Electrical interface
CPX-CTEL-2-M12-5POL-LK
Festo SE
& Co.
KG
Ruiter Straße
82
73734
Esslingen
Germany
+49 711 347-0
www.festo.com
Brief description
Translation of the original instructions
8101617
2018-11a
[8101619]
Electrical interface CPX-CTEL-2-M12-5POL-LK
English
. . . . . . . . . . . . . . . . . . . . . .
For all available product documentation
è
www.festo.com/pk
1
Intended use
The module described in this document provides 2 outward interfaces to connect
devices with IO-Link interface (devices).
The module is intended for use in an industrial environment. Outside of industrial
environments, e.g. in commercial and mixed-residential areas, actions to suppress
interference may have to be taken.
The module is intended exclusively for use in CPX terminals from Festo for installa
tion in machines or automated systems and may be used only in the following
ways:
– in perfect technical condition
– in original status without unauthorised modifications, except for the adapta
tions described in this documentation
– within the limits of the product defined through the technical data.
IO-Link
®
is a registered trademark of its respective trademark holder in
certain countries.
2
Security
This documentation is directed exclusively toward technicians trained in control
and automation technology.
You can find detailed information in the description for the module
(P.BE-CPX-CTEL-2-M12-5POL-LK-…) as well as in the CPX system
description (P.BE-CPX-SYS-…).
Warning
Electric shock
Injury to people, damage to the machine and system
For the electrical power supply, use only PELV circuits in accordance with
IEC 60204-1 (Protective Extra-Low Voltage, PELV).
Observe the general requirements of IEC 60204-1 for PELV circuits.
Use only voltage sources that guarantee a reliable electrical disconnection of
operating and load voltage in accordance with IEC 60204-1.
Always connect all circuits for operating and load voltage supplies U
EL/SEN
,
U
VAL
and U
OUT
.
Note
Electrostatically sensitive devices
Do not touch any components.
Observe the handling specifications for electrostatically sensitive
devices.
Note
Take into account the specifications and notes in the description of the mod
ule and mounting instructions of the components.
Commission the module only if fully mounted and wired.
3
Connections and displays
1
2
3
4
5
1
Rating plate
2
CPX-specific LEDs
3
X3 and X4
4
Port 1 and port 2
5
Status LEDs for port 1 and port 2
1)
Equip with protective cap (without function)
2)
Connector socket: M12, A-coded, 5-pin
Fig. 1
3.1 Interfaces
Port
Pin
Allocation
Function
M12 socket, 5-pin
1
2
3
4
5
24 V U
EL/SEN
24 V U
VAL/OUT
0 V U
EL/SEN
C/Q
0 V U
VAL/OUT
Power supply (PS)
Load voltage supply (PL)
Power supply (PS)
Communication C/Q
Load voltage supply (PL)
Fig. 2
3.2 LED indicators
Status LEDs for port 1 and 2
CPX-specific LEDs
X1 … X2
(green/red)
Status port 1 and 2
Connection status OK, device
error, configuration error or
compatibility error
PS (green)
Operating voltage supply (Power
System)
PL (green)
Load voltage supply (Power Load)
(red)
CPX peripheral error
1)
Detailed information (
è
description for the module P.BE-CPX-CTE L-2-M12-5POL-LK-…)
2)
Detailed information (
è
CPX system description P.BE-CPX-SYS-…)
Fig. 3
4
Mounting and installation
Warning
Electric shock
Injury to people, damage to the machine and system
Switch off the power supply before mounting or dismantling the module
(danger of malfunctions or damage).
The module is mounted in an interlinking block of the CPX terminal.
2
3
1
1
Screws,
tightening torque: 0.9 … 1.1 Nm
2
Module
3
Interlinking block with contact rails
Fig. 4
4.1 Dismantling
Unscrew screws and carefully lift off the module.
Note
Material damage due to incorrect mounting
Select screws suited to the material of the interlocking block:
– plastic: Thread-cutting tapping screws
– metal: Screws with metric thread.
If an individual module without CPX terminal is ordered, both screw types are
included.