Festo CPX-E-CEC PN Instructions Download Page 5

Connection status [XF1], [XF2]

LED
(green)

Meaning

Remedy

Flashes

Module locating in progress when both
LEDs are flashing in synchronisation,
e.g. for troubleshooting or configuration.

Off

No connection at the respective port or
line not connected.

Check network connection.

Tab. 15 Connection Status [XF1], [XF2]

12

Disposal

ENVIRONMENT!

Send the packaging and product for environmentally sound recycling in accord-
ance with the current regulations 

è

 www.festo.com/sp.

13

Technical Data

13.1

General Technical Data

General technical data

General technical data
Automation system CPX-E

Description of automation system CPX-E

è

 1.1 Applicable Documents

Dimensions
(length x× width × height)

1)

[mm]

124.3 × 75.9 × 82.5

Product weight

2)

[g]

288

Mounting position

Vertical/horizontal

Ambient temperature with
vertical mounting position

[°C]

–5 … +60

3)

Ambient temperature with
horizontal mounting position

[°C]

–5 … +50

3)

Storage temperature

[°C]

–20 … +70

Humidity
(non-condensing)

[%]

0 … 95

Degree of protection in accordance with
EN 60529

IP20
The degree of protection is not UL-tested.

Protection against electric shock
(Protection against direct and indirect
contact in accordance with IEC 60204-1)

through the use of PELV circuits
(protected extra-low voltage)

Electromagnetic compatibility

To EN 61000-6-2/-4 and NE 21

Module code/sub-module code

CPX-E-CEC-C1-PN

222/100

CPX-E-CEC-M1-PN

222/101

Module identification

CPX-E-CEC-C1-PN

E-CEC-C1-PN

CPX-E-CEC-M1-PN

E-CEC-M1-PN

1) Including covering, not including linking element
2) Including linking element
3) for non-conforming technical data see UL operating conditions table UL

Tab. 16 General Technical Data

Power supply

Operating power supply
U

EL/SEN

[V DC]

24 

_

 25%

Intrinsic current consumption
at nominal operating voltage
24 V from U

EL/SEN

[mA]

130

Reverse polarity protection
24 V U

EL/SEN

 against 0 V

U

EL/SEN

Yes

Mains buffering time

[ms]

20

Tab. 17 Power Supply

Network-specific data

Protocol

PROFINET

1)

, EtherCAT

Specification

Standards and norms with reference to PROFINET:
IEC 61158
IEC 61784
IEC 61918

Transmission rate

[Mbps]

100

Crossover detection

Auto-MDI/MDI-X

Maximum cable length per
segment

[m]

100

Cable specification

Cable type

Ethernet twisted pair cable, shielded

Transmission class

Category Cat 5 or higher

Cable diameter

[mm]

6 … 8

Wire cross section

[mm

2

]

0.14 … …0.75; 22 AWG

2)

1) based on the Ethernet protocol IEEE 802.3
2) required for maximum connection length between network participants

Tab. 18 Network-specific Data

13.2

Technical Data UL/CSA Certification

Ambient conditions UL/CSA

Pollution degree

3

Installation site

for indoor use only

Max. installation height

[m]

2000

Tab. 19 Ambient Conditions UL/CSA

Ambient temperature

Mounting position

Vertical

Horizontal

Operating power supply U

EL/SEN

 via XD

Ambient temperature, max. current rating
of terminal strip 

£

 4 A

[°C]

–5 … +60

–5 … +50

Ambient temperature, max. current rating
of terminal strip 

>

 4 … 8 A

[°C]

–5 … +50

–5 … +40

Operating voltage U

EL/SEN

 with feed via both connections [XD]

1)

Ambient temperature, max. current rating
of terminal strip 

>

 4 … 8 A

[°C]

–5 … +60

–5 … +50

1) see chapter 'Product design' or 'Connection elements'

Tab. 20 Ambient temperature ranges