of the
automation system CPX-E

Instruction manual for automation system CPX-E
(CPX-E-SYS)

Instruction manual and important information on
assembly, electrical installation and mainten-
ance tasks for an automation system CPX-E

Description of the bus module CPX-E-EP
(CPX-E-EP)

Detailed description of product function and
parameterisation options

Device description file (EDS)

Definition of the modules of an
automation system CPX-E for integration into the
higher-order controller

Documentation of the components in an
automation system CPX-E and the connected
peripherals

Information on using the components

Documentation for the higher-order controller
and the additional participants in the network

Information on commissioning and paramet-
erisation of the components

Tab. 1 Applicable Documents

1.2

Product version

This document refers to the following product versions:

Product

Version

CPX-E-EP

Bus module CPX-E-EP, revision 1 or later

Tab. 2 Product version
The product version can be identified from the product labelling or with the help
of appropriate software from Festo.

Appropriate software for determining the product version can be found in the
Festo Support Portal 

è

 www.festo.com/sp.

Information on using the software can be found in the integrated Help function.

There may be an updated version of this document for these or later product ver-
sions 

è

 www.festo.com/sp.

1.3

Product labelling

The product labelling is located on the left-hand side of the module. Scanning the
printed Data Matrix Code with an appropriate device opens the Festo Support
Portal, with the information appropriate for the product. Alternatively, the Product
Key (11-digit alphanumeric code on the product labelling) can be entered in the
search field of the Support Portal.

You can find detailed information on the product labelling in the description of the
module 

è

 1.1 Applicable Documents.

1.4

Specified standards

Version status

EN 60529:2013-10

IEC 60204-1:2014-10

EN 61000-6-2:2005-08

IEEE 802.3:2014-00

EN 61000-6-4:2007-01

NE 21:2012-05

Tab. 3 Standards specified in the document

1.5

UL/CSA Certification

In combination with the UL inspection mark on the product, the information in this
section must also be observed in order to comply with the certification conditions
of Underwriters Laboratories Inc. (UL) for USA and Canada.

UL certification information

Product category code

NRAQ/NRAQ7

File number

E239998

Considered standards

UL 61010-1, 3rd Edition, May 11, 2012, revised April 29, 2016
CAN/CSA-C22.2 No. 61010-1-12, 3rd Edition, revision dated April
29, 2016
UL 61010-2-201, 1st Edition, revised February 20, 2017
CSA-C22.2 No. 61010-2-201: 14, 1st Edition, issue date January
01, 2014

UL mark

Tab. 4 UL/CSA Certification Information

Technical data and environmental conditions may be subject to change in
order to comply with Underwriters Laboratories Inc. (UL) certification require-
ments for the USA and Canada.
Observe deviations 

è

 Technical data.

The unit shall be supplied by a power source which fulfils the requirements
on a limited-energy circuit in accordance to IEC/EN/UL/CSA 61010-1 or on a
Limited Power Source (LPS) in accordance to IEC/EN/UL/CSA 60950-1 or
IEC/EN/UL/CSA 62368-1 or a Class 2 circuit in accordance to NEC or CEC.

Unauthorised access to the device can cause damage or malfunctions.
When connecting the device to a network:
Protect the network against unauthorised access.
Measures to protect the network include: 

Firewall

Intrusion Prevention System (IPS)

Network segmentation

Virtual LAN (VLAN)

Virtual private Network (VPN)

Security at physical access level (port security)

For additional information 

è

 Guidelines and standards for security in information

technology, e. g. IEC 62443, ISO/IEC 27001.

An access password only protects against unintentional modification.

NOTICE!

Modules with Ethernet interfaces should only be operated in networks if all con-
nected network components are supplied by PELV circuits or integrated circuits
with equivalent protection.

2

Safety

2.1

Safety instructions

Take into consideration the legal regulations for the respective destination.

Use the product only within the defined values

è

 13 Technical Data

è

 Tab. 17 Ambient Conditions UL/CSA.

Observe labelling on the product.

Observe further applicable documents.

Store the product in a cool, dry, UV-protected and corrosion-protected envir-
onment. Ensure that storage times are kept to a minimum.

Before working on the product: switch off the power supply and secure it
against being switched on again.

Comply with the handling specifications for electrostatically sensitive devices.

2.2

Intended Use

The product described in this document is intended only for use as an interface
between an Automation system CPX-E and a higher-order controller through
integration in a network with the protocols EtherNet/IP or Modbus TCP.

8126550

CPX-E-EP

Bus module

8126550
2020-01a
[8126552]

Instructions | Operating

Festo SE & Co. KG 
Ruiter Straße 82 
73734 Esslingen 
Germany
+49 711 347-0 

www.festo.com 

Summary of Contents for CPX-E-EP

Page 1: ...ombination with the UL inspection mark on the product the information in this section must also be observed in order to comply with the certification conditions of Underwriters Laboratories Inc UL for USA and Canada UL certification information Product category code NRAQ NRAQ7 File number E239998 Considered standards UL 61010 1 3rd Edition May 11 2012 revised April 29 2016 CAN CSA C22 2 No 61010 1...

Page 2: ...ting voltage supply UEL SEN PS green Load voltage supply UOUT PL green System error SF rot Force mode M yellow Fig 2 LED displays The network specific LED displays are described below è 11 3 LED Displays The system specific LED displays are described in the documents for the automa tion system CPX E è 1 1 Applicable Documents 5 2 3 Control Elements NOTICE Damage to internal electronics Damage to a...

Page 3: ...0 Service NOTICE Accumulation of heat due to reduced air supply to electronics Keep the ventilation slots free and regularly remove contamination 11 Diagnostics and fault clearance 11 1 Diagnostics options Various options are available for diagnosing errors Internal system diagnostics LED indicators on the product 11 2 Internal system diagnostics The internal system diagnostics is described in the...

Page 4: ...d NE 21 Assigned address space inputs outputs Without diagnostics bit With status bits bit 8 With I O diagnostics inter face bit 16 16 1 not including linking element 2 Including linking element 3 for non conforming technical data see UL operating conditions table UL Tab 14 General Technical Data Power supply Operating power supply UEL SEN V DC 24 _ 25 Intrinsic current consumption at nominal oper...

Reviews: